Plan Review Details - Permit 05040914
Plan Review Stops For Permit 05040914
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-02-07 Cont ID  
Sent By jgomez Date 2006-02-07 Time 17:49 Rev Time 0.40
Received By jgomez Date 2006-02-07 Time 17:49 Sent To PC
Notes
2006-02-07 00:00:00ENERGY CALCULATIONS AND BUILDING
 REVISIONS AND PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-12-07 Cont ID  
Sent By jgomez Date 2005-12-07 Time 12:27 Rev Time 0.75
Received By jgomez Date 2005-12-07 Time 12:27 Sent To PC
Notes
2005-12-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- ENERGY CALCULATIONS SUBMITTED ARE FBC
 2004 FORM. NEED FBC 2001 FORMS SINCE
 PLANS WERE REVIEWED UNDER THE FBC 2001.
  
 2- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 OF
 DEPARMENT OF COMMUNITY AFFAIRS (DCA)
 FOR:
 A) ATRIUM DOOR. SEE PLANS FOR DOOR SIZE
 AND SWING DIRECTION.
  
 B) FRENCH DOORS AT GREAT ROOM. SEE PLANS
 FOR SIZE SPECIFIED.
  
 3- SHEET A-5 WAS NOT SUBMITTED WITH THIS
 PACKAGE. NEED TO SUBMIT IR TO SEE ROOF
 PLAN REVISIONS.
  
 4- OWES $60.00 FOR THIS SUBMITTAL
 REVISION FEES. ($50.00 FLAT FEE PLUS ONE
 DRAWINGS).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-31 Cont ID  
Sent By jgomez Date 2005-08-31 Time 13:08 Rev Time 0.50
Received By jgomez Date 2005-08-31 Time 12:08 Sent To PC
Notes
2005-08-31 00:00:00SUBMITTAL BUILDING REVIEW CHECKLIST:
 1- SEPARATE PERMIT FOR SHUTTERS HAS NOT
 BEEN APPLIED FOR YET.
  
 2- ROOF FRAMING PLAN: CONNECTORS NEED TO
 BE REVISED AT ENTRY FOYER AREA. TRUSSES
 ARE RESTING ON A GIRDER TRUSS, NOT ON A
 CONCRETE BEAM. REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 3- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS SPECIFIED FOR CONNECTOR HUS26.
 SEE 2005 CATALOGUE.
  
 4- ONE HOUR FIRE RATED DOOR AT ATRIUM
 PRODUCT APPROVAL SUBMITTED IS FOR
 OUTSWING DOOR. PLANS SHOW INSWING DOOR.
 REVISE AS REQUIRED.
 ***NOTE: DOOR AT THIS LOCATION NEED NOT
 TO BE FIRE RATED. WALL IS NOT LOCATED IN
 THE ZERO LOT LINE. BESIDES, THIS WALL IS
 MORE LIKE A FENCE NOT A BUILDING WALL.
 THEREFORE, TABLE 600 FBC 2001 DOESN'T
 APPLY.
  
 5- WINDOW MULLION SIZE SPECIFIED FOR
 FIXED WINDOWS AT GREAT ROOM DOESN'T
 RESIST THE CALCULATED DESIGN PRESSURES.
 SEE PRODUCT APPROVAL AND REVISE SIZE AS
 REQUIRED. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 6- ALL REVISED DRAWINGS WILL BE SUBJECT
 TO THE REVISION FEES. SEE THE SUBMITTAL
 FORM FOR APPLICABLE FEES.
  
 7- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR FRENCH DOORS. SEE PLANS FOR
 REQUIRED SIZE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By jgomez Date 2005-06-28 Time 17:41 Rev Time 2.00
Received By jgomez Date 2005-06-28 Time 17:40 Sent To PC
Notes
2005-06-28 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- CONTRACTOR AGREED TO APPLY FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2- SUBMIT SOIL TEST REPORT WITH FOOTING
 SIZE REVISION.
 3- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT FRONT PORCH MASONRY BEAM.
 NEED MASONRY CONNECTOR. SEE DETAIL 5/D1.
 **NOTE: ROOF FRAMING PLAN CALLS FOR
 DETAIL 6/D1. REVISE FOR 5/D1.
 4- TRUSS ANCHOR SCHEDULE: REVISE SIZE OF
 NAIL USED FOR HUS26. SEE CATALOGUE.
 5- PROVIDE PRODUCT APPROVAL FOR:
 A) 1 HR FIRE RATED ASSEMBLY EGRESS OP'G.
  
 B) FRENCH DOORS AS SHOWN ON PLANS.
 C) 8'-0" HIGH ENTRY DOORS.
 6- PROVIDE CLEAR WINDOW AND DOOR
 SCHEDULES WITH MATCHING SYMBOLS.
 7- PROVIDERECORDED EGRESS EASEMENT.
 8- REVISE SIZE OF WINDOW SPECIFIED ON
 WINDOW SCHEDULE FOR BEDROOM #3. SEE PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By jgomez Date 2005-05-20 Time 08:27 Rev Time 0.00
Received By jgomez Date 2005-06-28 Time 17:40 Sent To PC
Notes
2005-05-20 00:00:00CHECKLIST:
  
 1- MEETING WITH RON ELLISH. HE REQUESTED
 TO LOG OUT PLANS TO MAKE CORRECTIONS
 BASED ON COMMENTS PREVIOUSLY DONE TO
 SAME MODEL.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2005-06-28 Cont ID  
Sent By jgomez Date 2005-06-28 Time 17:40 Rev Time 0.00
Received By jgomez Date 2005-06-28 Time 17:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-17 Cont ID  
Sent By dpalmer Date 2006-01-17 Time 11:04 Rev Time 0.00
Received By dpalmer Date 2006-01-17 Time 10:56 Sent To PC
Notes
2006-01-17 00:00:00REDLINED 210.11C3, SHOWS A-38 AS BLANK
 YET THIS IS SHOWN ON PLANS AS BATHRM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 16:37 Rev Time 0.33
Received By dpalmer Date 2005-06-13 Time 16:31 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 13:07 Rev Time 0.40
Received By dpalmer Date 2005-04-25 Time 13:07 Sent To M
Notes
2005-04-25 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PANEL "A" SHOWS FEED
 TO PANEL "B" AS 100A OCP ON #6 AWG.
 PLEASE SEE 240.4,310.16 AND PLEASE
 CORRELATE WITH RISER DIAGRAM.
 PLEASE ALSO SEE THIS IS SHOWN AS 100A SP
 BRKR ON ONE PHASE? (MISPRINT)
  
 2)NOTE: PLEASE SEE PANEL "B" SHOWS SUB
 PANEL "C" IN TWO DIFFERENT LOCATIONS?
 PLEASE SEE THIS IS SHOWN ON SAME PHASE.
 PLEASE ALSO CORRELATE AWG FOR 60A OCP.
 SHOWS #6 AND #8?
 PLEASE ALSO SEE SINGLE POLE 60A FOR
 ADDITIONAL SUB PANEL.
 PLEASE SEE 240.4,310.16, 310.15B6
  
 3)NOTE: PLEASE SEE NOTE ADDED TO CENTER
 OF PLANS WHICH IS A PROVISO SET UP BY A
 PLAN REVIEWER FOR A PREVIOUS PROJECT.
 THIS COMMENT FROM OTHER ELECTRICAL PLAN
 REVIEW SHOULD NOT BE LOCATED ON THESE
 PLANS.
 PLEASE REMOVE.
  
 4)NOTE: PLEASE SEE SD'S ARE REQUIRED TO
 BE WIRED "INLINE" ON THE SAME CIRCUIT,
 HOWEVER PLANS INDICATE TWO SEPARATE
 CIRCUITS FOR THE SD'S.THESE MAY NOT BE
 ON THE SAME CIRCUIT.
 NFPA-72 8-1.4.1.6.2
  
 5)NOTE: PLEASE SEE ONE OF THE ABOVE
 CIRCUITS FOR SD'S (#38) IS THE SAME
 CIRCUIT ON PANEL SCHEDULE FOR SUB PANEL
 "B".
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
 215.5
  
 7)NOTE: PLEASE SHOW LOADS ON EACH
 ELECTRICAL PANEL. PANEL "B AND "C
 MENTIONS TO SEE LOAD CALCS, HOWEVER
 THESE PANELS NEED TO SHOW ACTUAL LOAD
 FOR THOSE PANELS.
 220,215.5
  
 8 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 9)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS SHOWN ON ON PANEL SCHEDULE,
 HOWEVER THIS IS NOT SHOWN ON PLANS AT
 WHAT APPEARS TO BE THE WP/JACUZZI TUB.
  
 10)NOTE: PLEASE SEE MISSING GFI RECEPT
 ON KITCHEN COUNTERSPACE.
 210.52C1,210.8A6
  
 PLEASE BE SURE TO REMOVE ALL OLD VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 PLEASE SEE ONE COPY/SET OF OLD SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 09:40 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 09:40 Sent To B
Notes
2006-02-06 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-01-06 Cont ID  
Sent By adarroug Date 2006-01-06 Time 09:50 Rev Time 0.00
Received By adarroug Date 2006-01-06 Time 09:50 Sent To E
Notes
2006-01-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 08:55 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 08:55 Sent To B
Notes
2005-10-19 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 16:21 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 16:21 Sent To B
Notes
2005-07-29 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 15:55 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 15:55 Sent To B
Notes
2005-07-29 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 08:19 Rev Time 0.00
Received By shill Date 2005-06-08 Time 08:19 Sent To E
Notes
2005-06-08 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 11:10 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 11:10 Sent To E
Notes
2005-04-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-20 Cont ID  
Sent By jgomez Date 2005-05-20 Time 08:29 Rev Time 0.00
Received By jgomez Date 2005-04-15 Time 14:02 Sent To PC
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-21 Cont ID  
Sent By hmoser Date 2005-06-21 Time 17:40 Rev Time 0.00
Received By hmoser Date 2005-06-21 Time 17:17 Sent To B
Notes
2005-06-21 00:00:00PASS PRIVISO
 PLEASE SIZE DUCT THAT IS MARKED ON THE
 PLAN BEFOR ROUGH INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By prafter Date 2005-04-26 Time 10:53 Rev Time 0.50
Received By prafter Date 2005-04-26 Time 10:53 Sent To P
Notes
2005-04-26 00:00:00MECH. PLAN REVIEW.
 SUPPLY AIR DUCT NOT SIZED TO GUEST
 SUITE.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By kstevens Date 2005-06-20 Time 14:25 Rev Time 0.33
Received By kstevens Date 2005-06-20 Time 14:25 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-03 Cont ID  
Sent By jleech Date 2005-05-03 Time 16:03 Rev Time 0.33
Received By jleech Date 2005-05-03 Time 16:03 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-21 Cont ID  
Sent By mmclean Date 2005-04-21 Time 15:51 Rev Time 0.00
Received By mmclean Date 2005-04-21 Time 15:51 Sent To I
Notes
***NONE***