Plan Review Details - Permit 05040434
Plan Review Stops For Permit 05040434
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-07 Cont ID  
Sent By jgomez Date 2005-07-07 Time 13:58 Rev Time 3.00
Received By jgomez Date 2005-07-07 Time 12:24 Sent To Z
Notes
2005-07-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SHEET T1: A) UPDATE GENERAL NOTES.
 SEE COMMENTS ON PLANS.
  
 B) DESIGN PARAMETERS: WHY MIN. SOIL
 BEARING PRESSURE IS : NA?.
  
 3- PROVIDE COMPLETE SPECS FOR BBQ WHICH
 IS SPECIFICALLY DESIGNED FOR A PORCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 4- PROVIDE COMPLETE INFORMATION FOR
 SHUTTERS OR APPLY FOR SEPARATE PERMIT.
  
 5- SPECIFY SAFETY GLASS FOR WINDOWS AT
 HER AND HIS BATH. SEE PLANS AND SEC.
 2405.2.1(2)
  
 6- PROVIDE COMPLETE SPECS AND UL LISTING
 FOR PORCH FIREPLACE. SEC. 2806 FBC 2001.
  
 7- SHEET A3: A) TRUSS ANCHOR SCHEDULE:
 CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. REVISE AS REQUIRED. SEE
 CATALOGUE FOR PROPER MASONRY CONNECTOR.
  
 B) ALL CONNECTORS TO SPECIFY SIZE AND
 NUMBER OF NAILS AS SHOWN ON LATEST
 CATALOGUE WHICH WAS REVISED TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001. OTHERWISE
 PROVIDE TESTING AND ENGINEERING FOR SIZE
 AND NUMBER OF NAILS THAT DIFFER FROM
 THOSE ALREADY TESTED AND PUBLISHED BY
 MANUFACTURER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 C) CLARIFY WHY USING ONLY AN F CONNECTOR
 TO SUPPORT END OF GIRDER TRUSS ABOVE
 BEDROOM #3 ENTRY. SEE PLAN FOR COMMENTS.
 SPECIFY CALCULATED UPLIFT. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 8- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR:
 A) SLIDING GLASS DOORS. (CLARIFY IF
 USING IMPACT DOORS OR NOT).
  
 B) WINDOW MULLIONS REQUIRED FOR LARGE
 FIXED WINDOWS AT LIVING ROOM. CLEARLY
 SPECIFY SIZE AND ANCHORS TO BE USED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 ALSO, CLEARLY SPECIFY MULLION SIZE AND
 FASTENERS FOR OTHER MULLIONS.
  
 C) CASEMENT WINDOWS DADE COUNTY NOA THAT
 MATCHES ONE SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL.
 NOTE: ASSEMBLIESSUBMITTED ALSO NEED TO
 MATCH THOSE SHOWN ON PLANS.
  
 D) CASEMENT WINDOW WITH IMPACT GLASS AS
 SHOWN ON BREAKFAST AREA TO PROVIDE
 EMERGENCY EGRESS.
  
 9- OWES $360.70 FOR ADDITIONAL GUEST
 SUITE VALUATION AND RADON FEES.
  
 10- REVISE ENERGY CALCULATIONS TO
 INCLUDE GUEST SUITE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 18:43 Rev Time 0.30
Received By dpalmer Date 2005-08-04 Time 18:25 Sent To B
Notes
2005-08-04 00:00:00IN ELEC FOR REVIEW.
 NEW ELECTRICAL SHEETS SUBMITTED.
 NEW ELECTRICAL SHEETS IN ONE SET.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-08 Cont ID  
Sent By btrobaug Date 2005-06-08 Time 16:28 Rev Time 0.50
Received By btrobaug Date 2005-06-08 Time 14:30 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-04-13 Cont ID  
Sent By dpalmer Date 2005-04-13 Time 17:00 Rev Time 0.50
Received By dpalmer Date 2005-04-13 Time 17:00 Sent To M
Notes
2005-04-13 00:00:00** PROVISO **
  
 1)NOTE: PLEASE SEE POSSIBLE MISSING
 RECEPT FOR 2' OF WALL.
 210.52
  
 2)NOTE: PLEASE SEE PANEL "C" SHOWN ON
 RISER IS NOT SHOWN ON PLANS.
  
 PLEASE REVISE THE ABOVE ALONG WITH ANY
 OTHER CHANGES BEFORE ROUGH ELECTRICAL
 INSPECTION.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 16:21 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 16:21 Sent To M
Notes
2005-07-28 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-01 Cont ID  
Sent By adarroug Date 2005-06-01 Time 09:36 Rev Time 0.00
Received By adarroug Date 2005-06-01 Time 09:36 Sent To E
Notes
2005-06-06 00:00:00TO ELECTRICAL NEW SHEETS.
2005-06-01 00:00:00TO "SFR" "M"
 PLANS DID NOT FINISH 1ST SET OF REVIEWS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 15:59 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 15:59 Sent To E
Notes
2005-04-12 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-07 Cont ID  
Sent By jgomez Date 2005-07-07 Time 15:30 Rev Time 0.00
Received By jgomez Date 2005-04-07 Time 10:29 Sent To  
Notes
2005-04-07 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By prafter Date 2005-08-03 Time 08:08 Rev Time 0.50
Received By prafter Date 2005-08-03 Time 08:08 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-16 Cont ID  
Sent By hmoser Date 2005-06-16 Time 16:39 Rev Time 0.00
Received By hmoser Date 2005-06-16 Time 16:22 Sent To P
Notes
2005-06-16 00:00:00PASS PRIVISO
 PLEASE MARK DUCT SIZE ON DUCT IN ROOM
 MARKED ON PLAN FOR ROUGH INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-18 Cont ID  
Sent By jleech Date 2005-06-18 Time 07:48 Rev Time 0.33
Received By jleech Date 2005-06-18 Time 07:48 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 18:05 Rev Time 0.00
Received By mmclean Date 2005-07-11 Time 18:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-11 Cont ID  
Sent By mmclean Date 2005-04-11 Time 16:11 Rev Time 0.00
Received By mmclean Date 2005-04-11 Time 16:11 Sent To I
Notes
2005-04-11 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 WALL/GATE/FENCE/COLUMNS.