Plan Review Details - Permit 05041965
Plan Review Stops For Permit 05041965
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-19 Cont ID  
Sent By jgomez Date 2005-05-19 Time 09:55 Rev Time 0.25
Received By jgomez Date 2005-05-19 Time 09:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-05-02 Cont ID  
Sent By jwitmer Date 2005-05-02 Time 16:25 Rev Time 1.11
Received By jwitmer Date 2005-05-02 Time 16:25 Sent To PC
Notes
2005-05-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05041965
 CONT:3610 EMBASSY DR
 TEL: (561)683-4262
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1507.10.1 DECK REQUIREMENTS. WOOD
 SHAKES SHALL ONLY BE USED ON SOLID
 OR SPACED SHEATHING.WHERE SPACED
 SHEATHING IS USED, SHEATHING BOARDS
 SHALL NOT BE LESS THAN 1 INCH X 4
 INCHES (25 MM X 102 MM) NOMINAL
 DIMENSIONS AND SHALL BE SPACED ON
 CENTERS EQUAL TO THE WEATHER EXPOSURE
 TO COINCIDE WITH THE PLACEMENT OF
 FASTENERS.WHERE 1-INCH X 4-INCH (25
 MM X 102 MM) SPACED SHEATHING IS
 INSTALLED AT 10 INCHES (254 MM) ON
 CENTER, ADDITIONAL 1-INCH X 4-INCH (25
 MM X 102 MM) BOARDS SHALL BE
 INSTALLED BETWEEN THE SHEATHING
 BOARDS.
  
 IN REVIEWING THIS ROOFING PERMIT USING
 THE EXISTING SPACED SHEATHING, 1X6 WITH
 A SPACE OF APPROX 3" THE BUILDING
 OFFICIAL GAVE THREE OPTIONSFOR ACHIEVING
 CODE COMPLIANCE:
  
 1)UNDER ALTERNATE METHODS AND MATERIALS
 THE ABOVE MENTIONED SPACED SHEATHING CAN
 BE USED, PROVIDED THAT AN ENGINEER WILL
 PROVIDE CALCULATIONS OF HOW THE ROOF
 DIAPHRAM CAN BE MET USING THIS METHOD.
  
 2) IF SPACED SHEATHING IS TO BE LEFT IN
 PLACE & SHEATHING IS TO BE APPLIED
 DIRECTLY OVER THE 1X6. FIRST 5/8"
 PLYWOOD OR STRUCTURAL PANELS IS THE
 MINIMUM THICKNESS TO BRING THE ROOF UP
 TO MEET THE CURRENT CODE. SECOND AN
 ENGINEER WILL HAVE TO CALCULATE THE
 LENGHT AND SPACING OF FASTENERS, AND
 ALSO EVALUATE IF BLOCKING WILL BE
 REQUIRED OVER THE TRUSS TO CREATE SOLID
 BACKING FOR THE SHEATHING NAILING.
  
 3) THE THIRD OPTION WILL BE TO REMOVE
 THE SPACED SHEATHING TOTALY & REPLACE
 WITH 5/8" CDX PLYWOOD.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-04-29 Cont ID  
Sent By shill Date 2005-04-29 Time 14:34 Rev Time 0.00
Received By shill Date 2005-04-29 Time 14:34 Sent To PC
Notes
2005-04-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE ATTACHED FBC TABLE 2306.1 AND
 FBC TABLE 2307.6B, NOTE 6, CITY OF WEST
 PALM BEACH AMENDMENTS."IN NO CASE
 SHALL ANY ROOF SHEATHING BE LESS THAN
 32/16 - 19/32 INICH WOOD STRUCTURAL
 PANELS IN SPANS 16 INCHES OR MORE ON
 CENTER."SHOW COMPLIANCE.
  
 2.)A LOCAL PRODUCT APPROVAL HAS BEEN
 ISSUED FOR THE FRASER CEDAR SHAKE, SEE
 ATTACHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By shill Date 2005-04-26 Time 15:51 Rev Time 0.50
Received By shill Date 2005-04-26 Time 15:51 Sent To PC
Notes
2005-04-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NOTICE OF COMMENCEMENT IS TO
 INCLUDE DESCRIPTION OF THE PROPERTY,
 ITEM #1.THIS IS THE LEGAL DESCRIPTION
 (LOT/BLOCK/SUBDIVISION NAME) ALONG WITH
 ADDRESS IF AVAILABLE.PLEASE READ
 FS713.13.
  
 2.)THE APPLICATION IS TO INCLUDE ROOF
 DECK TYPE, MEAN ROOF HEIGHT.
  
 3.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.