Plan Review Stops For Permit 05040925 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2006-01-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-01-26 |
Time |
19:00 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-01-26 |
Time |
18:53 |
Sent To |
PC |
|
Notes |
2006-01-27 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- NEED TO APPLY FOR STORM SHUTTERS | | PERMIT AS AGREED ON PROVISO. | | | | ***CASEMENT WINDOWS PRODUCT APPROVALS | | AND BBQ HOOD OK. SLIDING GLASS DOORS | | PERMIT ALREADY APPLIED AND APPROVED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2005-11-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-11-14 |
Time |
15:00 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2005-11-14 |
Time |
15:00 |
Sent To |
PC |
|
Notes |
2005-11-14 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | 1- NEED TO PROVIDE COMPLETE INFORMATION | | FOR NON-IMPACT SLIDING GLASS DOORS, | | CASEMENT WINDOWS AND SHUTTERS UNDER A | | SEPARATE PERMIT AS AGREED ON PROVISO | | DATED 9-9-05. SEE ATTACHED COPY. | | | | 2- PROVIDE COMPLETE SPECS AND LISTING | | FOR OUTDOOR USE OF THE BBQ HOOD. | | | | 3- OWES $60.00 FOR REVISION FEES AS | | NOTED ON PROVISO DATED 9-9-05.SEE | | ATTACHED COPY. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2005-09-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-09-09 |
Time |
13:02 |
Rev Time |
1.50 |
Received By |
jgomez |
Date |
2005-09-09 |
Time |
13:02 |
Sent To |
PC |
|
Notes |
2005-09-09 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- AS AGREED WITH G.C., PROVIDE INFO FOR | | NON-IMPACT SLIDING GLASS DOORS, CASEMENT | | WINDOWS (NON-IMPACT) AND SHUTTERS UNDER | | SEPARATE PERMITS. | | 2- PROVIDE COMPLETE SPECS FOR BBQ HOOD | | FOR EXTERIOR USE & SPECIFIC GRILL MODEL. | | 3- SHEET A3: SPECIFY TRUSS CONNECTOR FOR | | GIRDER TRUSS RESTING ON POST BY MASTER | | BEDRM VESTIBULE. REVISION FEES APPLY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2005-08-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-08-15 |
Time |
17:51 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2005-08-15 |
Time |
17:51 |
Sent To |
PC |
|
Notes |
2005-08-15 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- CLARIFY IF USING STORM SHUTTERS OR | | IMPACT GLAZING. THERE IS A NOTE ATTACHED | | TO THE SUBMITTAL SAYING THAT SHUTTERS | | UNDER A SEPARATE PERMIT. SOME PRODUCT | | APPROVALS ARE IMPACT AND SOME ARE NON | | IMPACT. WHICH WAY IS GOING TO BE. | | SHUTTERS OR IMPACT GLAZING?. | | | | 2- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | 3- A) PROVIDE COMPLETE SPECS AND | | APPROVED LISTING FOR THE GRILL. | | INCLUDING MODEL TO BE INSTALLED. | | | | B) PROVIDE COMPLETE SPECS AND APPROVED | | LISTING FOR HOOD FOR EXTERIOR USE. ONE | | SUBMITTED IS NOT LISTED FOR EXTERIOR USE | | | | 4- SLIDING GLASS DOORS: A) LOCAL PRODUCT | | APPROVAL APPLICATION IS UNDER REVIEW BY | | THE BUILDING OFFICIAL. CONTACT LUIS | | MARTINEZ AT 805-6712. | | | | B) NOA SUBMITTED IS INCOMPLETE. MISSING | | SOME DRAWINGS. | | | | 5- PROVIDE FLORIDA/LOCAL PRODUCT | | APPROVAL FOR ENTRY DOORS. | | | | 6- SHEET A3: SPECIFY TRUSS CONNECTOR FOR | | GIRDER TRUSS RESTING ON (3)2X6 POSTBY | | MASTER BEDROOM VESTIBULE. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-07-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-07-06 |
Time |
17:16 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2005-07-06 |
Time |
17:16 |
Sent To |
Z |
|
Notes |
2005-07-06 00:00:00 | SECOND CHECKLIST: | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | 2- THERE ARE COMPANIES WHO HAVE DESIGNED | | BBQ'S SPECIFICALLY FOR LANAI OR PORCH | | AND THEY REQUIRE EXHAUST HOOD. THE | | BUILDING OFFICIAL NEEDS TESTING AND | | ENGINEERING TO SUPPORT STATEMENT ON | | LETTER THAT EXHAUST HOOD IS NOT | | REQUIRED. ALSO, LETTER IS NOT ACCEPTABLE | | BECAUSE IT'S SIGNED BY NOBODY. | | | | 3- CLARIFY IF USING STORM SHUTTERS OR | | DOORS WITH IMPACT GLAZING. SLIDING GLASS | | DOORS PRODUCT APPROVAL SUBMITTED HAVE | | IMPACT GLAZING. | | CLARIFY WHICH OPENINGS WILL HAVE | | SHUTTERS OR NOT. | | PROVIDE COMPLETE SHUTTERS INFORMATION OR | | APPLY UNDER A SEPARATE PERMIT. STILL, | | CLARIFY OPENINGS TO HAVE SHUTTERS. | | | | 4- SHEET A3: A) REVISE/UPDATE TRUSS | | ANCHOR SCHEDULE (NOT DONE FROM PREVIOUS | | CHECKLIST). SEE LATEST CATALOGUE THAT | | WAS REVISED TO COMPLY WITH SEC. 1609.4.3 | | FBC 2001. OTHERWISE, PROVIDE TESTING AND | | ENGINEERING FOR NAIL SIZE AND NUMBER | | THAT DIFFER FROM THOSE TESTED AND | | PUBLISHED BY THE MANUFACTURER. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | B) CONNECTOR THD210 IS A WOOD TO WOOD | | CONNECTOR. NEED MASONRY HANGER. SEE | | CATALOGUE FOR PROPER MASONRY CONNECTOR. | | | | C) DETAIL E/A3: CLARIFY WHY HAVING 6" | | BOLTS INTO CONCRETE IF THERE IS NOT | | CONCRETE WALL TO BE ATTACHED TO.SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | 5- A)FLORIDA PRODUCT APPROVAL FOR CORNER | | | | SLIDING GLASS DOORS AND DADE COUNTY NOA | | SUBMITTED DON'T CORRESPOND TO EACH OTHER | | | | B) CLARIFY IF USING DOORS WITH IMPACT | | GLASS OR NOT AND PROVIDE CORRECT FLORIDA | | PRODUCT APPROVAL. | | | | 6- MULLION SIZE SPECIFIED FOR FIXED | | WINDOWS AT LIVING ROOM IS NOT GOOD. SEE | | DESIGN PRESSURES ON PLANS AND ON | | PRODUCT APPROVAL. REVISE MULLION SIZE | | AND ANCHOR AS REQUIRED AND PROVIDE | | PROPER FLORIDA PRODUCT APPROVAL FOR EACH | | TYPE OF MULLIONS. | | | | 7- DADE COUNTY NOA SUBMITTED FOR | | CASEMENT WINDOWS DOESN'T MATCH NOA | | SUBMITTED FOR FLORIDA PRODUCT APPROVAL. | | PROVIDE MATCHING NOA AND VERIFY THAT | | ASSEMBLY MATCHES ONE SHOWN ON PLANS TOO. | | | | 8- REAR ELEVATION DOESN'T MATCH FLOOR | | PLAN. SEE WINDOWS SPECIFIED ON PLAN FOR | | LIVING ROOM AREA AND REVISE AS REQUIRED. | | | | 9- PROVIDE FLORIDA PRODUCT APPROVAL FOR | | IMPACT GLASS CASEMENT WINDOW AT | | BREAKFAST AREA. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. | | | | 7- |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-05-31 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-05-31 |
Time |
16:51 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2005-05-31 |
Time |
16:51 |
Sent To |
PC |
|
Notes |
2005-05-31 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | 2- SHEET T1: A) UPDATE GENERAL NOTES. | | SEE COMMENTS ON PLANS AND RETURN | | REVIEWED PAGE AFTER CORRECTIONS ARE DONE | | TO EXPEDITE THE REVIEW PROCESS. | | | | B) DESIGN PARAMETERS. CLARIFY WHERE IS | | THE BASIC VELOCITY PRESSURE TAKEN FROM. | | THIS IS NO APPLICABLE TO THE FBC. SEE | | CHAPTER 16 FBC 2001. (THIS WAS | | APPLICABLE TO THE SBC 1997) | | ALSO, CLARIFY WHY THE MIN. SOIL BEARING | | PRESSURE IS: NA? | | | | 3- PROVIDE COMPLETE SPECS FOR BBQ | | SHOWING THAT IT WAS DESIGNED TO BE | | INSTALLED IN THE PORCH. SEC.2808 FBC | | 2001. | | | | 4- PROVIDE COMPLETE INFORMATION FOR | | STORM SHUTTERS OR APPLY FOR A SEPARATE | | PERMIT. | | | | 5- SHEET A1: A) SPECIFY COLUMNS AT BAY | | WINDOW AT MASTER BEDROOM. | | | | B) WHAT IS TS-2 SPECIFIED ON CONCRETE | | PAD BETWEEN GARAGE AND BEDROOM #2. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC. | | | | C) DETAIL 5 FOR FOOTING BETWEEN GARAGE | | AND CLUB ROOM DON'T MATCH. REVISE AS | | REQUIRED. | | | | 6) REVISE SIZESFOR FIXED WINDOW AT | | LIVING ROOM (36" X 234" FG ?). | | | | 7) SHEET A3: A) REVISE/UPDATE TRUSS | | ANCHOR SCHEDULE. SEE LATEST CATALOGUE | | WHICH WAS REVISED TO COMPLY WITH SEC. | | 1609.4.3 FBC 2001. PROVIDE COMPLETE | | ENGINEERING CALCULATIONS FOR FASTENERS | | THAT DIFFER FROM THOSE TESTED AND | | PUBLISHED BY MANUFACTURER. | | | | B) CONNECTOR THD210 IS A WOOD TO WOOD | | CONNECTOR. NEED MASONRY HANGER. SEE | | CATALOGUE FOR PROPER MASONRYCONNECTOR. | | | | C) DETAIL E/A3: CLARIFY WHY HAVING 6" | | BOLTS INTO CONCRETE. THERE IS NOT | | CONCRETE WALL TO BE ATTACHED TO? SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | 8- PROVIDE FLORIDA OR APPLY FOR LOCAL | | PRODUCT APPROVAL FOR SLIDING GLASS DOORS | | WITH CORNER ASSEMBLY AS SHOWN ON PLANS. | | | | 9-WINDOW AND DOOR MULLIONS: CLEARLY | | INDICATE MULLION SIZE AND FASTENERS TO | | BE USED TO VERIFY THAT IT MEETS THE | | DESIGN PRESSURES CALCULATED ON PLANS. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | 2001. | | | | 10- DADE COUNTY NOA SUBMITTED FOR | | CASEMENT WINDOWS DOESN'T MATCH NOA | | SUBMITTTED FOR FLORIDA PRODUCT APPROVAL. | | PROVIDE MATCHING NOA. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2006-10-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-16 |
Time |
20:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-16 |
Time |
20:31 |
Sent To |
PC |
|
Notes |
2006-10-16 20:38:46 | REDLINED AHU IN CLOSET FOR OCP PER 240.24D |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2006-06-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-07 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-07 |
Time |
15:59 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-05-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-05-09 |
Time |
20:00 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-05-09 |
Time |
19:56 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-04-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-04-24 |
Time |
18:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-04-24 |
Time |
16:02 |
Sent To |
PC |
|
Notes |
2006-04-24 00:00:00 | **** UNSAT **** | | | | 1) NOTE: PLEASE SEE PLANS SHOWS TWO | | PANEL "A", THIS APPEARS TO BE A MISPRINT | | AND WOULD HAVE BEEN REDLINED, HOWEVER | | PLANS ARE COMING BACK FOR OTHER | | COMMENTS, PLEASE CORRECT AT THIS TIME. | | | | 2) NOTE: PLEASE SEE 110.26 FOR MIN | | CLEARNECES REQUIRED FOR THE DISCONNECTS | | SHOWN FOR CU'S. | | PLEASE SEE DISC'S ARE SHOWN BEHIND | | UNITS. | | | | 3) NOTE: PLEASE SEE SD IN MASTER BEDRM | | IS REQUIRED TO BE LOCATED IN THE HIGHEST | | POINT OF THE TRAY/FLAT CECILING. | | NFPA-72 11.8.3.5 | | | | 4) NOTE: PLEASE SEE NOTES MENTIONS THE | | OLD SFBC FOR SD REQUIREMENTS. THIS | | SHOULD REFERENCE THE 2002 NFPA-72 | | 11.5.1.1. | | | | 5) NOTE: PLEASE SEE WHAT APPEARS TO BE | | HI-HAT LOADS ON PANEL SCHEDULE(S) WHICH | | ARE SHOWN ON ONE CIRCUIT. PLEASE SEE | | PANEL "A" INDICATES HI-HATS, YET PANEL | | "B" ONLY INDICATE STHE LOAD AND ONE | | CIRCUIT. | | PLEASE SEE LOADS ONLY NEED BE ADDED TO | | SERVICE, AS CIRCUITING FOR THESE MAY BE | | IN WITH THE OTHER CIRCUITS. IF THESE ARE | | INDEED DEDICATED CIRCUITS, PLEASE LABEL | | AND KNOW, A MAX OF 1440VAIS PERMITTED | | ONA 15A CIRCUIT. | | IF THIS ONLY FOR LOADS ADDED, THIS CAN | | BE LISTED IN LOAD CALCS FOR PANELS. | | 215.5 | | | | 6) NOTE: PLEASE SEE MISSING SW/LT FOR | | AHU ABOVE WIC AT GUEST SUITE LOCATION. | | 210.70. | | | | 7) NOTE: PLEASE SEE RECEPT LOCATED IN | | BATH BY VESTIBULE TO BE SHOWN AS GFI/GFI | | PROTECTED. 210.8A2 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2005-04-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-04-25 |
Time |
11:46 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2005-04-25 |
Time |
11:46 |
Sent To |
M |
|
Notes |
2005-04-25 00:00:00 | ** PROVISO ** | | | | 1)NOTE: PLEASE SEE PANEL "C" SHOWN ON | | RISER IS NOT SHOWN ON PLANS. | | | | 2)NOTE: PLEASE SEE RECEPT SHOWN IN | | GARAGE WITHOUT GFI INDICATION. | | 210.8A3 | | | | PLEASE REVISE THE ABOVE ALONG WITH ANY | | OTHER CHANGES BEFORE ROUGH ELECTRICAL | | INSPECTION. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
14 |
Status |
N |
Date |
2006-12-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-04 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-04 |
Time |
15:39 |
Sent To |
P |
|
Notes |
2006-12-04 15:39:51 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
13 |
Status |
N |
Date |
2006-10-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-14 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-14 |
Time |
14:02 |
Sent To |
E |
|
Notes |
2006-10-14 14:02:53 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2006-05-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-05-25 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-05-25 |
Time |
16:33 |
Sent To |
E |
|
Notes |
2006-05-25 00:00:00 | TO "E" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2006-05-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-05-03 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-05-03 |
Time |
14:21 |
Sent To |
E |
|
Notes |
2006-05-03 00:00:00 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2006-04-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-04-19 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-04-19 |
Time |
09:03 |
Sent To |
E |
|
Notes |
2006-04-19 00:00:00 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2006-01-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-01-22 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-01-22 |
Time |
12:48 |
Sent To |
B |
|
Notes |
2006-01-22 00:00:00 | TO "JGOMEZ" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2005-10-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-10-06 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-10-06 |
Time |
15:29 |
Sent To |
B |
|
Notes |
2005-10-06 00:00:00 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2005-09-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-01 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-01 |
Time |
14:39 |
Sent To |
B |
|
Notes |
2005-09-01 00:00:00 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2005-08-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-02 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-02 |
Time |
08:27 |
Sent To |
B |
|
Notes |
2005-08-02 00:00:00 | TO "JGOMEZ" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2005-07-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-28 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-28 |
Time |
11:30 |
Sent To |
Z |
|
Notes |
2005-07-28 00:00:00 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-07-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-07 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-07 |
Time |
13:58 |
Sent To |
M |
|
Notes |
2005-07-07 00:00:00 | TO "PKRAUSS" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-06-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-06-24 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-06-24 |
Time |
13:45 |
Sent To |
Z |
|
Notes |
2005-06-24 00:00:00 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-04-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-04-22 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-04-22 |
Time |
11:11 |
Sent To |
E |
|
Notes |
2005-04-22 00:00:00 | TO "SFR" "E" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-05-31 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-05-31 |
Time |
17:56 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2005-04-15 |
Time |
14:03 |
Sent To |
PC |
|
Notes |
2005-04-15 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2005-07-13 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-07-13 |
Time |
10:43 |
Rev Time |
0.50 |
Received By |
prafter |
Date |
2005-07-13 |
Time |
10:50 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2005-04-26 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-04-26 |
Time |
11:05 |
Rev Time |
0.50 |
Received By |
prafter |
Date |
2005-04-26 |
Time |
11:05 |
Sent To |
P |
|
Notes |
2005-04-26 00:00:00 | MECH. PLAN REVIEW. | | 1. SUPPLY AIR DUCT FROM AHU #1 SHOWES | | 12" FOR TWO DIST. TRINGALS,THEAN GOES TO | | 14". | | 2. RETURN AIR DUCT TO AHU #1 NOT SIZED. | | | | PLEASE CORRECT PLANS AND RESUMIT. | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | PATTY KRAUSS. | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2006-12-18 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-12-18 |
Time |
08:42 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2006-12-18 |
Time |
08:42 |
Sent To |
PC |
|
Notes |
2006-12-18 08:43:26 | REVISION: AS BUILT SANITARY RISER DIAGRAM |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-12-13 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-12-13 |
Time |
16:19 |
Rev Time |
0.45 |
Received By |
mperson |
Date |
2006-12-13 |
Time |
16:19 |
Sent To |
PC |
|
Notes |
2006-12-13 16:34:23 | REVISION DENIED | | REFERENCE: CHAPTER 481, FLORIDA STATUTES, PART 1 AND | | FLORIDA ADMINISTRATIVE CODE: | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1. PERMITTED SET OF DRAWINGS WERE SIGNED AND SEALED BY | | RANDALL STOFFT ARCHITECTS. PER CHAPTER 481, FLORIDA | | STATUTES, PART 1, ANY SUBMITTED REVISIONS NEED TO BE | | SIGNED AND SEALED BY SAID ARCHITECT. PLEASE REFERENCE | | THE FOLLOWING FLORIDA ADMINISTRATIVE CODE REQUIREMENTS | | FOR THE RESUBMITTAL. | | A) FAC-CODE-61G1-16001 ARCHITECT'S AND | | INTERIOR DESIGNER'S SEAL: | | EACH ARCHITECT AND INTERIOR DESIGNER | | SHALL ACQUIRE A SEAL WITH WHICH HE OR | | SHE SHALL IDENTIFY ALL PLANS, | | SPECIFICATIONS OR REPORTS PREPARED OR | | ISSUED BY HIM OR HER AND FILED FOR | | PUBLIC RECORD. THE SEAL SHALL BE OF A | | TYPE WHICH WILL MAKE AN IMPRESSION ON | | THE SURFACE OF PRINTS OR OTHER | | DUPLICATIONS OF DRAWINGS, AND AS | | APPROPRIATE, UPON SPECIFICATION PAGES, | | AND OTHER ARTICLES OF SERVICE. | | B) FAC-61G1-16.004 TITLE BLOCK: | | A TITLE BLOCK MUST APPEAR ON ALL | | ARCHITECTURAL OR INTERIOR DESIGN | | DRAWINGS AND SPECIFICATION | | IDENTIFICATION SHEETS. THE TITLE BLOCK | | MUST, AT A MINIMUM, CONTAIN THE | | FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE | | NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED | | SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE | | PERSON SEALING THE DOCUMENT. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2005-05-03 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-07-13 |
Time |
10:55 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2005-05-03 |
Time |
16:41 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2005-08-01 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-08-01 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-08-01 |
Time |
16:37 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2005-07-07 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-07-07 |
Time |
08:38 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-07-07 |
Time |
08:38 |
Sent To |
I |
|
Notes |
2005-07-07 00:00:00 | DENIED - RESUB - NEW SURVEYS | | 1. DOES NOT MEET THE SETBACK (SIDE). | | 2. NOT APART OF THE MINOR PD AMENDMENT | | FOR PARCEL FF. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2005-04-21 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-04-21 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-04-21 |
Time |
15:09 |
Sent To |
I |
|
Notes |
|
|