Plan Review Details - Permit 05040903
Plan Review Stops For Permit 05040903
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-02-28 Cont ID  
Sent By jgomez Date 2006-02-28 Time 14:16 Rev Time 0.33
Received By jgomez Date 2006-02-28 Time 14:16 Sent To P
Notes
2006-02-28 00:00:00DRAWING A-1.0 SENT TO PLUMBING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-02-15 Cont ID  
Sent By jgomez Date 2006-02-15 Time 07:55 Rev Time 0.40
Received By jgomez Date 2006-02-15 Time 07:55 Sent To P
Notes
2006-02-15 00:00:00BUILDING REVISION CHECKLIST:
 1- PLUMBING RISER DIAGRAM IS PART OF THE
 CONSTRUCTION DOCUMENTS SUBMITTED BY THE
 ARCHITECT AND IT WAS CROSSED OUT. SUBMIT
 CLEAN COPIES TO ROUTE PLANS FOR PROPER
 REVIEW TRADES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-01-18 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 07:29 Rev Time 0.50
Received By jgomez Date 2006-01-18 Time 07:45 Sent To PC
Notes
2006-01-18 00:00:00BUILDING REVISION CHECKLIST:
 1- DRAWING A-1.0 INCLUDES PLUMBING RISER
 DIAGRAM AND IT WAS CROSS OUT WITH THE
 WORDS NIC. THIS PLUMBING RISER DIAGRAM
 IS PART OF THE CONSTRUCTION DOCUMENTS
 AND IT CAN'T BE CROSSED OUT.RESUBMIT
 CLEAN DRAWINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (5610805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-21 Cont ID  
Sent By jgomez Date 2005-09-21 Time 15:16 Rev Time 0.50
Received By jgomez Date 2005-09-21 Time 15:16 Sent To PC
Notes
2005-09-21 00:00:00CORRECTED PLANS AND REQUESTED PRODUCT
 APPROVAL AND ENERGY CALCS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-29 Cont ID  
Sent By jgomez Date 2005-06-29 Time 17:18 Rev Time 2.00
Received By jgomez Date 2005-06-29 Time 17:18 Sent To PC
Notes
2005-06-29 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- REVISE ENERGY CALCULATIONS TO BE
 WORST CASE SCENARIO.
 3- REVISE DOOR AND WINDOW SCHEDULE TO
 MATCH FLOOR PLAN. INCLUDING SYMBOL USED.
 4- DETAIL 5/D-1; CONNECTOR HTS20 CAN'T
 SUPPORT BEAM. REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5- TRUSS ANCHOR SCHEDULE: UPDATE NAIL
 SIZE FOR HUS26 CONNECTOR. SEE CATALOGUE.
 6- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT ENTRY PORCH TO MATCH
 DETAILS 5 & 6 OF DRAWINGS D-1.
 7- PROVIDE PRODUCT APPROVAL FOR 9'-0" &
 12'-0" WIDE SLIDING GLASS DOORS.
 8- SHEET A-5.0 SHEAR VALUES NOTE:
 PROVIDE THE HAND CALCULATIONS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B) SPECIFY EDITION OF THE MANUAL.
 C)WHY USING TIMBER MANUAL FOR TAPCONS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 9- REVISE REAR ELEVATION: 12'-0" WIDE
 SLIDING GLASS DOOR IS DRAWN INCORRECTLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By jgomez Date 2005-05-20 Time 08:06 Rev Time 0.25
Received By jgomez Date 2005-05-20 Time 08:04 Sent To PC
Notes
2005-05-20 00:00:00CHECKLIST:
 1- MEETING WITH RON ELLISH. HE REQUESTED
 TO LOG OUT PLANS TO MAKE CORRECTIONS
 BASED ON PREVIOUS COMMENTS TO SAME
 MODEL.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 07:28 Rev Time 0.00
Received By dpalmer Date 2006-02-09 Time 07:28 Sent To B
Notes
2006-02-09 00:00:00** REDLINED **
  
 VERIFY OCP FOR CU, SHOWS 9.8KW, 40A OCP
  
 MIN 8' GROUND ROD REQUIRED PER 250.52A
  
 VERIFY MIN OCP FOR AHU#2, PER 424.3B,
 MIN OCP 125%.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 17:29 Sent To PC
Notes
2006-02-03 00:00:00 
  
 PLEASE SEE MIN GRND ROD 8' PER
 250.52A5

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 17:12 Rev Time 0.25
Received By dpalmer Date 2005-06-13 Time 17:12 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 10:05 Rev Time 0.50
Received By dpalmer Date 2005-04-26 Time 10:05 Sent To M
Notes
2005-04-26 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PANEL "A" SHOWS FEED
 TO PANEL "B" AS 100A OCP ON #6 AWG.
 PLEASE SEE 240.4,310.16 AND PLEASE
 CORRELATE WITH RISER DIAGRAM.
 PLEASE ALSO SEE THIS IS SHOWN AS 100A SP
 BRKR ON ONE PHASE? (MISPRINT)
  
 2)NOTE: PLEASE SEE PANEL "B" SHOWS SUB
 PANEL "C" IN TWO DIFFERENT LOCATIONS?
 PLEASE SEE THIS IS SHOWN ON SAME PHASE.
 PLEASE ALSO CORRELATE AWG FOR 60A OCP.
 SHOWS #6 AND #8?
 PLEASE ALSO SEE SINGLE POLE 60A FOR
 ADDITIONAL SUB PANEL.
 PLEASE SEE 240.4,310.16, 310.15B6
  
 3)NOTE: PLEASE SEE NOTE ADDED TO CENTER
 OF PLANS WHICH IS A PROVISO SET UP BY A
 PLAN REVIEWER FOR A PREVIOUS PROJECT.
 THIS COMMENT FROM OTHER ELECTRICAL PLAN
 REVIEW SHOULD NOT BE LOCATED ON THESE
 PLANS.
 PLEASE REMOVE.
  
 4)NOTE;
  
 5)NOTE: PLEASE SEE ONE OF THE ABOVE
 CIRCUITS FOR SD'S (#38) IS THE SAME
 CIRCUIT ON PANEL SCHEDULE FOR SUB PANEL
 "B".
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
 215.5
  
 7)NOTE: PLEASE SHOW LOADS ON EACH
 ELECTRICAL PANEL. PANEL "B AND "C
 MENTIONS TO SEE LOAD CALCS, HOWEVER
 THESE PANELS NEED TO SHOW ACTUAL LOAD
 FOR THOSE PANELS.
 220,215.5
  
 8 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 9)NOTE: PLEASE SEE PLANS REFERENCE THE
 1999 NEC FOR 210.12. WE ARE UNDER THE
 2002 NEC.
  
 PLEASE BE SURE TO REMOVE ALL OLD VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 PLEASE SEE ONE COPY/SET OF OLD SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 18:15 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 18:15 Sent To E
Notes
2006-02-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 15:47 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 15:47 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 18:58 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 18:58 Sent To B
Notes
2005-08-24 00:00:00TO "JGOMEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 09:37 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 09:37 Sent To E
Notes
2005-06-08 00:00:00TO 'DP' DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 09:21 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 09:21 Sent To E
Notes
2005-04-26 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-20 Cont ID  
Sent By jgomez Date 2005-05-20 Time 08:07 Rev Time 0.25
Received By jgomez Date 2005-04-18 Time 16:45 Sent To PC
Notes
2005-04-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-05-02 Cont ID  
Sent By prafter Date 2005-05-02 Time 10:55 Rev Time 0.50
Received By prafter Date 2005-05-02 Time 10:54 Sent To B
Notes
2005-05-02 00:00:00MECH. PLAN REVIEW:
  
 PRIVISO:
 AHU #2 REQUIRES AUX.DRAIN PAN WITH
 DRAIN PROTECTION. 2000 FBC/M 307.2.3 .
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-02-28 Cont ID  
Sent By jleech Date 2006-02-28 Time 17:22 Rev Time 0.00
Received By jleech Date 2006-02-28 Time 17:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-02-16 Cont ID  
Sent By jleech Date 2006-02-16 Time 14:40 Rev Time 0.25
Received By jleech Date 2006-02-16 Time 14:40 Sent To B
Notes
2006-02-16 00:00:00PLEASE DONOT "X" OUT PARTS OF THE PLAN.
 IF REVISIONS ARE REQUIRED THE PLANS MEED
 TO REVIEWED AND RESTAMPED BY ALL TRADES
 INVALVED.
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By jleech Date 2005-06-20 Time 16:16 Rev Time 0.25
Received By jleech Date 2005-06-20 Time 16:16 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-05 Cont ID  
Sent By jleech Date 2005-05-05 Time 14:01 Rev Time 0.33
Received By jleech Date 2005-05-05 Time 14:01 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By mmclean Date 2005-04-25 Time 18:21 Rev Time 0.00
Received By mmclean Date 2005-04-25 Time 18:21 Sent To I
Notes
***NONE***