Plan Review Details - Permit 05040897
Plan Review Stops For Permit 05040897
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-01-30 Cont ID  
Sent By jgomez Date 2006-01-30 Time 18:14 Rev Time 0.50
Received By jgomez Date 2006-01-30 Time 18:07 Sent To PC
Notes
2006-01-30 00:00:00BLDG REVISION, DOOR PRODUCT APPROVAL AND
 REVISED ENERGY CALCS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-11-15 Cont ID  
Sent By jgomez Date 2005-11-15 Time 14:57 Rev Time 1.00
Received By jgomez Date 2005-11-15 Time 14:57 Sent To PC
Notes
2005-11-15 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- NOW ENERGY CALCULATIONS WERE REVISED
 USING FBC 2004 FORM. THIS HOUSE WAS
 PERMITTED USING THE FBC 2001 FORMS.
 MIS-MATCHING CODES IS NOT ALLOWED.
 PROVIDE ENERGY CALCS USING THE FBC 2001
 FORMS AS REQUIRED.
  
 2- PROVIDE DETAIL 7/D1 AS KEYED ON
 REVISED ROOF FRAMING PLAN. THERE IS NOT
 DETAIL 7 ON SHEET D1.
  
 3- RESUBMIT FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ONE HOUR FIRE RATED DOOR AT
 ATRIUM AS SPECIFIED ON PLANS:
 A) DRAWINGS SUBMITTED ARE FOR OUTSWING
 DOORS. NEED INSWING DOOR AS SHOWN ON
 PLANS AND DADE COUNTY NOA #02--0215.03
 SUBMITTED.
 B) DRAWINGS SUBMITTED ARE FOR 7'-0"
 HIGH DOORS. NEED 8'-0" HIGH DOOR AS
 SHOWN ON PLANS.
  
 4- APPLY FOR SHUTTERS UNDER A SEPARATE
 PERMIT AS AGREED ON PROVISO DATED 6-9-05
 TO AVOID DELAYS OR CONFLICTS GIVEN THE
 HIGH VOLUME OF APPLICATIONS AND THE
 SHORTAGE OF REVIEWING PERSONNEL.
  
 ***NOTE:
 STAMPED DRAWINGS AND PRODUCT APPROVAL
 ARE ALREADY APPROVED. CONTRACTOR TO KEEP
 THEM IN THE JOBSITE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-20 Cont ID  
Sent By jgomez Date 2005-09-20 Time 14:14 Rev Time 1.00
Received By jgomez Date 2005-09-20 Time 14:14 Sent To PC
Notes
2005-09-20 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- ENERGY CALCS WERE REVISED. NOW, THEY
 ARE TAKING THE CEILING FAN CREDIT.
 THEREFORE, NEED TO REVISE THE ELECTRICAL
 PLAN TO SHOW CEILING FAN SIZES IN ALL
 ROOMS AND THE CEILING FANS REQ'D FOR THE
 GREAT RM. SEE TABLE 6-6 CHAPTER 13 FBC.
 REVISION FEES WILL APPLY.
  
 2- REVISE ROOF FRAMING PLAN AT ENTRY
 PORCH. SHOW CORRECTLY WHEN THERE IS A
 CONCRETE BEAM OR WOOD BEAM. INCLUDING
 THE KNEEWALL AND SPECIFY CORRESPONDING
 CONNECTORS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC. REVISION FEES APPLY.
  
 3- REVISE NUMBER OF NAILS SPECIFIED
 FOR HUS26. SEE 2005 CATALOGUE.
  
 4- PROVIDE PRODUCT APPROVAL FOR ONE HR
 FIRE RATED ATRIUM DOOR THAT MATCHES
 PLANS.
  
 5- APPLY FOR SHUTTERS PERMIT AS AGREED
 ON PROVISO DATED 6-9-05.
  
 JULIO GOMEZ
 PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-09 Cont ID  
Sent By jgomez Date 2005-06-09 Time 17:46 Rev Time 2.00
Received By jgomez Date 2005-06-09 Time 17:46 Sent To E
Notes
2005-06-09 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- REVISE ENERGY CALCULATIONS. NEED
 CALCULATIONS DONE TO WORST CASE SCENARIO
 FOR THIS MODEL.
 3- SUBMIT SOIL TEST REPORT WITH FOOTING
 SIZE REVISION.
 4- REVISE FRONT ELEVATION TO DELETE 45
 DEGREEE WINDOWS (TABLE 600 FBC 2001)
 5- ROOF FRAMING PLAN. REVISE CONNECTOR
 SPECIFIED AT FRONT PORCH MASONRY BEAM.
 NEED MASONRY CONNECTOR. SEE DETAIL 5/D-1
 6- TRUSS ANCHOR SCHEDULE:REVISE TYPE OF
 NAIL USED FOR HUS26. SEE CATALOGUE.
 7- REVISE FRONT ELEVATION SHOWING SOLID
 ENTRY DOOR. SEE PRODUCT APPROVAL.
 8- PROVIDE PRODUCT APPROVAL FOR ONE HOUR
 FIRE RATED ASSEMBLY EGRESS OPENING.
 9- PROVIDE PRODUCT APPROVAL FOR 12'-0"
 WIDE SLIDING GLASS DOORS.
 10- PROVIDE PRODUCT APPROVAL FOR 8'-0"
 HIGH ENTRY DOORS. SUBMITTED 6'-8" DOORS.
 11- PROVIDE CLEAR WINDOW AND DOORS
 SCHEDULES. NEED MATCHING SYMBOLS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By jgomez Date 2005-05-20 Time 07:51 Rev Time 0.25
Received By jgomez Date 2005-05-20 Time 07:51 Sent To PC
Notes
2005-05-20 00:00:00CHECKLIST:
 1- MEETING WITH RON ELLISH. HE REQUESTED
 TO LOG OUT PLANS TO MAKE CORRECTIONS
 BASED ON PREVIOUS COMMENTS TO SAME
 MODEL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 17:23 Sent To PC
Notes
2006-02-03 00:00:00 
  
 2)NOTE: PLEASE SEE MIN GRND ROD 8' PER
 250.52A5
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 15:44 Rev Time 0.30
Received By dpalmer Date 2005-06-13 Time 15:44 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 10:50 Rev Time 0.40
Received By dpalmer Date 2005-04-26 Time 10:50 Sent To M
Notes
2005-04-26 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PANEL "A" SHOWS FEED
 TO PANEL "B" AS 100A OCP ON #6 AWG.
 PLEASE SEE 240.4,310.16 AND PLEASE
 CORRELATE WITH RISER DIAGRAM.
 PLEASE ALSO SEE THIS IS SHOWN AS 100A SP
 BRKR ON ONE PHASE? (MISPRINT)
  
 2)NOTE: PLEASE SEE PANEL "B" SHOWS SUB
 PANEL "C" IN TWO DIFFERENT LOCATIONS?
 PLEASE SEE THIS IS SHOWN ON SAME PHASE.
 PLEASE ALSO CORRELATE AWG FOR 60A OCP.
 SHOWS #6 AND #8?
 PLEASE ALSO SEE SINGLE POLE 60A FOR
 ADDITIONAL SUB PANEL.
 PLEASE SEE 240.4,310.16, 310.15B6
  
 3)NOTE: PLEASE SEE NOTE ADDED TO CENTER
 OF PLANS WHICH IS A PROVISO SET UP BY A
 PLAN REVIEWER FOR A PREVIOUS PROJECT.
 THIS COMMENT FROM OTHER ELECTRICAL PLAN
 REVIEW SHOULD NOT BE LOCATED ON THESE
 PLANS.
 PLEASE REMOVE.
  
 4)NOTE;PLEASE SEE MISSING RECEPT(S) PER
 210.52 C1, 210.8A6
  
 5)NOTE: PLEASE SEE ONE OF THE ABOVE
 CIRCUITS FOR SD'S (#38) IS THE SAME
 CIRCUIT ON PANEL SCHEDULE FOR SUB PANEL
 "B".
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
 215.5
  
 7)NOTE: PLEASE SHOW LOADS ON EACH
 ELECTRICAL PANEL. PANEL "B AND "C
 MENTIONS TO SEE LOAD CALCS, HOWEVER
 THESE PANELS NEED TO SHOW ACTUAL LOAD
 FOR THOSE PANELS.
 220,215.5
  
 8 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 9)NOTE: PLEASE SEE PLANS REFERENCE 1999
 NEC FOR 210.12. WE HAVE BEEN UNDER THE
 2002 NEC SINCE JULY 1ST, 2003
  
 10)NOTE: PLEASE SEE SD'S ON MULTIPLE
 CIRCUITS WHEN THEY ARE REQUIRED TO BE
 WIRED "INLINE". PLEASE SEE #38 AND 25.
  
 PLEASE BE SURE TO REMOVE ALL OLD VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 PLEASE SEE ONE COPY/SET OF OLD SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 15:19 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:51 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:51 Sent To B
Notes
2006-01-22 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 10:42 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 10:42 Sent To B
Notes
2005-10-14 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 18:11 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 18:11 Sent To B
Notes
2005-08-09 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 08:27 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 08:27 Sent To E
Notes
2005-06-08 00:00:00TO 'DP' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 09:17 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 09:17 Sent To E
Notes
2005-04-26 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-20 Cont ID  
Sent By jgomez Date 2005-05-20 Time 07:53 Rev Time 0.25
Received By jgomez Date 2005-04-15 Time 14:36 Sent To PC
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-05-02 Cont ID  
Sent By prafter Date 2005-05-02 Time 10:33 Rev Time 0.50
Received By prafter Date 2005-05-02 Time 10:33 Sent To B
Notes
2005-05-02 00:00:00MECH. PLAN REVIEW:
 PROVISO:
 AHU #2 REQUIRES AUX. DRAIN PAN WITH
 DRAIN PROTECTION.FBC/M 307.2.3 .
 PAT RAFTER 561/805/6728 OR805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-03-23 Cont ID  
Sent By mperson Date 2006-03-23 Time 12:00 Rev Time 0.33
Received By mperson Date 2006-03-23 Time 12:00 Sent To PC
Notes
2006-03-23 00:00:00REVISION: AS BUILT ISOMETRIC SANITARY
 RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-03-21 Cont ID  
Sent By mperson Date 2006-03-21 Time 11:47 Rev Time 1.25
Received By mperson Date 2006-03-21 Time 11:47 Sent To PC
Notes
2006-03-21 00:00:00REVISION DENIED
 REFERENCE:FBC-2004 PLUMBING AND CITY OF
 WEST PALM BEACH AMENDMENTS TO FBC-2004
 CHAPTER 1
  
 1. CHAPTER 1, SEC. 106.1 PER CHAPTER
 481, FLORIDA STATUTES, PART 1, REVISION
 DRAWINGS SHALL BE SIGNED, SEALED, AND
 DATED BY DESIGN PROFESSIONAL, WITH TITLE
 BLOCK.
 2. ISOMETRIC DRAWING FOR BATHROOM #2
 DOES NOT REFLECT DRAWING A-2.0. BATHROOM
 #2 IS OFFSET OF LAUNDRY.
 3. WASHING MACHINE IN LAUNDRY DOES NOT
 REFLECT LAYOUT ON A-2.0.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 UNDERSUPERVISION OF K.STEVENS
 (561)805-6721
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By kstevens Date 2005-06-20 Time 15:44 Rev Time 1.00
Received By kstevens Date 2005-06-20 Time 15:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-05 Cont ID  
Sent By jleech Date 2005-05-05 Time 14:39 Rev Time 0.33
Received By jleech Date 2005-05-05 Time 14:39 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By mmclean Date 2005-04-25 Time 18:49 Rev Time 0.00
Received By mmclean Date 2005-04-25 Time 18:49 Sent To I
Notes
***NONE***