Plan Review Details - Permit 05040646
Plan Review Stops For Permit 05040646 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2005-05-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-05-17 |
Time |
11:56 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-05-17 |
Time |
11:56 |
Sent To |
|
|
Notes |
2005-05-17 00:00:00 | FIRE PUMP/ELEC UNDER 04110346 OK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-04-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-04-21 |
Time |
17:47 |
Rev Time |
0.30 |
Received By |
dpalmer |
Date |
2005-04-21 |
Time |
17:47 |
Sent To |
|
|
Notes |
2005-04-21 00:00:00 | ********** UNSAT *********** | | | | 1)NOTE: PLEASE SEE VALUATION FOR | | COMPLETE SCOPE OF WORK IS TO INCLUDE ALL | | LABOR AND MATERIALS; EVEN IF | | EQUIPMENT(IE: PUMPS, CONTROLLERS ETC) | | ARE OWNER SUPPLIED. | | FBC 104.6.5 AND LOCAL ADMINISTRATIVE | | CODE. | | | | 2)NOTE: PLEASE SEE PERMIT APPLICATION IS | | FOR MAIN FIRE PUMP ONLY, HOWEVER PLANS | | AND SPECS ALSO MENTIONS JOCKEY PUMPS | | ETC. | | PLEASE SEE JOCKEY PUMP APPEARS TO BE | | ELECTRICAL , HOWEVER NO ELECTRICAL PLANS | | FOR NEW OR EXISTING FEEDS WERE | | SUBMITTED. | | WIRING DIAGRAM ON LAST PAGE DOES NOT | | HAVE ENOUGH INFORMATION. | | 215.5 | | | | 3)NOTE: PLEASE SEE FIRE REVIEW AND | | MECHANICAL COMMENTS FOR FUEL TANK SPECS. | | THESE COULD NOT BE LOCATED IN SPECS. | | | | 4)NOTE: PLEASE SEEFBC 104.2.1 WHICH | | REQUIRES THE PRINTED NAME AND SIGNATURE | | OF PERSON RESPONSIBLE FOR PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2005-05-05 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-05-05 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-05-05 |
Time |
09:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2005-05-18 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-05-18 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-05-18 |
Time |
09:03 |
Sent To |
|
|
Notes |
2005-05-18 00:00:00 | 1) NFPA 704 MARKINGS WILL BE PROVIDED BY | | THE CONTRACTOR. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2005-05-05 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-05-05 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-05-05 |
Time |
09:35 |
Sent To |
|
|
Notes |
2005-05-05 00:00:00 | 1) PLEASE SUBMIT SPECS AND DETAILS | | REGARDING THE FUEL TANK SUCH AS SIZE, | | LOCATION, VENT PIPE ETC. | | | | 2) NFPA 704 MARKINGS ARE REQUIRED ON OR | | IN THE VICINITY OF THE FUEL TANK. | | | | 3) IF MECHANICAL DAMAGE IS LIKELY, | | PROTECTION OF THE FUEL TANK WILL BE | | NECESSARY. | | | | 4) PLEASE PROVIDE FACTORY TEST CURVE | | RESULTS FOR REVIEW. | | | | | | MIKE WENNERGREN, A/CAPTAIN | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-04-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-04-14 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-04-14 |
Time |
09:44 |
Sent To |
|
|
Notes |
2005-04-14 00:00:00 | TO "COMM" BD#57 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2005-05-18 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2005-05-18 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2005-05-18 |
Time |
15:24 |
Sent To |
|
|
Notes |
2005-05-18 00:00:00 | PASSED PER HAROLD MOSER |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2005-05-03 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2005-05-03 |
Time |
|
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-05-03 |
Time |
17:40 |
Sent To |
|
|
Notes |
2005-05-03 00:00:00 | PLAN DENIED | | 1) PLEASE INDICATE THE LOCATION OF THE | | FUEL TANK,AND FUEL LINES | | 2) PLEASE SUBMIT SPECS ON FUEL TANK | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
|