Plan Review Details - Permit 05040920
Plan Review Stops For Permit 05040920
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2005-12-28 Cont ID  
Sent By jgomez Date 2005-12-28 Time 09:55 Rev Time 0.33
Received By jgomez Date 2005-12-28 Time 09:55 Sent To M
Notes
2005-12-28 00:00:00INFORMATION SUBMITTED IS NOT FOR A
 FIREPLACE, BUT FOR A ROOM HEATER.
 THEREFORE, UL 127 TESTING REQUIREMENTS
 REQUIRED BY SEC. 2806 FBC 2001 DON'T
 APPLY.SENT FOR MECHANICAL REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-12-21 Cont ID  
Sent By jgomez Date 2005-12-21 Time 17:57 Rev Time 1.00
Received By jgomez Date 2005-12-21 Time 17:57 Sent To M
Notes
2005-12-21 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- NEED LISTED SEE THRU PRE FABRICATED
 FIREPLACE AS SHOWN ON PLANS TESTED AND
 MEETING THE REQUIREMENTS OF UL 127.
 SECTION 2806.1.2 FBC 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-08 Cont ID  
Sent By jgomez Date 2005-09-08 Time 14:09 Rev Time 1.50
Received By jgomez Date 2005-09-08 Time 14:09 Sent To PC
Notes
2005-09-08 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- AS AGREED WITH G.C. A) APPLY FOR
 SHUTTERS UNDER A SEPARATE PERMIT.
 B) APPLY FOR NON-IMPACT SLIDING GLASS
 DOOR UNDER A SEPARATE PERMIT.
 2- NEED COMPLETE SPECS FOR BBQ GRILL
 INCLUDING MODEL & HOOD FOR EXTERIOR USE.
 3- PROVIDE PRODUCT APPROVAL FOR CASEMENT
 WINDOWS WITH LEGIBLE DRAWINGS (WITHOUT
 CUTTING INFORMATION ON TOP OR BOTTOM OF
 PAGE) AND SPECIFY GLASS TYPE TO BE USED
 TO VERIFY COMPLIANCE W/ DESIGN PRESSURES
 4- PROVIDE COMPLETE SPECS AND UL LISTING
 FOR SEE THRU FIREPLACE AS SHOWN ON
 PLANS. AND, PROVIDE COMBUSTION AIR CALCS
 FOR MECHANICAL PLAN REVIEWER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-16 Cont ID  
Sent By jgomez Date 2005-08-16 Time 12:31 Rev Time 2.00
Received By jgomez Date 2005-08-16 Time 12:31 Sent To PC
Notes
2005-08-16 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- A) PROVIDE COMPLETE SPECS & APPROVED
 LISTING FOR GRILL. INCLUDING MODEL TO BE
 USED.
  
 B) PROVIDE SPECS AND APPROVED LISTING
 FOR HOOD SPECIFICALLY FOR EXTERIOR USE.
  
 3- SLIDING GLASS DOOR PRODUCT APPROVAL
 SUBMITTED DOESN'T MATCH DOOR ASSEMBLY AS
 SHOWN ON PLANS. SEE PLANS AND RE-SUBMIT
 FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 THAT SPECIFIC ASSEMBLY.
  
 4- CLARIFY IF USING IMPACT GLASS OR
 SHUTTERS. MIXED INFORMATION WAS
 SUBMITTED. THERE IS A NOTE FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT, WHILE
 THERE ARE SOME PRODUCT APPROVALS WITH
 IMPACT GLASS AND SOME OTHERS ARE NOT.
  
 5- PRODUCT APPROVAL DRAWINGS FOR
 CASEMENT WINDOWS ARE NOT CLEAR. THEY ARE
 MISSING INFORMATION. PLEASE COPY
 DRAWINGS THAT FIT IN THE SELECTED PAPER
 WITHOUT CUTTING OUT INFORMATION.
  
 6- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR ENTRY DOORS.
  
 7- PROVIDE COMPLETE SPECS AND APPROVED
 UL LISTING FOR SEE THRU FIREPLACE AS
 SHOWN ON PLANS. SEC. 2806 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-06 Cont ID  
Sent By jgomez Date 2005-07-06 Time 11:39 Rev Time 2.00
Received By jgomez Date 2005-07-06 Time 11:39 Sent To Z
Notes
2005-07-06 00:00:00SECOND CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 3- THE BUILDING OFFICIAL IS THE ONE WHO
 APPROVES THE BBQ INSTALLATION. HE WANTS
 TO SEE TESTING AND ENGINEERING
 JUSTIFYING WHY PROPOSED INSTALLATION
 DOESN'T NEED THE EXHAUST HOOD SINCE
 THERE ARE OTHER COMPANIES WHO DESIGNED
 BBQ'S FOR LANAI OR PORCH INSTALLATION
 AND THEY REQUIRE HOOD EXHAUST.
 LETTER SUBMITTED IS INSUFFICIENT AND IS
 SIGNED BY NOBODY. BESIDES, MANUFACTURER
 SPECS SAYS FOR OUTDOOR INSTALLATION ONLY
  
 4- SHEET A3: A) REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE (NOT DONE FROM PREVIOUS
 CHECKLIST). SEE LATEST CATALOGUE WHICH
 WAS REVISED TO COMPLY WITH SECTION
 1609.4.3 FBC 2001. PROVIDE TESTING AND
 ENGINEERING CALCS FOR NUMBER AND SIZE OF
 NAILS THAT DIFFER FROM THOSE ALREADY
 TESTED AND PUBLISHED BY MANUFACTURER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 B) CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY MASONRY
 CONNECTOR. SEE CATALOGUE FOR PROPER
 MASONRY CONNECTOR.
  
 C) SPECIFY CONNECTOR FOR TRUSS GIRDER
 END AT INTERSECTION OF MASTER BEDROOM
 AND CLUB ROOM CORNER. SEE PLANS.
  
 5- A)SLIDING GLASS DOORS NOA AND FLORIDA
 PRODUCT APPROVAL DON'T CORRESPOND TO
 EACH OTHER.
 B) NOA SUBMITTED IS FOR IMPACT DOORS.
 ARE IMPACT DOORS GOING TO BE INSTALLED?
  
 6- MULLIONS SPECIFIED FOR WINDOWS AT
 LIVING ROOM DON'T RESIST CALCULATED
 DESIGN PRESSURES. REVISE SIZE OF
 MULLIONS AND PROVIDE PRODUCT APPROVAL
 AS REQUIRED.
  
 7- DADE COUNTY NOA SUBMITTED FOR
 CASEMENT WINDOWS DOESN'T MATCH NOA
 LISTED IN THE FLORIDA PRODUCT APPROVAL.
 REVISE AS REQUIRED AND MAKE SURE IS THE
 TYPE OF WINDOW ASSEMBLY TO BE INSTALLED.
  
 8- REAR ELEVATION DOESN'T MATCH FLOOR
 PLAN. REVISE LIVING ROOM WINDOW AND
 CABANA BATH WING TO MATCH FLOOR PLAN.
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR IMPACT GLASS CASEMENT
 WINDOW FOR BREAKFAST AREA.
  
 10- PROVIDE ENERGY CALCULATIONS SHOWING
 WORST CASE SCENARIO FOR THIS MODEL.
 CALCULATIONS TO MATCH FLOOR PLAN. SEE
 OVERHANG LENGTH AND HEIGHT, SIZES OF
 WINDOWS/DOORS ETC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-01 Cont ID  
Sent By jgomez Date 2005-06-01 Time 13:47 Rev Time 2.00
Received By jgomez Date 2005-06-01 Time 13:47 Sent To PC
Notes
2005-06-01 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SHEET T1: A) UPDATE GENERAL NOTES.
 SEE COMMENTS ON PLANS AND RETURN
 REVIEWED SET AFTER CORRECTIONS ARE DONE
 TO ORIGINAL DRAWINGS TO EXPEDITE REVIEW.
  
 3- DESIGN PARAMETERS: CLARIFY WHERE IS
 THE BASIC VELOCITY PRESSURE TAKEN FROM.
 SEE SEC. 1606 FBC 2001.
 ALSO, CLARIFY WHY THE MIN. SOIL BEARING
 PRESSURE IS -NA?
  
 4- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 5- SHEET A1: A) COLUMNS AT LANAI WERE
 KEYED WRONG. THEY SHOULD BE C4 NOT C2.
 SEE COMMENTS ON PLANS & REVISE AS REQ'D.
  
 B) DETAIL 4 DOESN'T MATCH FOOTING SHOWN
 ON PLAN BETWEEN BEDROOM #2 AND GARAGE.
 REVISE AS REQUIRED.
  
 6- SHEET A2: A) SPECIFY SAFETY GLASS FOR
 WINDOWS AT HER BATH, HIS BATH AND LIVING
 ROOM. SEC. 2405.2 FBC 2001.
  
 B) CLARIFY NOTE #6. ARE WINDOWS AND
 DOORS HAVING IMPACT GLAZING OR STORM
 SHUTTERS?. SEE NOTE UNDER DESIGN
 PRESSURES CHART AND REVISE AS REQ'D.
  
 7- PROVIDE COMPLETE BBQ SPECS STATING
 THAT GRILL IS DESIGNED TO BE INSTALLED
 IN PORCH OR LANAI. SEC. 2808 FBC 2001.
  
 8- SHEET A3: A) REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE. SEE LATEST CATALOGUE
 WHICH WAS REVISED TO COMPLY WITH SEC.
 1609.4.3 FBC 2001. PROVIDE COMPLETE
 ENGINEERING CALCULATIONS SHOWING
 COMPLIANCE WITH SEC. 1609.4.3 FBC 2001
 FOR FASTENERS TYPE AND SPACING THAT
 DIFFER FROM THOSE TESTED AND PUBLISHED
 BY THE MANUFACTURER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 B) CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY HANGER. SEE CATALOGUE FOR PROPER
 MASONRY CONNECTORS AND REVISE AS
 REQUIRED.
  
 C) SPECIFY CONNECTOR FOR TRUSS GIRDER
 END AT INTERSECTION OF MASTER BEDROOM
 AND CLUB ROOM CORNER. SEE PLANS.
  
 9- APPLY FOR LOCAL PRODUCT APPROVAL FOR
 CORNER SLIDING GLASS DOORS. DADE COUNTY
 NOA ALONE IS NOT AUTOMATICALLY A FLORIDA
 PRODUCT APPROVAL. FILL OUT APPLICATION
 FOR LOCAL PRODUCT APPROVAL. SEE
 WWW.FLORIDABUILDING.ORG.
  
 10- WINDOW AND DOOR MULLIONS: CLEARLY
 INDICATE SIZE AND ANCHOR TYPE ACCORDING
 TO ASSEMBLY TO VERIFY COMPLIANCE WITH
 DESIGN PRESSURES. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 11- DADE COUNTY NOA SUBMITTED FOR
 CASEMENT WINDOWS DOESN'T MATCH NOA
 LISTED ON FLORIDA PRODUCT APPROVAL COVER
 PAGE. REVISE AS REQUIRED.
  
 12- PROVIDE COMPLETE LISTING FOR
 FIREPLACE SHOWING COMPLIANCE WITH UL 127
 REQUIREMENTS. SEC. 2806 FBC 2001.
  
 *** PLEASE DON'T STAPLE PRODUCT
 APPROVALS TO PLANS. IT WILL EXPEDITE
 REVIEW PROCESS AND HANDLING OF PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-21 Cont ID  
Sent By dpalmer Date 2006-09-21 Time 08:16 Rev Time 0.00
Received By dpalmer Date 2006-09-21 Time 07:32 Sent To PC
Notes
2006-09-21 00:00:00REDLINED, TWO AHU'S #3 BEING SHOWN, ONE
 SHOULD BE #2.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-17 Cont ID  
Sent By dpalmer Date 2006-04-17 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2006-04-17 Time 11:19 Sent To PC
Notes
2006-04-17 00:00:00REDLINED
  
  
 ** 110.26 FOR A/C DISC'S.
 ** AFCI FOR SD'S AS NOTE MENTIONS TO
 WIRE TO KITCHEN OR BATH LT CIRCUIT.
 210.12
 ** PANEL "A" SHOWS 50A BRKR TO PANEL
 "C", HOWEVER LOAD AND SIZE OF PANEL "C"
 IS 100A'S PER RISER AND PANEL SCHEDULE.
  
  
 THE ABOVE ARE REDLINED AND NEEDS TO BE
 CORRECTED WITH OTHER REV'S BEFORE ROUGH.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 12:25 Rev Time 0.33
Received By dpalmer Date 2005-04-25 Time 12:25 Sent To M
Notes
2005-04-25 00:00:00** PROVISO **
  
 1)NOTE: PLEASE SEE POSSIBLE MISSING
 RECEPT FOR 2' OF WALL.
 210.52
  
 2)NOTE: PLEASE SEE PANEL "C" SHOWN ON
 RISER IS NOT SHOWN ON PLANS.
  
 PLEASE REVISE THE ABOVE ALONG WITH ANY
 OTHER CHANGES BEFORE ROUGH ELECTRICAL
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 16:31 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 16:31 Sent To E
Notes
2006-09-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 16:37 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 16:37 Sent To E
Notes
2006-04-14 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 13:38 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 13:38 Sent To B
Notes
2005-11-16 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 14:43 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 14:43 Sent To B
Notes
2005-09-01 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 08:26 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 08:26 Sent To B
Notes
2005-08-02 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 11:07 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 11:07 Sent To Z
Notes
2005-07-28 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 13:09 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 13:09 Sent To P
Notes
2005-07-07 00:00:00TO "KSTEVENS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 16:18 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 16:18 Sent To M
Notes
2005-06-23 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 11:14 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 11:14 Sent To E
Notes
2005-04-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-01 Cont ID  
Sent By jgomez Date 2005-06-01 Time 17:55 Rev Time 0.00
Received By jgomez Date 2005-08-16 Time 12:30 Sent To PC
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-22 Cont ID  
Sent By tgordon Date 2005-12-22 Time 14:42 Rev Time 1.00
Received By tgordon Date 2005-12-22 Time 15:37 Sent To  
Notes
2005-12-22 00:00:00 
 1) COMBUSTION AIR CALCULATIONS HAVE BEEN
 SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 08:10 Rev Time 0.40
Received By pkrauss Date 2005-06-28 Time 07:25 Sent To  
Notes
2005-06-28 00:00:00PROVISO:2ND REQUEST
 PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE VENTLESS FIREPLACE PRIOR TO
 INPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-02 Cont ID  
Sent By prafter Date 2005-05-02 Time 11:46 Rev Time 1.00
Received By prafter Date 2005-05-02 Time 11:46 Sent To P
Notes
2005-05-02 00:00:00MECH. PLAN REVIEW:
 PROVIDE PRODUCT APPROVAL FOR GAS FIRE
 PLACE WITH COMBUSTION AIR INFORMATION.
 PAT RAFTER 561/805/6728 OR805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-12 Cont ID  
Sent By jleech Date 2005-07-12 Time 07:47 Rev Time 0.25
Received By jleech Date 2005-07-12 Time 07:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-05 Cont ID  
Sent By jleech Date 2005-05-05 Time 13:56 Rev Time 0.33
Received By jleech Date 2005-05-05 Time 13:56 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-08-01 Time 16:25 Rev Time 0.00
Received By mmclean Date 2005-08-01 Time 16:25 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-07-07 Cont ID  
Sent By mmclean Date 2005-07-07 Time 08:29 Rev Time 0.00
Received By mmclean Date 2005-07-07 Time 08:29 Sent To I
Notes
2005-07-07 00:00:00DENIED - RESUB - NEW SURVEYS
 1. DOES NOT MEET THE SETBACK (SIDE).
 2. NOT APART OF THE MINOR PD AMENDMENT
 FOR PARCEL FF.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-21 Cont ID  
Sent By mmclean Date 2005-04-21 Time 16:24 Rev Time 0.00
Received By mmclean Date 2005-04-21 Time 16:24 Sent To I
Notes
***NONE***