Plan Review Details - Permit 05040925
Plan Review Stops For Permit 05040925
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-01-27 Cont ID  
Sent By jgomez Date 2006-01-26 Time 19:00 Rev Time 0.50
Received By jgomez Date 2006-01-26 Time 18:53 Sent To PC
Notes
2006-01-27 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED TO APPLY FOR STORM SHUTTERS
 PERMIT AS AGREED ON PROVISO.
  
 ***CASEMENT WINDOWS PRODUCT APPROVALS
 AND BBQ HOOD OK. SLIDING GLASS DOORS
 PERMIT ALREADY APPLIED AND APPROVED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-11-14 Cont ID  
Sent By jgomez Date 2005-11-14 Time 15:00 Rev Time 0.50
Received By jgomez Date 2005-11-14 Time 15:00 Sent To PC
Notes
2005-11-14 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- NEED TO PROVIDE COMPLETE INFORMATION
 FOR NON-IMPACT SLIDING GLASS DOORS,
 CASEMENT WINDOWS AND SHUTTERS UNDER A
 SEPARATE PERMIT AS AGREED ON PROVISO
 DATED 9-9-05. SEE ATTACHED COPY.
  
 2- PROVIDE COMPLETE SPECS AND LISTING
 FOR OUTDOOR USE OF THE BBQ HOOD.
  
 3- OWES $60.00 FOR REVISION FEES AS
 NOTED ON PROVISO DATED 9-9-05.SEE
 ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-09 Cont ID  
Sent By jgomez Date 2005-09-09 Time 13:02 Rev Time 1.50
Received By jgomez Date 2005-09-09 Time 13:02 Sent To PC
Notes
2005-09-09 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- AS AGREED WITH G.C., PROVIDE INFO FOR
 NON-IMPACT SLIDING GLASS DOORS, CASEMENT
 WINDOWS (NON-IMPACT) AND SHUTTERS UNDER
 SEPARATE PERMITS.
 2- PROVIDE COMPLETE SPECS FOR BBQ HOOD
 FOR EXTERIOR USE & SPECIFIC GRILL MODEL.
 3- SHEET A3: SPECIFY TRUSS CONNECTOR FOR
 GIRDER TRUSS RESTING ON POST BY MASTER
 BEDRM VESTIBULE. REVISION FEES APPLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-15 Cont ID  
Sent By jgomez Date 2005-08-15 Time 17:51 Rev Time 2.00
Received By jgomez Date 2005-08-15 Time 17:51 Sent To PC
Notes
2005-08-15 00:00:00BUILDING REVIEW CHECKLIST:
 1- CLARIFY IF USING STORM SHUTTERS OR
 IMPACT GLAZING. THERE IS A NOTE ATTACHED
 TO THE SUBMITTAL SAYING THAT SHUTTERS
 UNDER A SEPARATE PERMIT. SOME PRODUCT
 APPROVALS ARE IMPACT AND SOME ARE NON
 IMPACT. WHICH WAY IS GOING TO BE.
 SHUTTERS OR IMPACT GLAZING?.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- A) PROVIDE COMPLETE SPECS AND
 APPROVED LISTING FOR THE GRILL.
 INCLUDING MODEL TO BE INSTALLED.
  
 B) PROVIDE COMPLETE SPECS AND APPROVED
 LISTING FOR HOOD FOR EXTERIOR USE. ONE
 SUBMITTED IS NOT LISTED FOR EXTERIOR USE
  
 4- SLIDING GLASS DOORS: A) LOCAL PRODUCT
 APPROVAL APPLICATION IS UNDER REVIEW BY
 THE BUILDING OFFICIAL. CONTACT LUIS
 MARTINEZ AT 805-6712.
  
 B) NOA SUBMITTED IS INCOMPLETE. MISSING
 SOME DRAWINGS.
  
 5- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR ENTRY DOORS.
  
 6- SHEET A3: SPECIFY TRUSS CONNECTOR FOR
 GIRDER TRUSS RESTING ON (3)2X6 POSTBY
 MASTER BEDROOM VESTIBULE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-06 Cont ID  
Sent By jgomez Date 2005-07-06 Time 17:16 Rev Time 2.00
Received By jgomez Date 2005-07-06 Time 17:16 Sent To Z
Notes
2005-07-06 00:00:00SECOND CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- THERE ARE COMPANIES WHO HAVE DESIGNED
 BBQ'S SPECIFICALLY FOR LANAI OR PORCH
 AND THEY REQUIRE EXHAUST HOOD. THE
 BUILDING OFFICIAL NEEDS TESTING AND
 ENGINEERING TO SUPPORT STATEMENT ON
 LETTER THAT EXHAUST HOOD IS NOT
 REQUIRED. ALSO, LETTER IS NOT ACCEPTABLE
 BECAUSE IT'S SIGNED BY NOBODY.
  
 3- CLARIFY IF USING STORM SHUTTERS OR
 DOORS WITH IMPACT GLAZING. SLIDING GLASS
 DOORS PRODUCT APPROVAL SUBMITTED HAVE
 IMPACT GLAZING.
 CLARIFY WHICH OPENINGS WILL HAVE
 SHUTTERS OR NOT.
 PROVIDE COMPLETE SHUTTERS INFORMATION OR
 APPLY UNDER A SEPARATE PERMIT. STILL,
 CLARIFY OPENINGS TO HAVE SHUTTERS.
  
 4- SHEET A3: A) REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE (NOT DONE FROM PREVIOUS
 CHECKLIST). SEE LATEST CATALOGUE THAT
 WAS REVISED TO COMPLY WITH SEC. 1609.4.3
 FBC 2001. OTHERWISE, PROVIDE TESTING AND
 ENGINEERING FOR NAIL SIZE AND NUMBER
 THAT DIFFER FROM THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 B) CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. NEED MASONRY HANGER. SEE
 CATALOGUE FOR PROPER MASONRY CONNECTOR.
  
 C) DETAIL E/A3: CLARIFY WHY HAVING 6"
 BOLTS INTO CONCRETE IF THERE IS NOT
 CONCRETE WALL TO BE ATTACHED TO.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5- A)FLORIDA PRODUCT APPROVAL FOR CORNER
  
 SLIDING GLASS DOORS AND DADE COUNTY NOA
 SUBMITTED DON'T CORRESPOND TO EACH OTHER
  
 B) CLARIFY IF USING DOORS WITH IMPACT
 GLASS OR NOT AND PROVIDE CORRECT FLORIDA
 PRODUCT APPROVAL.
  
 6- MULLION SIZE SPECIFIED FOR FIXED
 WINDOWS AT LIVING ROOM IS NOT GOOD. SEE
 DESIGN PRESSURES ON PLANS AND ON
 PRODUCT APPROVAL. REVISE MULLION SIZE
 AND ANCHOR AS REQUIRED AND PROVIDE
 PROPER FLORIDA PRODUCT APPROVAL FOR EACH
 TYPE OF MULLIONS.
  
 7- DADE COUNTY NOA SUBMITTED FOR
 CASEMENT WINDOWS DOESN'T MATCH NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
 PROVIDE MATCHING NOA AND VERIFY THAT
 ASSEMBLY MATCHES ONE SHOWN ON PLANS TOO.
  
 8- REAR ELEVATION DOESN'T MATCH FLOOR
 PLAN. SEE WINDOWS SPECIFIED ON PLAN FOR
 LIVING ROOM AREA AND REVISE AS REQUIRED.
  
 9- PROVIDE FLORIDA PRODUCT APPROVAL FOR
 IMPACT GLASS CASEMENT WINDOW AT
 BREAKFAST AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  
 7-

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-31 Cont ID  
Sent By jgomez Date 2005-05-31 Time 16:51 Rev Time 2.00
Received By jgomez Date 2005-05-31 Time 16:51 Sent To PC
Notes
2005-05-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SHEET T1: A) UPDATE GENERAL NOTES.
 SEE COMMENTS ON PLANS AND RETURN
 REVIEWED PAGE AFTER CORRECTIONS ARE DONE
 TO EXPEDITE THE REVIEW PROCESS.
  
 B) DESIGN PARAMETERS. CLARIFY WHERE IS
 THE BASIC VELOCITY PRESSURE TAKEN FROM.
 THIS IS NO APPLICABLE TO THE FBC. SEE
 CHAPTER 16 FBC 2001. (THIS WAS
 APPLICABLE TO THE SBC 1997)
 ALSO, CLARIFY WHY THE MIN. SOIL BEARING
 PRESSURE IS: NA?
  
 3- PROVIDE COMPLETE SPECS FOR BBQ
 SHOWING THAT IT WAS DESIGNED TO BE
 INSTALLED IN THE PORCH. SEC.2808 FBC
 2001.
  
 4- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 5- SHEET A1: A) SPECIFY COLUMNS AT BAY
 WINDOW AT MASTER BEDROOM.
  
 B) WHAT IS TS-2 SPECIFIED ON CONCRETE
 PAD BETWEEN GARAGE AND BEDROOM #2. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 C) DETAIL 5 FOR FOOTING BETWEEN GARAGE
 AND CLUB ROOM DON'T MATCH. REVISE AS
 REQUIRED.
  
 6) REVISE SIZESFOR FIXED WINDOW AT
 LIVING ROOM (36" X 234" FG ?).
  
 7) SHEET A3: A) REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE. SEE LATEST CATALOGUE
 WHICH WAS REVISED TO COMPLY WITH SEC.
 1609.4.3 FBC 2001. PROVIDE COMPLETE
 ENGINEERING CALCULATIONS FOR FASTENERS
 THAT DIFFER FROM THOSE TESTED AND
 PUBLISHED BY MANUFACTURER.
  
 B) CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. NEED MASONRY HANGER. SEE
 CATALOGUE FOR PROPER MASONRYCONNECTOR.
  
 C) DETAIL E/A3: CLARIFY WHY HAVING 6"
 BOLTS INTO CONCRETE. THERE IS NOT
 CONCRETE WALL TO BE ATTACHED TO? SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 8- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR SLIDING GLASS DOORS
 WITH CORNER ASSEMBLY AS SHOWN ON PLANS.
  
 9-WINDOW AND DOOR MULLIONS: CLEARLY
 INDICATE MULLION SIZE AND FASTENERS TO
 BE USED TO VERIFY THAT IT MEETS THE
 DESIGN PRESSURES CALCULATED ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001.
  
 10- DADE COUNTY NOA SUBMITTED FOR
 CASEMENT WINDOWS DOESN'T MATCH NOA
 SUBMITTTED FOR FLORIDA PRODUCT APPROVAL.
 PROVIDE MATCHING NOA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-10-16 Cont ID  
Sent By dpalmer Date 2006-10-16 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2006-10-16 Time 20:31 Sent To PC
Notes
2006-10-16 20:38:46REDLINED AHU IN CLOSET FOR OCP PER 240.24D

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-07 Cont ID  
Sent By dpalmer Date 2006-06-07 Time 16:06 Rev Time 0.00
Received By dpalmer Date 2006-06-07 Time 15:59 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 20:00 Rev Time 0.00
Received By dpalmer Date 2006-05-09 Time 19:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 18:53 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 16:02 Sent To PC
Notes
2006-04-24 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE PLANS SHOWS TWO
 PANEL "A", THIS APPEARS TO BE A MISPRINT
 AND WOULD HAVE BEEN REDLINED, HOWEVER
 PLANS ARE COMING BACK FOR OTHER
 COMMENTS, PLEASE CORRECT AT THIS TIME.
  
 2) NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARNECES REQUIRED FOR THE DISCONNECTS
 SHOWN FOR CU'S.
 PLEASE SEE DISC'S ARE SHOWN BEHIND
 UNITS.
  
 3) NOTE: PLEASE SEE SD IN MASTER BEDRM
 IS REQUIRED TO BE LOCATED IN THE HIGHEST
 POINT OF THE TRAY/FLAT CECILING.
 NFPA-72 11.8.3.5
  
 4) NOTE: PLEASE SEE NOTES MENTIONS THE
 OLD SFBC FOR SD REQUIREMENTS. THIS
 SHOULD REFERENCE THE 2002 NFPA-72
 11.5.1.1.
  
 5) NOTE: PLEASE SEE WHAT APPEARS TO BE
 HI-HAT LOADS ON PANEL SCHEDULE(S) WHICH
 ARE SHOWN ON ONE CIRCUIT. PLEASE SEE
 PANEL "A" INDICATES HI-HATS, YET PANEL
 "B" ONLY INDICATE STHE LOAD AND ONE
 CIRCUIT.
 PLEASE SEE LOADS ONLY NEED BE ADDED TO
 SERVICE, AS CIRCUITING FOR THESE MAY BE
 IN WITH THE OTHER CIRCUITS. IF THESE ARE
 INDEED DEDICATED CIRCUITS, PLEASE LABEL
 AND KNOW, A MAX OF 1440VAIS PERMITTED
 ONA 15A CIRCUIT.
 IF THIS ONLY FOR LOADS ADDED, THIS CAN
 BE LISTED IN LOAD CALCS FOR PANELS.
 215.5
  
 6) NOTE: PLEASE SEE MISSING SW/LT FOR
 AHU ABOVE WIC AT GUEST SUITE LOCATION.
 210.70.
  
 7) NOTE: PLEASE SEE RECEPT LOCATED IN
 BATH BY VESTIBULE TO BE SHOWN AS GFI/GFI
 PROTECTED. 210.8A2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 11:46 Rev Time 0.50
Received By dpalmer Date 2005-04-25 Time 11:46 Sent To M
Notes
2005-04-25 00:00:00** PROVISO **
  
 1)NOTE: PLEASE SEE PANEL "C" SHOWN ON
 RISER IS NOT SHOWN ON PLANS.
  
 2)NOTE: PLEASE SEE RECEPT SHOWN IN
 GARAGE WITHOUT GFI INDICATION.
 210.8A3
  
 PLEASE REVISE THE ABOVE ALONG WITH ANY
 OTHER CHANGES BEFORE ROUGH ELECTRICAL
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 15:39 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 15:39 Sent To P
Notes
2006-12-04 15:39:51TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 14:02 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 14:02 Sent To E
Notes
2006-10-14 14:02:53TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-05-25 Cont ID  
Sent By adarroug Date 2006-05-25 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-05-25 Time 16:33 Sent To E
Notes
2006-05-25 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 14:21 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 14:21 Sent To E
Notes
2006-05-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-04-19 Cont ID  
Sent By adarroug Date 2006-04-19 Time 09:03 Rev Time 0.00
Received By adarroug Date 2006-04-19 Time 09:03 Sent To E
Notes
2006-04-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:48 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:48 Sent To B
Notes
2006-01-22 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 15:29 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 15:29 Sent To B
Notes
2005-10-06 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 14:39 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 14:39 Sent To B
Notes
2005-09-01 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 08:27 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 08:27 Sent To B
Notes
2005-08-02 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 11:30 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 11:30 Sent To Z
Notes
2005-07-28 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 13:58 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 13:58 Sent To M
Notes
2005-07-07 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 13:45 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 13:45 Sent To Z
Notes
2005-06-24 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 11:11 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 11:11 Sent To E
Notes
2005-04-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-31 Cont ID  
Sent By jgomez Date 2005-05-31 Time 17:56 Rev Time 0.00
Received By jgomez Date 2005-04-15 Time 14:03 Sent To PC
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-13 Cont ID  
Sent By prafter Date 2005-07-13 Time 10:43 Rev Time 0.50
Received By prafter Date 2005-07-13 Time 10:50 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By prafter Date 2005-04-26 Time 11:05 Rev Time 0.50
Received By prafter Date 2005-04-26 Time 11:05 Sent To P
Notes
2005-04-26 00:00:00MECH. PLAN REVIEW.
 1. SUPPLY AIR DUCT FROM AHU #1 SHOWES
 12" FOR TWO DIST. TRINGALS,THEAN GOES TO
 14".
 2. RETURN AIR DUCT TO AHU #1 NOT SIZED.
  
 PLEASE CORRECT PLANS AND RESUMIT.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-12-18 Cont ID  
Sent By mperson Date 2006-12-18 Time 08:42 Rev Time 0.33
Received By mperson Date 2006-12-18 Time 08:42 Sent To PC
Notes
2006-12-18 08:43:26REVISION: AS BUILT SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-13 Cont ID  
Sent By mperson Date 2006-12-13 Time 16:19 Rev Time 0.45
Received By mperson Date 2006-12-13 Time 16:19 Sent To PC
Notes
2006-12-13 16:34:23REVISION DENIED
 REFERENCE: CHAPTER 481, FLORIDA STATUTES, PART 1 AND
 FLORIDA ADMINISTRATIVE CODE:
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PERMITTED SET OF DRAWINGS WERE SIGNED AND SEALED BY
 RANDALL STOFFT ARCHITECTS. PER CHAPTER 481, FLORIDA
 STATUTES, PART 1, ANY SUBMITTED REVISIONS NEED TO BE
 SIGNED AND SEALED BY SAID ARCHITECT. PLEASE REFERENCE
 THE FOLLOWING FLORIDA ADMINISTRATIVE CODE REQUIREMENTS
 FOR THE RESUBMITTAL.
 A) FAC-CODE-61G1-16001 ARCHITECT'S AND
 INTERIOR DESIGNER'S SEAL:
 EACH ARCHITECT AND INTERIOR DESIGNER
 SHALL ACQUIRE A SEAL WITH WHICH HE OR
 SHE SHALL IDENTIFY ALL PLANS,
 SPECIFICATIONS OR REPORTS PREPARED OR
 ISSUED BY HIM OR HER AND FILED FOR
 PUBLIC RECORD. THE SEAL SHALL BE OF A
 TYPE WHICH WILL MAKE AN IMPRESSION ON
 THE SURFACE OF PRINTS OR OTHER
 DUPLICATIONS OF DRAWINGS, AND AS
 APPROPRIATE, UPON SPECIFICATION PAGES,
 AND OTHER ARTICLES OF SERVICE.
 B) FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-03 Cont ID  
Sent By prafter Date 2005-07-13 Time 10:55 Rev Time 0.33
Received By jleech Date 2005-05-03 Time 16:41 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-08-01 Time 16:37 Rev Time 0.00
Received By mmclean Date 2005-08-01 Time 16:37 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-07-07 Cont ID  
Sent By mmclean Date 2005-07-07 Time 08:38 Rev Time 0.00
Received By mmclean Date 2005-07-07 Time 08:38 Sent To I
Notes
2005-07-07 00:00:00DENIED - RESUB - NEW SURVEYS
 1. DOES NOT MEET THE SETBACK (SIDE).
 2. NOT APART OF THE MINOR PD AMENDMENT
 FOR PARCEL FF.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-21 Cont ID  
Sent By mmclean Date 2005-04-21 Time 15:09 Rev Time 0.00
Received By mmclean Date 2005-04-21 Time 15:09 Sent To I
Notes
***NONE***