Plan Review Details - Permit 05040431
Plan Review Stops For Permit 05040431
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-07-27 Cont ID  
Sent By shill Date 2005-07-27 Time 14:50 Rev Time 2.00
Received By shill Date 2005-07-27 Time 14:50 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-07-27 Cont ID  
Sent By shill Date 2005-07-27 Time 10:20 Rev Time 0.00
Received By shill Date 2005-07-27 Time 10:20 Sent To PC
Notes
2005-07-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)CONTRACTOR TO PUT TOGETHER TWO
 COMPLETE PERMIT PACKAGES FOR ISSUANCE.
 OTHERWISE CODE COMPLIANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-20 Cont ID  
Sent By shill Date 2005-07-20 Time 10:42 Rev Time 0.50
Received By shill Date 2005-07-20 Time 10:42 Sent To PC
Notes
2005-07-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)ZONING APPROVAL REQUIRED BEFORE A
 PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 17:41 Rev Time 1.00
Received By shill Date 2005-06-10 Time 13:56 Sent To PC
Notes
2005-06-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)HAVE THE PERMIT SET OF PLANS
 STAMPED BY HISTORIC.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-06 Cont ID  
Sent By btrobaug Date 2005-06-02 Time 16:09 Rev Time 3.00
Received By shill Date 2005-05-06 Time 09:41 Sent To PC
Notes
2005-05-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.) A ROOF PERMIT NUMBER WAS NOT
 ASSIGNED.THIS TYPE OF ROOF IS NOT
 WITHIN THE SCOPE OF YOUR GC LICENSE,
 FS489.
  
 4.)SHOW LANDING DIMENSION FOR STAIRS.
  
 5.)PROVIDE A STRUCTURAL DETAIL FOR THE
 STAIRS.
  
 6.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 7.)SUBMIT THE FOLLOWING PRODUCT
 APPROVALS:
 FIXED GLASS WINDOW
 MULLION
  
 8.)CONNECTION DETAIL 5, A7, LUS210-3
 FASTENING CONFLICTS WITH CATALOG.CHECK
 ALL CONNECTORS.IF YOU SPECIFY
 FASTENING IN CONFLICT WITH
 MANUFACTURER?S SPECIFICATIONS A LOCAL
 PRODUCT APPROVAL IS REQUIRED FAC9B72.
  
 9.)PROVIDE DRAFTSTOP SCHEDULE, 2ND
 FLOOR FRAMING PLAN, FBC705.3.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-07-18 Cont ID  
Sent By btrobaug Date 2006-07-18 Time 06:22 Rev Time 0.50
Received By btrobaug Date 2006-07-18 Time 06:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-21 Cont ID  
Sent By btrobaug Date 2006-06-21 Time 12:12 Rev Time 0.50
Received By btrobaug Date 2006-06-21 Time 12:02 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-08 Cont ID  
Sent By btrobaug Date 2005-07-08 Time 12:15 Rev Time 0.50
Received By btrobaug Date 2005-07-08 Time 07:00 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-02 Cont ID  
Sent By btrobaug Date 2005-06-02 Time 16:02 Rev Time 0.50
Received By btrobaug Date 2005-06-02 Time 15:15 Sent To P
Notes
2005-06-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} COMMENTS FROM PRIOR REVIEW, NOTE #3.
 3/0CU BEING FED WITH A 300 AMP BREAKER
 (OCP) IS IN VIOLATION OF 310.15(B)(6).
  
 2} THE QUESTION FROM COMMENT #1 STILL
 REMAAINS, IS THE SERVICE EQUIPMENT A
 METER/MAIN, IF SO USE CORRECT DIAGRAM
 FOR SAME, REMOVE THE 2" CONDUIT SHOWN ON
 RISER. IF NOT THE FEEDERS WOULD HAVE TO
 BE 250MCM TO COMPLY WITH 310.15,
 TERMINATING IN A 300 AMP OCP. IF THERE
 ARE QUESTIONS REGARDING THIS ISSUE, CALL
 DEWEY OR MYSELF PRIOR TO REDRAWING AND
 RESUBMITTING.
  
 3} NOTE #6. CLEARANCE FOR DISCONNECTS AT
 THE CONDENSERS, COMPLY WITH 110.26.
  
 4} NOTE #12, SUBMIT AIC(FAULT CURRENT)
 RATINGS FOR THE EQUIPMENT PER 110.10.
  
 5} IF THE OBJECT IN THE KITCHEN THAT
 RESEMBLES A TABLE, IS IN FACT AN ISLAND
 , THE RECEPTACLE MUST BE GFI PER
 210.8(A)(6).
  
 PLEASE LABEL THE ROOMS ON THE ELECTRICAL
 PLAN PER 104.2.1.3 FBC, CWPB
 AMMENDMENTS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By dpalmer Date 2005-04-13 Time 18:05 Rev Time 0.50
Received By dpalmer Date 2005-04-13 Time 18:05 Sent To M
Notes
2005-04-13 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE CLARIFY RISER, IT APPEARS
 TO SHOW A METER/MAIN COMBO??
 PLEASE SEE RISER APPEARS TO SHOW A FEED
 GOING OUT OF THE TOP OF EQUIPMENT TO A
 SUB-PANEL?
 215.5
 PLEASE PROVIDE A PANEL SCHEDULE FOR
 EQUIPMENT OUTSIDE IF INDEED A PANEL.
  
 2)NOTE: PLEASE CLARIFY IF LOAD SHOWN FOR
 POOL HEATER IS THE LOAD ALREADY FIGURED
 AT 125% FOR CONTINUOUS LOADS.
 215.3,230.42 ETC.
  
 3)NOTE: PLEASE SEE RISER SHOWS A 300A
 MAIN WITH NO OCP SHOWN FOR SUB PANEL.
 300A MAIN ON 2/0'S??
 240.4,310.15B6
  
 4)NOTE: PLEASE SEE 250.66 FOR MIN
 GROUNDING ELECTRODE CONDUCTOR. #2 MIN
 310.15B6
  
 5)NOTE: PLEASE SEE 210.52D FOR MISSING
 BATH RECEPTS WITHIN 3' OF SINK.
  
 6)NOTE: PLEASE SEE MISSING A/C
 DISCONNECTS FOR AC/ CU'S AND AHU'S. PER
 440.11 AND CLEARENCE PER 110.26
  
 7)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 SEE ISLAND.
  
 8)NOTE: PLEASE SEE 210.8A2 FOR GARAGES.
  
 9)NOTE: PLEASE SEE PLANS ARE MISISNG ALL
 SERVICE EQUIPMENT?? UNABLE TO REVIEW
 LOCATIONS FOR CODE COMPLIANCE AT THIS
 TIME.215.
  
 10)NOTE:SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 :PLEASE SEE MISSING SD LEADING TO FLOOR
 ABOVE:
  
 11)NOTE: PLEASE SEE MISSING FOOTER STEEL
 FOR GROUNDING ELECTRODE REQUIRED. 250.50
  
 12)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWOM
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET/COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 11:40 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 11:40 Sent To P
Notes
2006-08-11 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-07-15 Cont ID  
Sent By adarroug Date 2006-07-15 Time 10:20 Rev Time 0.00
Received By adarroug Date 2006-07-15 Time 10:20 Sent To E
Notes
2006-07-15 00:00:00TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 11:03 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 10:57 Sent To E
Notes
2006-06-14 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 16:00 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 16:00 Sent To Z
Notes
2005-07-21 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 16:08 Sent To E
Notes
2005-07-01 00:00:00TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-22 Cont ID  
Sent By adarroug Date 2005-06-22 Time 11:28 Rev Time 0.00
Received By adarroug Date 2005-06-22 Time 11:28 Sent To Z
Notes
2005-06-22 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 09:01 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 09:01 Sent To E
Notes
2005-05-31 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 16:33 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 16:33 Sent To Z
Notes
2005-05-18 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 16:03 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 16:03 Sent To E
Notes
2005-04-12 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By shill Date 2005-05-06 Time 10:50 Rev Time 0.00
Received By shill Date 2005-04-07 Time 09:23 Sent To  
Notes
2005-04-07 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-04-19 Cont ID  
Sent By prafter Date 2005-04-19 Time 11:41 Rev Time 0.50
Received By prafter Date 2005-04-19 Time 11:41 Sent To P
Notes
2005-04-19 00:00:00MECH. PLAN REVIEW.
  
 A/C CONTRACTOR TO SUBMIT A/C PLANS AND
 EQUIPMENT INFORMATION AT A/C PERMIT
 TIME.
 PAT RAFTER 4/19/05 561/6728O OR
 805/6719 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-09-06 Cont ID  
Sent By jleech Date 2006-09-06 Time 10:15 Rev Time 0.00
Received By jleech Date 2006-09-06 Time 10:15 Sent To  
Notes
2006-09-06 00:00:00REVISION; REVISED SANITARY RISER DIAGRAM
 OK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-04 Cont ID  
Sent By jleech Date 2005-06-04 Time 14:45 Rev Time 0.33
Received By jleech Date 2005-06-04 Time 14:45 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-04-23 Cont ID  
Sent By pschmitz Date 2005-04-23 Time 07:11 Rev Time 0.00
Received By pschmitz Date 2005-04-23 Time 07:11 Sent To B
Notes
2005-04-23 00:00:00INSTALLATION OF FITTINGS FBC 2001
 SEC 706.3

Review Stop Z ZONING
Rev No 4 Status P Date 2005-07-26 Cont ID  
Sent By mmclean Date 2005-07-26 Time 15:09 Rev Time 0.00
Received By mmclean Date 2005-07-26 Time 15:09 Sent To B
Notes
2005-07-26 00:00:00GIVEN TO SAMANTHA HILL

Review Stop Z ZONING
Rev No 3 Status F Date 2005-06-30 Cont ID  
Sent By mmclean Date 2005-06-30 Time 14:56 Rev Time 0.00
Received By mmclean Date 2005-06-30 Time 14:56 Sent To I
Notes
2005-06-30 00:00:00DENIED,
 1. SURVEY & SITEPLAN DOES NOT MATCH.
 2. NEED TO HAVE SURVEY TO MATCH SITEPLAN
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-05-26 Cont ID  
Sent By mmclean Date 2005-05-26 Time 13:16 Rev Time 0.00
Received By mmclean Date 2005-05-26 Time 13:16 Sent To I
Notes
2005-05-26 00:00:00DENIED,
 1. DRIVEWAY HAS TOO MUCH PAVERS/CONCRETE
 WITHIN THE FIRST 25FT FRONT SETBACK.
 2. NEED TO REDUCE THE DRIVE FROM 16FT
 WIDE TO 10FT WIDE.
 **MUST HAVE 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK.**
 3. NEED TO PROVIDE TWO COPY OF SURVEY
 4. NEED TO PROVIDE THE REAR SETBACK FROM
 THE STRUCTURE TO PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-11 Cont ID  
Sent By mmclean Date 2005-04-11 Time 15:09 Rev Time 0.00
Received By mmclean Date 2005-04-11 Time 15:09 Sent To I
Notes
2005-04-11 00:00:00DENIED,
 1. NEED KNOW THE WIDTH OF THE DRIVEWAY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720