Plan Review Stops For Permit 05040912 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2005-04-20 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2005-04-20 |
Time |
13:36 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
2005-04-20 |
Time |
13:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-04-14 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2005-04-14 |
Time |
10:51 |
Rev Time |
0.75 |
Received By |
lsmith |
Date |
2005-04-14 |
Time |
10:51 |
Sent To |
|
|
Notes |
2005-04-14 00:00:00 | BUILDING PLAN REVIW: FAILED | | | | 1. WHAT IS THE SQ. FT. OF SHINGLES & | | PITCH? | | | | 2. BUILDING IS LOCATED IN THE FIRE | | DISTRICT. SUBMIT DOCUMENTATION ON FIRE | | RATING OF ROOFING PRODUCTS. | | | | 2. THE PRODUCT APPROVAL FOR THE FLAT | | SYSTEM TYPE E-3 & E-2 ARE FOR AN | | UNDERLAYMENT FOR A TILE ROOF. SUBMIT THE | | CORRECT SYSTEM FOR A NON-INSULATED WOOD | | DECK SYSTEM E-1. | | 3. SUBMIT THE ROOFING SYSTEM APPROVAL | | SHEETS PGS. 2-8 & HIGHLIGHT THE ITEMS | | USED IN THIS FLAT ROOF SYSTEM. | | | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH, BUILDING PLANS EXAMINER | | 805-6713 | | | | |
|
|
|