Plan Review Details - Permit 05040646
Plan Review Stops For Permit 05040646
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-05-17 Cont ID  
Sent By dpalmer Date 2005-05-17 Time 11:56 Rev Time 0.25
Received By dpalmer Date 2005-05-17 Time 11:56 Sent To  
Notes
2005-05-17 00:00:00FIRE PUMP/ELEC UNDER 04110346 OK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-21 Cont ID  
Sent By dpalmer Date 2005-04-21 Time 17:47 Rev Time 0.30
Received By dpalmer Date 2005-04-21 Time 17:47 Sent To  
Notes
2005-04-21 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE VALUATION FOR
 COMPLETE SCOPE OF WORK IS TO INCLUDE ALL
 LABOR AND MATERIALS; EVEN IF
 EQUIPMENT(IE: PUMPS, CONTROLLERS ETC)
 ARE OWNER SUPPLIED.
 FBC 104.6.5 AND LOCAL ADMINISTRATIVE
 CODE.
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION IS
 FOR MAIN FIRE PUMP ONLY, HOWEVER PLANS
 AND SPECS ALSO MENTIONS JOCKEY PUMPS
 ETC.
 PLEASE SEE JOCKEY PUMP APPEARS TO BE
 ELECTRICAL , HOWEVER NO ELECTRICAL PLANS
 FOR NEW OR EXISTING FEEDS WERE
 SUBMITTED.
 WIRING DIAGRAM ON LAST PAGE DOES NOT
 HAVE ENOUGH INFORMATION.
 215.5
  
 3)NOTE: PLEASE SEE FIRE REVIEW AND
 MECHANICAL COMMENTS FOR FUEL TANK SPECS.
 THESE COULD NOT BE LOCATED IN SPECS.
  
 4)NOTE: PLEASE SEEFBC 104.2.1 WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF PERSON RESPONSIBLE FOR PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-05-05 Cont ID  
Sent By mwennerg Date 2005-05-05 Time 09:46 Rev Time 0.00
Received By mwennerg Date 2005-05-05 Time 09:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-18 Cont ID  
Sent By mwennerg Date 2005-05-18 Time 09:03 Rev Time 0.00
Received By mwennerg Date 2005-05-18 Time 09:03 Sent To  
Notes
2005-05-18 00:00:001) NFPA 704 MARKINGS WILL BE PROVIDED BY
 THE CONTRACTOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-05 Cont ID  
Sent By mwennerg Date 2005-05-05 Time 09:35 Rev Time 0.00
Received By mwennerg Date 2005-05-05 Time 09:35 Sent To  
Notes
2005-05-05 00:00:001) PLEASE SUBMIT SPECS AND DETAILS
 REGARDING THE FUEL TANK SUCH AS SIZE,
 LOCATION, VENT PIPE ETC.
  
 2) NFPA 704 MARKINGS ARE REQUIRED ON OR
 IN THE VICINITY OF THE FUEL TANK.
  
 3) IF MECHANICAL DAMAGE IS LIKELY,
 PROTECTION OF THE FUEL TANK WILL BE
 NECESSARY.
  
 4) PLEASE PROVIDE FACTORY TEST CURVE
 RESULTS FOR REVIEW.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 09:44 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 09:44 Sent To  
Notes
2005-04-14 00:00:00TO "COMM" BD#57

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-18 Cont ID  
Sent By lmartine Date 2005-05-18 Time 15:24 Rev Time 0.00
Received By lmartine Date 2005-05-18 Time 15:24 Sent To  
Notes
2005-05-18 00:00:00PASSED PER HAROLD MOSER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By hmoser Date 2005-05-03 Time   Rev Time 0.00
Received By hmoser Date 2005-05-03 Time 17:40 Sent To  
Notes
2005-05-03 00:00:00PLAN DENIED
 1) PLEASE INDICATE THE LOCATION OF THE
 FUEL TANK,AND FUEL LINES
 2) PLEASE SUBMIT SPECS ON FUEL TANK
 PLAN REVIEW BY HAROLD MOSER 561-805-6732