Plan Review Details - Permit 05040901
Plan Review Stops For Permit 05040901
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-02-28 Cont ID  
Sent By jgomez Date 2006-02-28 Time 14:26 Rev Time 0.33
Received By jgomez Date 2006-02-28 Time 14:26 Sent To P
Notes
2006-02-28 00:00:00DRAWING A.1-0 SUBMITTAL. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-02-13 Cont ID  
Sent By jgomez Date 2006-02-13 Time 13:11 Rev Time 0.40
Received By jgomez Date 2006-02-13 Time 12:53 Sent To PC
Notes
2006-02-13 00:00:00REVISION RE-SUBMITTAL 2ND CHECKLIST:
 1- SAME COMMENT FROM PREVIOUS CHECKLIST.
 PLUMBING RISER DIAGRAM IS PART OF THE
 CONSTRUCTION DOCUMENTS AND IT WAS
 CROSSED OUT BY HAND AGAIN. SEE ATTACHED
 COMMENT FROM PREVIOUS CHECKLIST.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-01-18 Cont ID  
Sent By jgomez Date 2006-01-17 Time 18:58 Rev Time 0.75
Received By jgomez Date 2006-01-17 Time 18:58 Sent To PC
Notes
2006-01-17 00:00:00BUILDING REVISION CHECKLIST;
 1- DRAWING A-1.0 INCLUDES PLUMBING RISER
 DIAGRAM AND IT WAS CROSS OUT WITH THE
 WORDS NIC. THIS PLUMBING RISER DIAGRAM
 IS PART OF THE CONSTRUCTION DOCUMENTS
 AND IT CAN'T BE CROSSED OUT. RE-SUBMIT
 CLEAN DRAWINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-21 Cont ID  
Sent By dpalmer Date 2006-01-10 Time 09:29 Rev Time 0.50
Received By jgomez Date 2005-09-21 Time 16:37 Sent To PC
Notes
2005-09-21 00:00:00CORRECTED DRAWINGS AND REQUESTED PRODUCT
 APPROVALS AND ENERGY CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-30 Cont ID  
Sent By jgomez Date 2005-06-30 Time 10:30 Rev Time 2.00
Received By jgomez Date 2005-06-30 Time 10:30 Sent To PC
Notes
2005-06-30 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- NEED REVISED ENERGY CALCULATIONS FOR
 WORST CASE SCENARIO.
 3- REVISE DOOR/WINDOW SCHEDULE TO MATCH
 PLANS. INCLUDING SYMBOL USED.
 4- DETAIL 5/D1: CONNECTOR HTS20 CAN'T
 SUPPORT BEAM. REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5- TRUSS ANCHOR SCHEDULE: UPDATE NAIL
 SIZE USED FOR HUS26. SEE CATALOGUE.
 6- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT ENTRY PORCH TO MATCH
 DETAILS 5 & 6 OF DRAWING D-1.
 7- PROVIDE PRODUCT APPROVAL FOR:
 A) 9'-0" WIDE SLIDING GLASS DOORS.
 B) 8'-0" HIGH ENTRY DOORS.
 8- SHEET A-5 SHEAR VALUE NOTE:
 A) PROVIDE HAND CALCULATIONS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B) WHY USING TIMBER MANUAL TO CALCULATE
 TAPCON VALUES?.
 C) SPECIFY TIMBER MANUAL EDITION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By jgomez Date 2005-05-20 Time 07:40 Rev Time 0.25
Received By jgomez Date 2005-05-20 Time 07:39 Sent To PC
Notes
2005-05-20 00:00:00CHECKLIST:
 1- MEETING WITH RON ELLISH. HE REQUESTED
 TO LOG OUT PLANS TO MAKE REVISIONS BASED
 ON COMMENTS ADDRESSED TO SAME MODEL ON
 PREVIOUS CHECKLISTS.
2005-05-02 00:00:00MECH. PLAN REVIEW:
  
 A/C PLANS DOES NOT MATCH HOUSE PLANS,
 PLEASE SUBMIT CORRECT A/C PLANS.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE IF THEAR ANY QUESTIONS.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-08-03 Cont ID  
Sent By dpalmer Date 2006-08-03 Time 20:19 Rev Time 0.00
Received By dpalmer Date 2006-08-03 Time 20:19 Sent To PC
Notes
2006-08-03 00:00:00REDLINED TO VERIFY LOADONCU #1,
 REVISE AS NEEDED AS LOAD IS SHOWN AS
 9.8KW.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2006-02-09 Time 11:30 Sent To B
Notes
2006-02-09 00:00:00** REDLINED **
  
 VERIFY OCP FOR CU, SHOWS 9.8KW, 40A OCP
  
 MIN 8' GROUND ROD REQUIRED PER 250.52A
  
 VERIFY MIN OCP FOR AHU#2, PER 424.3B,
 MIN OCP 125%.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 20:17 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 20:17 Sent To PC
Notes
2006-02-03 00:00:00REDLINED:
  
  
 MIN OCP FOR AHU#2 SHALL BE SIZED A MIN
 OF 125%. 424.3B
  
 MIN GRND ROD SAHLL BE 8' PER 250.52A5

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-01-10 Cont ID  
Sent By dpalmer Date 2006-01-09 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2006-01-09 Time 16:45 Sent To B
Notes
2006-01-09 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE SEE PANEL "A" IS MISSING
 LOAD FROM PANEL "B"AND "C".
 PLEASE ALSO SEE LOADS ON PANEL "B" AND
 "C". SOME ARE SHOWN WITH 83 KW, 96, KW
 ETC.
 PLEASE ADJUST LOADS AND CALCUALTIONS.
 220, 215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 DEN
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 17:07 Rev Time 0.30
Received By dpalmer Date 2005-06-13 Time 17:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 10:59 Rev Time 0.30
Received By dpalmer Date 2005-04-26 Time 10:59 Sent To M
Notes
2005-04-26 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PANEL "A" SHOWS FEED
 TO PANEL "B" AS 100A OCP ON #6 AWG.
 PLEASE SEE 240.4,310.16 AND PLEASE
 CORRELATE WITH RISER DIAGRAM.
 PLEASE ALSO SEE THIS IS SHOWN AS 100A SP
 BRKR ON ONE PHASE? (MISPRINT)
  
 2)NOTE: PLEASE SEE PANEL "B" SHOWS SUB
 PANEL "C" IN TWO DIFFERENT LOCATIONS?
 PLEASE SEE THIS IS SHOWN ON SAME PHASE.
 PLEASE ALSO CORRELATE AWG FOR 60A OCP.
 SHOWS #6 AND #8?
 PLEASE ALSO SEE SINGLE POLE 60A FOR
 ADDITIONAL SUB PANEL.
 PLEASE SEE 240.4,310.16, 310.15B6
  
 3)NOTE: PLEASE SEE NOTE ADDED TO CENTER
 OF PLANS WHICH IS A PROVISO SET UP BY A
 PLAN REVIEWER FOR A PREVIOUS PROJECT.
 THIS COMMENT FROM OTHER ELECTRICAL PLAN
 REVIEW SHOULD NOT BE LOCATED ON THESE
 PLANS.
 PLEASE REMOVE.
  
 4)NOTE;
  
 5)NOTE: PLEASE SEE ONE OF THE ABOVE
 CIRCUITS FOR SD'S (#38) IS THE SAME
 CIRCUIT ON PANEL SCHEDULE FOR SUB PANEL
 "B".
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
 215.5
  
 7)NOTE: PLEASE SHOW LOADS ON EACH
 ELECTRICAL PANEL. PANEL "B AND "C
 MENTIONS TO SEE LOAD CALCS, HOWEVER
 THESE PANELS NEED TO SHOW ACTUAL LOAD
 FOR THOSE PANELS.
 220,215.5
  
 8 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 9)NOTE: PLEASE SEE PLANS REFERENCE 1999
 NEC FOR 210.12. WE HAVE BEEN UNDER THE
 2002 NEC SINCE JULY 1ST, 2003
  
 PLEASE BE SURE TO REMOVE ALL OLD VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 PLEASE SEE ONE COPY/SET OF OLD SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 12:04 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 12:04 Sent To E
Notes
2006-02-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 15:57 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-30 Cont ID  
Sent By adarroug Date 2005-12-30 Time 09:20 Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 09:20 Sent To E
Notes
2005-12-30 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 11:31 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 11:31 Sent To B
Notes
2005-08-24 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-07 Cont ID  
Sent By shill Date 2005-06-07 Time 15:37 Rev Time 0.00
Received By shill Date 2005-06-07 Time 15:37 Sent To E
Notes
2005-06-07 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 09:19 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 09:19 Sent To E
Notes
2005-04-26 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-20 Cont ID  
Sent By jgomez Date 2005-05-20 Time 07:45 Rev Time 0.00
Received By jgomez Date 2005-04-18 Time 16:44 Sent To PC
Notes
2005-04-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-06-21 Cont ID  
Sent By hmoser Date 2005-06-21 Time 18:03 Rev Time 0.00
Received By hmoser Date 2005-06-21 Time 17:44 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-15 Cont ID  
Sent By pkrauss Date 2005-05-15 Time 19:44 Rev Time 0.30
Received By pkrauss Date 2005-05-15 Time 19:44 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-02 Cont ID  
Sent By prafter Date 2005-05-02 Time 12:13 Rev Time 0.50
Received By prafter Date 2005-05-02 Time 12:13 Sent To P
Notes
2005-05-02 00:00:00MECH. PAN REVIEW:
  
 A/C PLAN DOES NOT MATCH HOUSE PLANS,
 PLEASE SUBMIT CORRECT A/C PLANS.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTION.
 MECH. PLAN REVIEW:
  
 A/C PLAN DOES NOT MATCH HOUSE PLANS,
 PLEASE SUBMIT CORRECTED A/C PLANS.
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-28 Cont ID  
Sent By jleech Date 2006-02-28 Time 17:12 Rev Time 0.00
Received By jleech Date 2006-02-28 Time 17:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By jleech Date 2005-06-20 Time 16:51 Rev Time 0.25
Received By jleech Date 2005-06-20 Time 16:51 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-04 Cont ID  
Sent By jleech Date 2005-05-04 Time 15:07 Rev Time 0.33
Received By jleech Date 2005-05-04 Time 15:07 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By mmclean Date 2005-04-25 Time 18:32 Rev Time 0.00
Received By mmclean Date 2005-04-25 Time 18:32 Sent To I
Notes
***NONE***