Plan Review Details - Permit 05041903
Plan Review Stops For Permit 05041903
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-03 Cont ID  
Sent By btrobaug Date 2005-06-03 Time 15:52 Rev Time 0.50
Received By btrobaug Date 2005-06-03 Time 14:59 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-09 Cont ID  
Sent By btrobaug Date 2005-05-09 Time 16:59 Rev Time 0.50
Received By btrobaug Date 2005-05-09 Time 13:36 Sent To M
Notes
2005-05-09 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} A DISCONNECT MUST BE INSTALLED PRIOR
 TO CONDUCTORS ENTERING THE BUILDING PER
 225.31 & 225.32.
  
 2} THE SITE PLAN DOES NOT SHOW THE
 LOCATION OF THE NEW 125 AMP PANEL.
  
 3} THE RISER DOES NOT SHOW THE UTILITY
 SOURCE CONNECTION. IF BEING ROUTED TO
 THE ATS THAT EQUIPMENT MUST BE LISTED
 PER 225.36 AND 230.66.
  
 4} DISCONNECTS MUST BE GROUPED PER
 230.72.
  
 5} IDENTIFICATION MUST BE INSTALLED PER
 225.37.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 PLEASE NOTE THAT A GAS APPLICATION MUST
 BE SUBMITTED FOR REVIEW PRIOR TO PERMIT
 BEING ISSUED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-05-21 Cont ID  
Sent By kstevens Date 2005-05-21 Time 06:02 Rev Time 0.25
Received By kstevens Date 2005-05-21 Time 06:02 Sent To  
Notes
2005-05-21 00:00:00GAS APPLICATION # 05051032

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 15:43 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 15:43 Sent To E
Notes
2005-05-31 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 10:59 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 10:59 Sent To E
Notes
2005-05-03 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 14:09 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 14:09 Sent To Z
Notes
2005-04-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-05-10 Cont ID  
Sent By hmoser Date 2005-05-10 Time   Rev Time 0.00
Received By hmoser Date 2005-05-10 Time 17:06 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-29 Cont ID  
Sent By mmclean Date 2005-04-29 Time 19:00 Rev Time 0.00
Received By mmclean Date 2005-04-29 Time 19:00 Sent To I
Notes
2005-04-29 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.