2005-05-05 00:00:00 | DENIED |
| REFERENCE: FBC-2001 FUEL GAS |
| FBC-2001 CHAPTE 1 |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| 2. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| 4. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| 5) A RESIDENTIAL GENERATOR PERMIT SHALL |
| BE APPLIED FOR BY THE CONTRACTOR THAT |
| SETS AND HOOKS UP THE GENERATOR. THE |
| FOLLOWING INFORMATION IS REQUIRED: |
| A. A SURVEY/SITE PLAN IS REQUIRED |
| SHOWING THE LOCATION OF THE GENERATOR |
| AND THE SET BACKS FOR THE PROPERTY LINE. |
| THE DISTANCE FROM ALL OPENINGS IN THE |
| STRUCTURE SHALL BE SHOWN ON THE PLAN. |
| B. REVIEWS BY THE FOLLOWING ARE |
| REQUIRED PRIOR TO ANY PERMIT BEING |
| ISSUED FOR THE GENERATOR. ZONING, |
| MECHANICAL, ELECTRIC, BUILDING, AND FUEL |
| GAS. |
| 6) ALL INFORMATION, DRAWINGS, |
| SPECIICATIONS AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN . |
| SECTION 104.2.1. |
| |