Plan Review Details - Permit 05040895
Plan Review Stops For Permit 05040895
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-02-23 Cont ID  
Sent By jgomez Date 2006-02-23 Time 18:25 Rev Time 0.40
Received By jgomez Date 2006-02-23 Time 18:25 Sent To  
Notes
2006-02-23 00:00:00REVISED DRAWINGS #2 AND #5. REVISED
 ENERGY CALCS. ATRIUM DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-12-08 Cont ID  
Sent By jgomez Date 2005-12-08 Time 07:58 Rev Time 0.75
Received By jgomez Date 2005-12-08 Time 07:58 Sent To PC
Notes
2005-12-08 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- ENERGY CALCS SUBMITTED ARE FBC 2004
 FORMS. NEED TO SUBMIT FBC 2001 FORMS,
 SINCE PLANS WERE REVIEWED UNDER FBC 2001
  
 2- MISSING SHEET A-5. IT WAS NOT
 SUBMITTED IN THIS PACKAGE.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ATRIPUM DOOR AS REQUIRED BY
 RULE 9B-72. SEE SPECIFICATIONS ON PLANS
 FOR DOOR SIZE AND SWING DIRECTION.
  
 4- OWES $60.00 REVISION FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-01 Cont ID  
Sent By jgomez Date 2005-09-01 Time 09:26 Rev Time 0.75
Received By jgomez Date 2005-09-01 Time 09:26 Sent To PC
Notes
2005-09-01 00:00:00SUBMITTAL BUILDING REVIEW CHECKLIST:
 1- SEPARATE PERMIT FOR SHUTTERS HAS NOT
 BEEN APPLIED FOR YET.
  
 2- ENERGY CALCULATIONS WERE REVISED. NOW
 CEILING FAN CREDIT WAS TAKEN. THEREFORE,
 NEED TO REVISE ELECTRICAL PLAN SHOWING
 SIZE OF CEILING FANS, INCLUDING FANS IN
 THE GREAT ROOM AS REQUIRED BY TABLE 6-6
 OF CHAPTER 13 FBC 2001.
  
 3- ROOF FRAMING PLAN NEEDS TO BE REVISED
 AT ENTRY PORCH AREA TO MATCH FOUNDATION
 PLAN AND FLOOR PLAN. NOTICE THAT
 CONCRETE BEAM DOESN'T EXTEND ALL THE WAY
 INSIDE TO THE FOYER AREA. CONCRETE BEAM
 IS ONLY AT ENTRY PORCH AREA. REVISE ROOF
 FRAMING PLAN AS REQUIRED AND SPECIFIY
 CORRESPONDING CONNECTORS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS SPECIFIED FOR CONNECTOR HUS26.
 SEE 2005 CATALOGUE.
  
 5- ONE HOUR FIRE RATED DOOR AT ATRIUM
 PRODUCT APPROVAL SUBMITTED IS FOR
 OUTSWING DOOR. PLANS SHOW INSWING DOOR.
 REVISE AS REQUIRED.
  
 6- SPECIFY WINDOW MULLION AND ANCHORS
 FOR FIXED WINDOWS AT GREAT ROOM. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 7- PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLION SPECIFIED FOR FIXED WINDOWS AT
 GREAT ROOM.
  
 8- ALL REVISED DRAWINGS WILL BE SUBJECT
 TO THE REVISION FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-10 Cont ID  
Sent By jgomez Date 2005-06-10 Time 16:36 Rev Time 1.00
Received By jgomez Date 2005-06-10 Time 16:36 Sent To E
Notes
2005-06-10 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- REVISE ENERGY CALCULATIONS. NEED
 WORST CASE SCENARIO CALCS FOR THIS MODEL
 3- SUBMIT REVISED SOIL TEST REPORT.
 4- REVISE FRONT ELEVATION TO SHOW ENTRY
 DOOR SHOWN ON PRODUCT APPROVAL.
 5- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT ENTRY PORCH. NEED MASONRY
 CONNECTOR. SEE DETAIL 5/D-1.
 6- TRUSS ANCHOR SCHEDULE: REVISE TYPE OF
 NAIL USED FOR HUS26. SEE CATALOGUE.
 7- PROVIDE PRODUCT APPROVAL FOR ONE HOUR
 FIRE RATED ASSEMBLY EGRESS OPENING.
 8- PROVIDE PRODUCT APPROVAL FOR 12'-0"
 WIDE SLIDING GLASS DOORS.
 9- PROVIDE PRODUCT APPROVAL FOR 8'-0"
 HIGH ENTRY DOORS.
 10- PROVIDE CLEAR WINDOW AND DOOR
 SCHEDULES. NEED MATCHING SYMBOLS.
 11- PROVIDE COPY OF EGRESS EASEMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-13 Cont ID  
Sent By prafter Date 2005-05-02 Time 10:19 Rev Time 2.00
Received By jgomez Date 2005-05-13 Time 17:16 Sent To P
Notes
2005-05-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOC.
  
 2- SOIL TEST REPORT RECOMMENDS 18" MIN.
 FOOTING WIDTH. FOUNDATION PLAN CALLS FOR
 16" WIDTH. REVISE AS REQUIRED.
  
 3- 45 DEGREE WINDOW ON BEDROOM #3 AT
 ZERO LOT LINE WALL IS NOT ALLOWED BY
 TABLE 600 FBC 2001.
  
 4- PROVIDE NOTE ON DEN ROOM STATING THAT
 ROOM IS NOT ALLOWED TO BE USED FOR
 SLEEPING PURPOSES. OR, PROVIDE COMPLETE
 EGRESS REQUIREMENTS INCLUDING RECORDED
 EGRESS EASEMENT.
  
 5- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES.
 SPECIFY FASTENERS TYPE AND SPACING. SEE
 SECTION 2504.2 FBC 2001.
  
 6- SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE EXCEPTION IN
 SECTION 1909.3 FBC 2001.
  
 7- SPECIFY FOOTINGS FOR ENTRY COLUMNS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 8- SHEET A-5.0:A) ROOF NAILING ZONE
 DIAPHRAGM IS MISSING ZONE 3. SEE FIGURE
 1606.2(C) FBC 2001.
  
 B) DETAIL 3 SPECIFIED HGUS 28-2 SIMPSON
 CONNECTOR IS A WOOD TO WOOD CONNECTOR.
 NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. SEE CATALOGUE AND REVISE AS
 REQUIRED.
  
 C) DETAILS 1 AND 2: REVISE TYPE OF
 NAILS. SEE CATALOGUE.
  
 D) REVISE CONNECTOR SPECIFIED AT ENTRY
 PORCH. NEED MASONRY CONNECTOR. ALSO, SEE
 DETAIL 5/D-1 AND REVISE AS REQUIRED.
  
 9- REVISE/UPDATE TRUSS ANCHOR SCHEDULE.
 SEE LATEST CATALOGUE THAT WAS REVISED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 TYPE AND NUMBER OF NAILS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY
 MANUFACTURER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 10- A) RIGHT SIDE ELEVATION DOESN'T
 MATCH PLANS. BATHROOM #2 HAS GLASS BLOCK
 NOT WINDOW. REVISE AS REQUIRED.
  
 B) SHOW GLASS BLOCK ON LEFT ELEVATION TO
 MATCH PLAN. REVISE AS REQUIRED.
  
 11- CLARIFY IF USING STORM SHUTTERS OR
 IMPACT GLAZING. THEN, PROVIDE COMPLETE
 INFORMATION FOR EITHER METHOD.
  
 12- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR:A) ONE HOUR FIRE RATED
 ASSEMBLY AT EMERGENCY EGRESS OPENING.
  
 B) SLIDING GLASS DOORS. DRAWINGS
 SUBMITTED DON'T MATCH DADE COUNTY NOA
 SUBMITTED.
  
 C) PROVIDE PRODUCT APPROVAL FOR 12'-0"
 WIDE SLIDING GLASS DOORS. SEE PLANS.
  
 D) LARGE FIXED WINDOWS AS SHOWN ON GREAT
 ROOM. PRODUCT APPROVAL SUBMITTED DOESN'T
 COVER THOSE SIZES.
  
 E) 8'-0" HIGH ENTRY DOORS. DRAWINGS
 SUBMITTED ARE FOR 6'-8" HIGH DOORS.
  
 F) ALL TRUSS CONNECTORS AS SPECIFIED ON
 PLANS AFTER THEY ARE REVISED.
  
 13- SHEET D-1:A) CONNECTORS CS-16X AND
 HTS-20 SHOWN ON DETAILS 3,4 AND 5 ARE
 WOOD TO WOOD CONNECTORS. NEED TO SPECIFY
 MASONRY CONNECTORS. SEE CATALOGUE AND
 REVISE AS REQUIRED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 B) REVISE TYPE AND NUMBER OF NAILS FOR
 HUS26 CONNECTOR. SEE CATALOGUE.
  
 14- PLEASE DON'T STAPLE PRODUCT
 APPROVALS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 16:15 Sent To PC
Notes
2006-02-03 00:00:00REDLINED 250.52A5

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 15:38 Rev Time 0.33
Received By dpalmer Date 2005-06-13 Time 15:38 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 10:36 Rev Time 0.30
Received By dpalmer Date 2005-04-26 Time 10:36 Sent To M
Notes
2005-04-26 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PANEL "A" SHOWS FEED
 TO PANEL "B" AS 100A OCP ON #6 AWG.
 PLEASE SEE 240.4,310.16 AND PLEASE
 CORRELATE WITH RISER DIAGRAM.
 PLEASE ALSO SEE THIS IS SHOWN AS 100A SP
 BRKR ON ONE PHASE? (MISPRINT)
  
 2)NOTE: PLEASE SEE PANEL "B" SHOWS SUB
 PANEL "C" IN TWO DIFFERENT LOCATIONS?
 PLEASE SEE THIS IS SHOWN ON SAME PHASE.
 PLEASE ALSO CORRELATE AWG FOR 60A OCP.
 SHOWS #6 AND #8?
 PLEASE ALSO SEE SINGLE POLE 60A FOR
 ADDITIONAL SUB PANEL.
 PLEASE SEE 240.4,310.16, 310.15B6
  
 3)NOTE: PLEASE SEE NOTE ADDED TO CENTER
 OF PLANS WHICH IS A PROVISO SET UP BY A
 PLAN REVIEWER FOR A PREVIOUS PROJECT.
 THIS COMMENT FROM OTHER ELECTRICAL PLAN
 REVIEW SHOULD NOT BE LOCATED ON THESE
 PLANS.
 PLEASE REMOVE.
  
 4)NOTE;PLEASE SEE MISSING RECEPT(S) PER
 210.52 C1, 210.8A6
  
 5)NOTE: PLEASE SEE ONE OF THE ABOVE
 CIRCUITS FOR SD'S (#38) IS THE SAME
 CIRCUIT ON PANEL SCHEDULE FOR SUB PANEL
 "B".
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
 215.5
  
 7)NOTE: PLEASE SHOW LOADS ON EACH
 ELECTRICAL PANEL. PANEL "B AND "C
 MENTIONS TO SEE LOAD CALCS, HOWEVER
 THESE PANELS NEED TO SHOW ACTUAL LOAD
 FOR THOSE PANELS.
 220,215.5
  
 8 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 9)NOTE: PLEASE SEE PLANS REFERENCE 1999
 NEC FOR 210.12. WE HAVE BEEN UNDER THE
 2002 NEC SINCE JULY 1ST, 2003
  
 PLEASE BE SURE TO REMOVE ALL OLD VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 PLEASE SEE ONE COPY/SET OF OLD SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-07 Cont ID  
Sent By adarroug Date 2006-02-07 Time 12:43 Rev Time 0.00
Received By adarroug Date 2006-02-07 Time 12:43 Sent To B
Notes
2006-02-07 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 13:09 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 13:09 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 09:05 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 09:05 Sent To B
Notes
2005-10-19 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 16:24 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 16:24 Sent To B
Notes
2005-07-29 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-02 Cont ID  
Sent By adarroug Date 2005-06-02 Time 17:37 Rev Time 0.00
Received By adarroug Date 2005-06-02 Time 17:37 Sent To E
Notes
2005-06-02 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 09:18 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 09:18 Sent To E
Notes
2005-04-26 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-15 Cont ID  
Sent By mmclean Date 2005-05-13 Time 17:45 Rev Time 0.00
Received By jgomez Date 2005-04-15 Time 14:35 Sent To Z
Notes
2005-04-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-05-02 Cont ID  
Sent By prafter Date 2005-05-02 Time 09:56 Rev Time 0.50
Received By prafter Date 2005-05-02 Time 10:18 Sent To B
Notes
2005-05-02 00:00:00MECH. PLAN REVIEW:
  
 PROVISO:
 AHU 2 REQUIRES AUX. DRAIN PAN UNDER
 UNIT WITH DRAIN PROTECTION.
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By kstevens Date 2005-06-20 Time 17:50 Rev Time 0.85
Received By kstevens Date 2005-06-20 Time 17:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-14 Cont ID  
Sent By jleech Date 2005-05-14 Time 06:47 Rev Time 0.50
Received By jleech Date 2005-05-14 Time 06:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-25 Cont ID  
Sent By mmclean Date 2005-04-25 Time 18:49 Rev Time 0.00
Received By mmclean Date 2005-04-25 Time 18:49 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy