Plan Review Details - Permit 05040918
Plan Review Stops For Permit 05040918
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-04-04 Cont ID  
Sent By jgomez Date 2006-04-04 Time 18:53 Rev Time 0.50
Received By jgomez Date 2006-04-04 Time 18:53 Sent To  
Notes
2006-04-04 00:00:00CASEMENT EGRESS WINDOW IN SECOND FLOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-02-27 Cont ID  
Sent By jgomez Date 2006-02-27 Time 11:39 Rev Time 0.50
Received By jgomez Date 2006-02-27 Time 11:39 Sent To  
Notes
2006-02-27 00:00:00BUILDING REVIEW CHECKLIST:
 1- 24-5 SH WINDOW ON SECOND FLOOR
 DOESN'T COMPLY WITH SECTION 1005.4.4 OF
 FLORIDA BUILDING CODE 2001. ACCORDING TO
 SHOP DRAWINGS FOR 24-5 SH WINDOW HAS A
 CLEAR OPENING OF 5.5SF. TOTAL CLEAR
 OPENING MUST HAVE A MINIMUM OF 5.7SF.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-12-09 Cont ID  
Sent By jgomez Date 2005-12-09 Time 13:37 Rev Time 0.50
Received By jgomez Date 2005-12-09 Time 12:19 Sent To PC
Notes
2005-12-09 00:00:00BUILDING REVIEW PROVISO:
 1- APPLY FOR STORM SHUTTERS AS AGREED ON
 PROVISO. NOTE: APPLY AS SOON AS POSSIBLE
 TO AVOID DELAYS OR CONFLICTS GIVEN THE
 HIGH VOLUME OF PERMIT APPLICATIONS THE
 CITY IS RECEIVING.
  
 2- SINGLE HUNG WINDOWS CUT SHEETS:
 A) THE PURPOSE OF CUT SHEETS IS TO
 VERIFY COMPLIANCE WITH EGRESS
 REQUIREMENTS: 24" MIN. CLEAR HEIGHT AND
 5.7 S.F. MIN. TOTAL CLEAR OPENING.
 INFORMATION SUBMITTED DOESN'T PROVIDE
 THIS INFORMATION.
 B) CUT SHEETS ARE COMING FROM S&P
 ARCHITECTURAL PRODUCTS. PRODUCT APPROVAL
 SUBMITTED IS FOR PGT WINDOWS.
 CLARIFY/REVISE AS REQUIRED.
 C) ARCHITECT OF RECORD TO REVIEW CUT
 SHEETS TO VERIFY DESIGN CRITERIA AND
 EGRESS COMPLIANCE WITH SEC. 1005.4.4 FBC
 2001 PRIOR TO SUBMITTAL TO THIS OFFICE.
 D) SEE 2ND FLOOR PLANS FOR SIZE OF
 WINDOWS SPECIFIED. NEED CUT SHEETS FOR
 ALL SPECIFIED SIZES.
  
 3- STAIR SHOP DRAWINGS NEED TO BE SIGNED
 AND SEALED BY THE ENGINEER, ORLANDO M.
 FORTUN AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
  
 4- OWES $70.00 FOR REVISION FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By jgomez Date 2005-08-03 Time 16:45 Rev Time 2.50
Received By jgomez Date 2005-08-03 Time 15:42 Sent To Z
Notes
2005-08-03 00:00:00BUILDING REVIEW PROVISO:
 1-
 BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- REVISE ROOF SHEATHING NAIL TYPE FOR
 ROOF ZONE #3. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001.
 3- PRIOR TO INSTALLATION: PROVIDE CUT
 SHEETS FOR 24SH EGRESS WINDOWS TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS SEC.
 1005.4.4 FBC 2001. (5.7 S.F. MIN. CLEAR
 OPENING ALLOWED).
 4- STAIR SHOP DRAWINGS ARE NOT LEGIBLE.
 NEED LEGIBLE DRAWINGS. RESUBMIT.
 5- SHEET S-1: UPDATE NOTES 2(B) & 3(A).
 SEE CHAPTER 19 FOR PROPER ACI REFERENCE.
 6- PROVIDE COMPLETE INFORMATION FOR
 SINGLE HUNG WINDOWS PRODUCT APPROVAL.
 MISSING THE FLORIDA APPROVAL COVER PAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-31 Cont ID  
Sent By jgomez Date 2005-05-31 Time 08:34 Rev Time 3.00
Received By jgomez Date 2005-05-31 Time 08:34 Sent To PC
Notes
2005-05-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- FLOOR PLANS SHOW HANDRAIL ON ONE SIDE
 OF STAIRS ONLY. NEED HANDRAIL AT RUN
 THAT GOES FROM LANDING TO 2ND FLOOR.
 SEC. 1007.5.1 EXCEPTION #3.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQ'D BY SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 4- SPECIFY CONTROL JOINTS OR SPECIFY WWM
 SUPPORTS AND SPACING AS REQ'D BY SEC.
 1909.3 FBC 2001.
  
 5- SPECIFY ROOF SHEATHING NAIL SIZE AND
 SPACING. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001 FOR MEAN ROOF
 HEIGHT ABOVE 25'-0" FOR ZONES 1,2 AND 3.
  
 6- PROVIDE ATTIC ACCESS AT MASTER
 BEDROOM WING. SEC. 2309.6 FBC 2001.
  
 7- PROVIDE CUT SHEETS FOR 24SH WINDOWS
 SHOWING COMPLIANCE WITH MIN. EGRESS
 OPENING OF 5.7SF. AS REQUIRED BY SEC.
 1005.4.4 FBC 2001.
 NOTE: PRODUCT APPROVAL SUBMITTED DOESN'T
 HAVE THIS SIZE WINDOWS.
  
 8- REVISE NOTE #3 ON SHEET A-3.1. NEED
 7/8" STUCCO THICKNESS. NO 5/8". SEE ASTM
 C-926.
  
 9- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCH.
 SEE ASTM C-926 AND C-1063. SPECIFY
 FASTENER SIZE AND SPACING.
  
 10- SHEET A-7: A) REVISE STAIR KEY NOTE
 #1. HANDRAIL TO BE BETWEEN 34" AND 38"
 AS REQ'D BY SEC. 1007.5.1 EXCEPTION #3.
 NOTE: HANDRAIL AND GUARDRAIL ARE NOT THE
 SAME THING.
  
 B) SPECIFY MATERIAL AND LOCATION OF
 FIREBLOCKING AT STAIRS. ALSO MISSING
 FIREBLOCKING AT TOP OF STAIRS. SEC.
 2305.1.4 FBC 2001.
  
 C) SPECIFY ALL FASTENERS FOR STAIR
 FRAMING. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 11- PROVIDE CALCULATIONS SHOWING HOW 2
 STORY STRUCTURE ONLY REQUIRES 2000PSF
 SOIL BEARING CAPACITY. SEC. 104.2.1.2
 CITY AMMENDMENTS TO FBC 2001.
  
 12- THERE ARE 2 GARAGE DOOR BUCK DETAILS
 WITH DIFFERENT SPECS.CLARIFY WHICH ONE
 APPLIES TO THIS JOB. SEE SHEET A-6 AND
 SHEET S-4.
  
 13- SPECIFY DRAFSTOPPING LOCATION AND
 MATERIAL ON 2ND FLOOR FRAMING PLAN AS
 REQ'D BY SEC. 2305.2.2.1 FBC 2001.
  
 14- PROVIDE SMOKE DETECTOR AT FIRST
 FLOOR IN CLOSE PROXIMITY TO STAIRS.
 ELECTRICAL PLAN SHOWS SMOKE DETECTOR ON
 FOYER CEILING WHICH IS A DOUBLE VOLUME
 CEILING. SEC. 905.2.2 FBC 2001.
  
 15- SHEET S-1: A) UPDATE STRUCTURAL
 NOTES 2(B) AND 3(A). SEE CHAPTER 19 FOR
 PROPER ACI REFERENCE AND CHAPTER 35 FOR
 PROPER EDITION.
  
 B) DETAIL #6 FOR PRIVACY WALL IS FOR
 6'-0" HIGH WALL. FIRST FLOOR PLAN CALLS
 FOR 8'-0" HIGH WALL. REVISE AS REQ'D.
  
 C) FOOTING FOR COLUMN AT REAR PORCH IS
 ENCROACHING INTO NEIGHBOR'S PROPERTY AT
 ZERO LOT LINE. REVISE AS REQUIRED.
  
 D) STEEL COLUMN BY AHU #1 CALLS FOR F30
 FOOTING. THERE IS NOT F30 ON FOOTING
 SCHEDULE. REVISE AS REQUIRED.
  
 E) SPECIFY CONNECTORS AT TOP OF ALL WOOD
 COLUMNS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 F) SOIL STATEMENT. DESIGNER OF RECORD TO
 REVIEW SOIL TEST REPORT. THERE IS NO
 LIMEROCK.
 ALSO, REPORT RECOMMENDS 18" MIN. WIDTH
 FOR FOOTINGS. FOOTING M-16 CALLS FOR 16"
 WIDTH. SPECIFY IF DESIGNER REVIEWED SOIL
 TEST REPORT AND FOOTING RECOMMENDATION
 IS NOT REQUIRED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 16- SHEET S-2: A) FRAMING PLAN CALLS FOR
 CONNECTOR #22. WHERE IS IT ON THE TRUSS
 CONNECTOR SCHEDULE?
  
 B) CONNECTOR #5 IS A WOOD TO WOOD
 CONNECTOR. NEED WOOD TO MASONRY
 CONNECTOR. REVISE AS REQUIRED.
  
 C) THERE IS OVERLAPPING INFORMATION BY
 MASTER BEDROOM ROOF AREA. REVISE.
  
 D) COLUMN BY STAIRWAY SAYS STEEL COLUMN
 DETAIL #38. FOUNDATION PLAN CALLS FOR
 WOOD COLUMN. REVISE AS REQUIRED.
  
 E) SPECIFY CONNECTOR FOR TRUSS GIRDER
 ABOVE LAUNDRY AREA. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 17- SHEET S-3: A) CONNECTOR SCHEDULE:
 REVISE NUMBER AND TYPE OF NAILS. SEE
 LATEST CATALOGUE FOR PROPER NUMBER OF
 NAILS.
  
 B) WHERE IS CONNECTOR #22?
  
 C) REVISE CONNECTOR #5. NEED WOOD TO
 MASONRY CONNECTOR.
  
 18- SHEET S-5: A) DETAIL 38. THERE ARE
 NOT SPECS FOR SIZE AND NUMBER OF BOLTS.
  
 B) DETAIL 50: NEED TO SPECIFY WOOD TO
 MASONRY STRAPS. SEE CATALOGUE FOR
 MASONRY CONNECTORS.
  
 19- ENTRY DOOR PRODUCT APPROVAL
 SUBMITTED IS FOR 6'-8" DOORS. NEED 8'-0"
 HIGH DOORS.
  
 20- REVISE ENERGY CALCULATIONS. THERE IS
 NOT EXTERIOR FRAMED WALLS. 2ND FLOOR IS
 MASONRY TOO.
  
 21- SURVEYOR NEED TO SIGN AND DATE
 SURVEY AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
  
 22- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-13 Cont ID  
Sent By dpalmer Date 2006-03-13 Time 20:27 Rev Time 0.00
Received By dpalmer Date 2006-03-13 Time 20:27 Sent To PC
Notes
2006-03-13 00:00:00REDLINED:
 VIF THE OCP FOR AHU #2 IS TOO SMALL,
 THIS SHALL BE SIZED AT A MIN OF 125%.
  
 NFPA-72 HAS CHANGE TO 2002 11.5.1.1, AND
 11.8.3.5

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-16 Cont ID  
Sent By dpalmer Date 2006-02-16 Time 13:58 Rev Time 0.00
Received By dpalmer Date 2006-02-16 Time 13:58 Sent To PC
Notes
2006-02-16 00:00:00REDLINED.
  
 210.70, LS101 7.8 FOR REAR PORCH.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 15:28 Rev Time 0.33
Received By dpalmer Date 2005-07-15 Time 15:28 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 14:47 Rev Time 0.50
Received By dpalmer Date 2005-04-25 Time 13:39 Sent To M
Notes
2005-04-25 00:00:00********UNSAT *********
  
 1)NOTE: PLEASE SEE PANEL "B" (2P80A)
 FEEDING #12 AWG.PLEASE SEE 310.16,240.4
  
 2)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52
  
 3)NOTE: PLEASE SEE CODES REFERENCED IN
 NOTES ARE FROM THE 1996 NEC. PLEASE SEE
 NEW REVISED ARTS. IN 2002 NEC.
  
 4)NOTE: PLEASE SEE SD'S SHOWN ON MORE
 THAN ONE CIRCUIT.
 PLEASE SEE ALL SD'S ARE REQUIRED TO BE
 WIRED "INLINE". THEY CAN NOT BE WIRED
 INLINE AND BE ON TWO SEPARATE
 PHASES/CIRCUITS.
 NEC
  
 5)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH PANEL SCHEDULE.
 PLEASE SEE A-21 FOR OVEN ALSO SHOWN FOR
 SD'S.
 PLEASE SEE OVEN SHOWN ON PLANS AS SPACE?
 ETC.
  
 6)NOTE: PLEASE LABEL PANEL IN GARAGE.
 PLEASE VERIFY PANEL "B WHICH IS SHOWN
 NEXT TO METER, BUT BEING FED FROM PANEL
 "A" LOCATED INSIDE.
 PLEASE ALSO SEE MIN CLEARENCE FOR PANEL
 "B". 110.26
  
 7)NOTE: PLEASE VERIFY KW LOAD FOR OVEN.
 (THIS IS ONLY A NOTE).
  
 PLEASE SEE SOME OF THE ABOVE ITEMS HAVE
 BEEN REDLINED IN SOME LOCATIONS ON PLANS
 FOR ABOVE COMMENTS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 16:53 Sent To B
Notes
2006-03-21 00:00:00TO JG DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 10:28 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 10:28 Sent To E
Notes
2006-03-10 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 18:09 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 18:09 Sent To E
Notes
2006-02-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 18:06 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 18:06 Sent To B
Notes
2006-02-15 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-18 Cont ID  
Sent By adarroug Date 2005-11-18 Time 09:58 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 09:58 Sent To B
Notes
2005-11-18 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 16:35 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 16:35 Sent To E
Notes
2005-07-12 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 11:12 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 11:12 Sent To E
Notes
2005-04-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-31 Cont ID  
Sent By jgomez Date 2005-05-31 Time 11:00 Rev Time 0.00
Received By jgomez Date 2005-04-15 Time 14:01 Sent To PC
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-01 Cont ID  
Sent By rregueir Date 2005-08-01 Time 16:47 Rev Time 0.00
Received By rregueir Date 2005-08-01 Time 16:47 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By prafter Date 2005-04-26 Time 13:51 Rev Time 1.00
Received By prafter Date 2005-04-26 Time 13:51 Sent To B
Notes
2005-04-26 00:00:00MECH. PLAN REVIEW.
  
 FIRST FLOOR:
 1. NO R/A OUT OF FIRST FLOOR MASTER
 BEDROOM AREA.2003 FBC/M 601.4 .
 2. NO EXHAUST FAN REFLECTED IN MASTER
 BATH AREA.2001 FBC/M 402.3.1 .
 3. AHU #1 SUPPLY AIR REFLECT 12" TO
 FIRST TRIANGEL THEN GOES TO 14" .
  
 SECOND FLOOR:
 1. AHU #2 NOT REFLECTED ON PLAN.
 2. R/A DUCT BETWEEN AHU #2 AND 24/18
 GRILL NOT REFLECTED.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-01 Cont ID  
Sent By jleech Date 2005-08-01 Time 13:06 Rev Time 0.33
Received By jleech Date 2005-08-01 Time 13:05 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-04-29 Cont ID  
Sent By kstevens Date 2005-04-29 Time 13:24 Rev Time 0.50
Received By kstevens Date 2005-04-29 Time 13:24 Sent To B1
Notes
2005-04-29 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 PLUMBING
  
 1) SHT MP SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. - THE RISER
 SHOWS THREE BATHROOMS ON THE SECOND
 FLOOR, BUT THE FLOOR PLAN ONLY SHOWS TWO
 BATHROOMS. SECTION 104.2.1. (ALSO THE
 RISER DIAGRAM IS REVERSE FROM THE FLOOR
 PLAN). PLEASE CORRELATE THE RISER
 DIAGRAM WITH THE FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-04 Cont ID  
Sent By mmclean Date 2005-08-04 Time 12:03 Rev Time 0.00
Received By mmclean Date 2005-08-04 Time 12:03 Sent To  
Notes
2005-08-04 00:00:00RE-STAMP OF PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-21 Cont ID  
Sent By mmclean Date 2005-04-21 Time 13:26 Rev Time 0.00
Received By mmclean Date 2005-04-21 Time 13:26 Sent To I
Notes
***NONE***