Plan Review Details - Permit 05040923
Plan Review Stops For Permit 05040923
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-23 Cont ID  
Sent By jgomez Date 2006-02-23 Time 17:58 Rev Time 0.50
Received By jgomez Date 2006-02-23 Time 17:58 Sent To  
Notes
2006-02-23 00:00:00OUTDOOR HOOD, BBQ AND FIREPLACE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-08 Cont ID  
Sent By jgomez Date 2005-09-08 Time 12:56 Rev Time 2.00
Received By jgomez Date 2005-09-08 Time 12:56 Sent To PC
Notes
2005-09-08 00:00:00BUILDING REVIEW PROVISO:
 1- AS AGREED WITH G.C. APPLY FOR SLIDING
 GLASS DOORS UNDER A SEPARATE PERMIT.
 2- FIREPLACE: PROVIDE COMPLETE INFO.
 INCLUDING SPECIFIC MODEL AND COMBUSTION
 CALCULATIONS FOR MECHANICAL REVIEW.
 3- PROVIDE COMPLETE AND SPECIFIC INFO.
 FOR BBQ HOOD AND GRILL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-02 Cont ID  
Sent By jgomez Date 2005-08-02 Time 11:20 Rev Time 2.00
Received By jgomez Date 2005-08-02 Time 11:20 Sent To PC
Notes
2005-08-02 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED TO PASS ZONING FIRST. IF HOUSE
 NEEDS TO BE LOCATED ON THE ZERO LOT LINE
 THEN OPENINGS ARE NOT ALLOWED BY TABLE
 600 FBC 2001.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- PROVIDE COMPLETE SPECS FOR APPROVED
 BBQ AND EXTERIOR HOOD. SEC. 2808 FBC
 2001. SEE PLANS FOR ARCHITECT'S SPECS.
  
 4- STILL IS NOT CLEAR IF USING SHUTTERS
 OR IMPACT GLAZING. LETTER SUBMITTED
 STATES THAT SHUTTERS UNDER A SEPARATE
 PERMIT. WHILE, ARCHITECT'S PLANS STATES
 THAT IMPACT GLASS TO BE USED IN DOORS
 AND WINDOWS. IN ADDITION, SOME OF THE
 PRODUCT APPROVALS SUBMITTED ARE WITH
 IMPACT GLAZING AND OTHERS ARE NOT.
 PROVIDE COMPLETE CONSTANT INFORMATION
 FOR EITHER WAY TO EXPEDITE AND
 FACILITATE THE REVIEW.
  
 5- IF IMPACT GLASS IS NOT USED, THEN
 PLANS NEED TO SPECIFY SAFETY GLASS IN
 HIS BATH, HER BATH, GUEST BATH AND BATH
 #3. SEC. 2405.2. FBC 2001.
  
 6- ANCHOR SCHEDULE: CLARIFY WHY
 CONNECTORS G AND H HAVE THE SAME UPLIFT
 CAPACITY IF THEY HAVE DIFFERNT NUMBER OF
 NAILS. SEE CATALOGUE FOR NUMBER OF NAILS
 TO BE USED TO OBTAIN TESTED UPLIFT
 CAPACITY. PROVIDE TESTING RESULTS AND
 ENGINEERED CALCS FOR NAIL NUMBER THAT
 DIFFER FROM THOSE TESTED AND PUBLISHED
 BY THE MANUFACTURER. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 7- MULLION SIZE SPECIFIED FOR FIXED
 WINDOWS IN LIVING ROOM AREA DOESN'T
 RESIST THE DESIGN PRESSURES. SEE PRODUCT
 APPROVAL. SPECIFY BIGGER MULLION AND
 ANCHORS. SEC. 104.2.1.2 CITY AMENDMENTS.
  
 8- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) MULLION SPECIFIED BY ARCHITECTON
 ITEM #7 ABOVE.
 B) CASEMENT WINDOWS THAT MATCH FLORIDA
 PRODUCT APPROVAL AND WINDOWS SHOWN ON
 PLANS.
 C) ALL WINDOWS AND DOORS TO BE USED.
 IMPACT OR NON IMPACT.
  
 9- PROVIDE COMPLETE SPECS AND LISTING
 FOR FIREPLACE SHOWING COMPLIANCE WITH
 2806 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-02 Cont ID  
Sent By jgomez Date 2005-06-02 Time 10:27 Rev Time 2.00
Received By jgomez Date 2005-06-02 Time 10:27 Sent To PC
Notes
2005-06-02 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- SEE COMMENTS BY ZONING. IF HOUSE
 NEEDS TO BE LOCATED ON THE ZERO LOT
 LINE, THEN, OPENINGS ARE NOT ALLOWED BY
 TABLE 600 FBC 2001.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- SHEET T1: A) UPDATE GENERAL NOTES.
 SEE COMMENTS ON PLANS. SEE RESPECTIVE
 FBC CHAPTER FOR PROPER REFERENCE (EG:
 CHAPTER 19 ACI 318) AND CHAPTER 35 FOR
 PROPER REFERENCE EDITION.
  
 B) DESIGN PARAMETERS: CLARIFY WHERE IS
 THE BASIC VELOCITY PRESSURE TAKEN FROM.
 SEE SECTION 1606 FBC 2001.
 ALSO, CLARIFY WHY THE MIN. SOIL BEARING
 PRESSURE IS - NA?.
  
 4- PROVIDE COMPLETE SPECS FOR BBQ
 SHOWING THAT IT WAS DESIGNED TO BE
 INSTALLED IN THE PORCH. SEC. 2808 FBC
 2001.
  
 5- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 6- SHEET A1: A) SPECIFY COLUMNS AT BAY
 WINDOW IN MASTER BEDROOM.
  
 B) WHAT DOES TS-2 SPECIFIED ON CONCRETE
 PAD BETWEEN GARAGE AND BEDROOM #2 STANDS
 FOR?. SEC. 104.2.1.2 CITY AMENDMENTS TO
 FBC 2001.
  
 C) DETAIL 5 FOR FOOTING BETWEEN GARAGE
 AND CLUB ROOM DOESN'T MATCH. REVISE AS
 REQUIRED.
  
 7- SHEET A2; A) NOTE #1 AND #6 CALL FOR
 IMPACT GLAZING ON DOORS AND WINDOWS.
 NOTE ON DESIGN PRESSURES CHART SHOWN ON
 ELEVATIONS CALLS FOR STORM SHUTTERS.
 CLARIFY/REVISE AS REQUIRED.
  
 B) REVISE SIZES FOR FIXED WINDOWS AT
 LIVING ROOM (36' X 234" FG ?).
  
 C) SPECIFY SAFETY GLASS AT HIS BATH, HER
 BATH, GUEST SUITE BATH, BATH #3 AND
 LIVING ROOM. SEE PLANS AND SECTION
 2405.2 FBC 2001.
  
 8- SHEET A3: A) REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE. SEE LATEST CATALOGUE
 (2005) WHICH WAS REVISED TO COMPLY WITH
 SEC. 1609.4.3 FBC 2001. OR, PROVIDE
 COMPLETE ENGINEERING CALCS THAT COMPLY
 WITH SEC. 1609.4.3 FBC 2001 FOR TYPE AND
 NUMBER OF CONNECTORS THAT DIFFER FROM
 THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 104.2.1.2OF CITY
 AMENDMENTS TO FBC 2001.
  
 B) CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. NEED MASONRY CONNECTOR. SEE
 CATALOGUE FOR PROPER MASONRY CONNECTOR.
  
 C) DETAIL E/13 DOESN'T APPLY. THERE IS
 NOT CONCRETE WALL TO BE ATTACHED TO.
 REVISE AS REQUIRED. SEE PLANS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 D) SPECIFY CONNECTOR FOR TRUSS GIRDER
 RESTING ON WOOD COLUMN LOCATED IN
 VESTIBULE FOR CLUB ROOM AND MASTER
 BEDROOM. SEC. 104.2.1.2 CITY AMENDMENTS.
  
 9- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR CORNER SLIDING
 GLASS DOORS.
  
 10- WINDOW AND DOOR MULLIONS: CLEARLY
 SPECIFY MULLION SIZE AND ANCHOR TYPE TO
 BE USED ACCORDING TO THE ASSEMBLY TO BE
 INSTALLED ON TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 11- DADE COUNTY NOA SUBMITTED FOR
 CASEMENT WINDOWS DOESN'T MATCH NOA
 LISTED ON FLORIDA PRODUCT APPROVAL COVER
 PAGE. REVISE AS REQUIRED.
  
 12- PROVIDE COMPLETE SPECS AND LISTING
 FOR FIREPLACE SHOWING COMPLIANCE WITH UL
 127 REQUIREMENTS. SEC. 2806 FBC 2001.
  
 ***PLEASE DON'T STAPLE PRODUCT APPROVALS
 TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-10-11 Cont ID  
Sent By btrobaug Date 2006-10-11 Time 18:25 Rev Time 0.50
Received By btrobaug Date 2006-10-11 Time 17:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-09-28 Cont ID  
Sent By dpalmer Date 2006-09-28 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2006-09-28 Time 14:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-04-17 Cont ID  
Sent By dpalmer Date 2006-04-17 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2006-04-17 Time 11:15 Sent To PC
Notes
2006-04-17 00:00:00REDLINED 110.26 FOR A/C DISC'C.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 19:20 Sent To PC
Notes
2006-03-23 00:00:00REDLINED:
 424.3B MIN OCPF OR AHU'S (AHU #1) TO BE
 125%. PLEASE SEE 20A BRKR SHOWN FOR 10KW
 UNIT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-07 Cont ID  
Sent By dpalmer Date 2005-09-07 Time 19:45 Rev Time 0.25
Received By dpalmer Date 2005-09-07 Time 19:45 Sent To B
Notes
2005-09-07 00:00:00REDLINED 110.26 FOR DISCONNECTS.
  
 REDLINED 210.52C1 FOR KITCHEN
 COUNTERSPACE RECEPTS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-19 Cont ID  
Sent By dpalmer Date 2005-07-19 Time 07:24 Rev Time 0.30
Received By dpalmer Date 2005-07-19 Time 07:16 Sent To P
Notes
2005-07-19 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SEE ZONING COMMENTS, THIS
 DIRECTLY AFFECTS ELECTRICAL PLANS AND
 LAYOUT OF HOUSE IN MORE THAN ONE WAY.
 PLEASE ADJUST HOWEVER NESSCESARY TO MEET
 ZONING COMMENTS.
  
  
 2)NOTE: PLEASE SEE REDLINED 210.52C1,FOR
 KITCHEN COUNTERSPACE.
 PLEASE SEE 110.26 FOR A/C CU DISC'S.
  
 PLEASE NOTICE BOTH OF THESE ITEMS ARE
 REDLINED ITEMS AND DO NOT NEED TO BE
 CORRECTED ON PLANS UNLESS REV'S ARE MADE
 TO ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-28 Cont ID  
Sent By dpalmer Date 2005-04-28 Time 10:34 Rev Time 0.30
Received By dpalmer Date 2005-04-28 Time 10:34 Sent To M
Notes
2005-04-28 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE ZONING COMMENTS WHICH
 WILL HAVE A DIRECT AFFECT ELECTRICAL
 PLANS AND CHANGES WHICH MAY NEED TO BE
 MADE.
  
 2)NOTE: PLEASE SEE "PANEL C" IS NOT
 SHOWN ON PLANS.
 PLEASE SHOW AT THIS TIME , SINCE PLANS
 ARE COMING BACK FOR ZONING COMMENTS.
  
 3)NOTE: PLEASE SEE ONE COPY OF
 ELECTRICAL PLANS WERE STAMPED IN ERROR
 DUE TO UNKNOWN ZONING COMMENTS.
 THE ONE STAMPED SET HAS NOW BEEN VOIDED
 AND WILL NEED TO BE REPLACED.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 19:38 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 19:38 Sent To E
Notes
2006-09-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 16:35 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 16:35 Sent To E
Notes
2006-04-14 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 18:00 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 18:00 Sent To E
Notes
2006-03-21 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-14 Cont ID  
Sent By adarroug Date 2006-02-14 Time 08:50 Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 08:50 Sent To B
Notes
2006-02-14 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 11:25 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 11:25 Sent To Z
Notes
2005-08-24 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 09:59 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 09:59 Sent To E
Notes
2005-07-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 11:14 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 11:14 Sent To Z
Notes
2005-07-11 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-27 Cont ID  
Sent By adarroug Date 2005-04-27 Time 16:03 Rev Time 0.00
Received By adarroug Date 2005-04-27 Time 16:03 Sent To E
Notes
2005-04-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-02 Cont ID  
Sent By jgomez Date 2005-06-02 Time 11:08 Rev Time 0.00
Received By jgomez Date 2005-04-15 Time 14:32 Sent To PC
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-06 Cont ID  
Sent By prafter Date 2005-09-06 Time 11:43 Rev Time 1.00
Received By prafter Date 2005-09-06 Time 11:43 Sent To B
Notes
2005-09-06 00:00:00MECH. PLAN REVIEW:
  
 FIRE PLACE INFORMATION NOT MARKED,
 GERNARIC MODELS. BUILDING PLAN REVIEW TO
 CLEARFIE WITH G/C CONT.
  
 PAT RAFTER 561/805/6728

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-27 Cont ID  
Sent By prafter Date 2005-07-27 Time 07:07 Rev Time 0.50
Received By prafter Date 2005-07-27 Time 07:07 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By prafter Date 2005-05-03 Time 07:44 Rev Time 0.00
Received By prafter Date 2005-09-06 Time 11:43 Sent To P
Notes
2005-05-03 00:00:00MECH. PLAN REVIEW:
  
 1. R/A DUCT NOT SIZED, AHU 1.
  
 2. SUPPLY AIR FROM AHU 1. REFLECT 12"
 FOR TWO TRIANGELS THEN INCRESES TO 14" .
 PLEASE CORRECT AND RESUMMIT.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-02 Cont ID  
Sent By jleech Date 2005-09-02 Time 07:52 Rev Time 0.33
Received By jleech Date 2005-09-02 Time 07:52 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-07-23 Cont ID  
Sent By jleech Date 2005-07-23 Time 14:23 Rev Time 0.33
Received By jleech Date 2005-07-23 Time 14:23 Sent To M
Notes
2005-07-23 00:00:00DENIED;
 1. SECOND REQUEST, ADD MORNING SINK TO
 RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By jleech Date 2005-05-03 Time 16:52 Rev Time 0.50
Received By jleech Date 2005-05-03 Time 16:52 Sent To B
Notes
2005-05-03 00:00:00DAY SINK MISSING FROM RISER DIAGRAM.
 ZONING COMMENTS WILL CHANGE FLOOR PLAN.
 PLUMBING PLANREVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2005-09-01 Cont ID  
Sent By mmclean Date 2005-09-01 Time 13:48 Rev Time 0.00
Received By mmclean Date 2005-09-01 Time 13:48 Sent To B
Notes
2005-09-01 00:00:00GIVEN TO LUIS MARTINEZ.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-07-15 Cont ID  
Sent By mmclean Date 2005-07-15 Time 13:01 Rev Time 0.00
Received By mmclean Date 2005-07-15 Time 13:01 Sent To I
Notes
2005-07-15 00:00:00DENIED,
 1. MUST HAVE INTERIOR ACCESS TO THE
 GUEST SUITE FROM MAIN STRUCTURE.
 2. SITEPLAN DOES NOT MATCH WHAT WAS
 APPROVED FOR SETBACK, "LOT 13 WILL
 ADHERE TO THE MODIFIED ZERO SETBACKS
 WITH THE ZERO SIDE OF THE HOUSE LOCATED
 ON THE 3'1' ZERO LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By mmclean Date 2005-04-26 Time 18:04 Rev Time 0.00
Received By mmclean Date 2005-04-25 Time 18:48 Sent To I
Notes
2005-04-26 00:00:00DENIED,
 1. MUST HAVE INTERIOR ACCESS TO THE
 GUEST SUITE FROM MAIN STRUCTURE.
 2. MUST REMOVE U/C REF & SINK FROM
 GUEST SUITE.
 3. MUST PROVIDE SITEPLAN THAT MATCHES
 THE PLAT THAT WAS APPROVED (APPROVED
 2002, ZERO LOT)
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2005-04-25 00:00:00HAVE QUESTIONS TO GRACE REGARDING PLANS