Plan Review Details - Permit 05040426
Plan Review Stops For Permit 05040426
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-02-07 Cont ID  
Sent By jgomez Date 2006-02-07 Time 18:08 Rev Time 0.40
Received By jgomez Date 2006-02-07 Time 18:08 Sent To  
Notes
2006-02-07 00:00:00ENERGY CALCULATIONS, BUILDING REVISIONS
 AND PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-12-08 Cont ID  
Sent By jgomez Date 2005-12-08 Time 09:35 Rev Time 0.50
Received By jgomez Date 2005-12-08 Time 09:34 Sent To PC
Notes
2005-12-08 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- ENERGY CALCS SUBMITTED ARE FBC 2004
 FORMS. NEED ENERGY CALCS WITH FBC 2001
 FORMS, SINCE PLANS WERE REVIEWED UNDER
 FBC 2001.
  
 2- MISSING REVISED SHEET A-5. IT WAS NOT
 SUBMITTED IN THIS PACKAGE.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ATRIUM DOOR AS REQUIRED BY
 RULE 9B-72. SEE PLANS FOR SPECIFICATIONS
 SIZE AND SWING DIRECTION OF DOOR.
  
 4- OWES $60.00 REVISION FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-01 Cont ID  
Sent By jgomez Date 2005-09-01 Time 10:17 Rev Time 0.75
Received By jgomez Date 2005-09-01 Time 10:17 Sent To PC
Notes
2005-09-01 00:00:00SUBMITTAL BUILDING REVIEW CHECKLIST:
 1- SEPARATE PERMIT FOR SHUTTERS HAS NOT
 BEEN APPLIED FOR YET.
  
 2- ENERGY CALCULATIONS WERE REVISED. NOW
 CEILING FAN CREDIT WAS TAKEN. THEREFORE,
 NEED TO REVISE ELECTRICAL PLAN SHOWING
 SIZE OF CEILING FANS, INCLUDING FANS IN
 THE GREAT ROOM AS REQUIRED BY TABLE 6-6
 OF CHAPTER 13 FBC 2001.
  
 3- ROOF FRAMING PLAN NEEDS TO BE REVISED
 AT ENTRY PORCH AREA TO MATCH FOUNDATION
 AND FLOOR PLAN. NOTICE THAT CONCRETE
 BEAM DOESN'T EXTEND ALL THE WAY INSIDE
 TO THE FOYER AREA. CONCRETE BEAM IS ONLY
 AT ENTRY PORCH AREA. REVISE ROOF FRAMING
 PLAN AS REQUIRED AND SPECIFY
 CORRESPONDING CONNECTORS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS SPECIFIED FOR CONNECTOR HUS26.
 SEE 2005 CATALOGUE.
  
 5- ONE HOUR FIRE RATED DOOR AT ATRIUM
 PRODUCT APPROVAL IS FOR OUTSWING DOOR.
 PLANS CALL FOR INSWING DOOR. REVISE AS
 REQUIRED.
  
 6- SPECIFY WINDOW MULLION AND ANCHORS
 FOR FIXED WINDOWS AT GREAT ROOM. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 7- PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLION SPECIFIED FOR GREAT ROOM FIXED
 WINDOWS.
  
 8- ALL REVISED DRAWINGS WILL BE SUBJECT
 TO THE REVISION FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-10 Cont ID  
Sent By jgomez Date 2005-06-10 Time 17:17 Rev Time 1.00
Received By jgomez Date 2005-06-10 Time 17:17 Sent To E
Notes
2005-06-10 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- REVISE ENERGY CALCULATIONS. NEED
 WORST CASE SCENARIO CALCS FOR THIS MODEL
 3- REVISE FRONT ELEVATION TO SHOW ENTRY
 DOORS AS SHOWN ON PRODUCT APPROVAL.
 4- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT ENTRY PORCH. NEED MASONRY
 CONNECTOR. SEE DETAIL 5/D-1.
 5- TRUSS ANCHOR SCHEDULE: REVISE TYPE OF
 NAIL USED FOR HUS26. SEE CATALOGUE.
 6- PROVIDE PRODUCT APPROVAL FOR ONE HOUR
 FIRE RATED ASSEMBLY AT EGRESS OPENING.
 7- PROVIDE PRODUCT APPROVAL FOR 12'-0"
 WIDE SLIDING GLASS DOORS.
 8- PROVIDE PRODUCT APPROVAL FOR 8'-0"
 HIGH ENTRY DOORS.
 9- PROVIDE CLEAR WINDOW & DOOR
 SCHEDULES. NEED MATCHING SYMBOLS.
 10- PROVIDE COPY OF EGRESS EASEMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-06 Cont ID  
Sent By jgomez Date 2005-05-06 Time 18:50 Rev Time 2.50
Received By jgomez Date 2005-05-06 Time 18:50 Sent To PC
Notes
2005-05-06 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SOIL TEST REPORT RECOMMENDS 18" MIN.
 WIDTH FOR FOOTING. FOUNDATION PLAN CALLS
 FOR 16". REVISE AS REQUIRED.
  
 3- 45 DEGREE WINDOW ON BEDROOM #3 AT
 ZERO LOT LINE WALL IS NOT ALLOWED BY
 TABLE 600 FBC 2001. NO OPENINGS ALLOWED.
  
 4- PROVIDE NOTE ON DEN ROOM STATING THAT
 ROOM IS NOT ALLOWED TO BE USED FOR
 SLEEPING PURPOSES. OTHERWISE, NEED TO
 COMPLY WITH EGRESS REQUIREMENTS OF
 SECTION 1005.4 FBC 2001.
  
 5- NEED RECORDED EGRESS EASEMENT WHEN
 USING THE ZERO LOT SIDE FOR EGRESS. SEE
 ATTACHED REQUIREMENTS AND SAMPLE.
  
 6- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES.
 SPECIFY FASTENERS TYPE AND SPACING. SEE
 ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
  
 7- SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE EXCEPTION IN SEC.
 1909.3 FOR LOCATION OF WWM AND REVISE
 NOTE ON FOUNDATION NOTE AS REQUIRED.
  
 8- SPECIFY FOOTINGS FOR ENTRY COLUMNS.
 SEC. 104.2.1.2 CITY AMENDEMNTS TO FBC.
  
 9- SHEET A-5.0: A) ROOF NAILING ZONE
 DIAPHRAGM IS MISSING ZONE #3. SEE FIGURE
 1606.2(C) FBC 2001..
  
 B) DETAIL 3 SPECIFIES HGUS 28-2 SIMPSON
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
  
 C) DETAIL 1 AND 2: REVISE TYPE OF NAILS.
 SEE SIMPSON CATALOGUE.
  
 10- REVISE/UPDATE TRUSS ANCHOR SCHEDULE
 TO MATCH LATEST MANUFACTURER CATALOGUE
 THAT WAS REVISED TO COMPLY WITH SECTION
 1609.4.3 FBC 2001. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER.
  
 11- RIGHT SIDE ELEVATION DOESN'T MATCH
 PLANS. BATHROOM #2 NEED TO SHOW GLASS
 BLOCK.
 ALSO, SHOW GLASS BLOCK ON LEFT SIDE
 ELEVATION.
  
 12- CLARIFY IF USING DOORS AND WINDOWS
 WITH IMPACT GLASS OR IF STORM SHUTTERS
 ARE GOING TO BE USED. THEN, PROVIDE
 COMPLETE INFORMATION FOR EITHER METHOD.
  
 13- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR:A) 1 HOUR FIRE RATED
 ASSEMBLY AT EMERGENCY EGRESS OPENING.
  
 B) SLIDING GLASS DOORS: DRAWINGS
 SUBMITTED DON'T CORRESPOND TO DADE
 COUNTY NOA. NEED DRAWING NO 4340.
  
 C) PROVIDE PRODUCT APPROVAL FOR 12'-0"
 WIDE SLIDING GLASS DOORS. SEE PLANS.
  
 D) SIMPSON TRUSS CONNECTORS SPECIFIED ON
 PLANS. SOME PRODUCT APPROVALS SUBMITED
 ARE FOR CONNECTORS NOT SPECIFIED ON
 PLANS.
  
 14- SHEET D-1: A) CONNECTORS CS-16 X,
 HTS-20 SHOWN ON DETAILS 3, 4 AND 5 ARE
 WOOD TO WOOD CONNECTORS. NEED TO SPECIFY
 CONNECTORS THAT ARE DESIGNED FOR MASONRY
 APPLICATIONS. SEE SIMPSON CATALOGUE FOR
 PROPER CONNECTOR SPECS AND PROPER TYPE
 AND NUMBER OF FASTENERS. REVISE AS REQ'D
  
  
 B) REVISE TYPE AND NUMBER OF NAILS
 SPECIFIED ON DETAIL #4 FOR CONNECTOR
 HUS26. SEE SIMPSON CATALOGUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-17 Cont ID  
Sent By dpalmer Date 2006-01-17 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2006-01-17 Time 10:47 Sent To PC
Notes
2006-01-17 00:00:00REDLINED 210.11C3, SHOWS A-38 AS MASTER
 BEDRM, YET THIS IS SHOWN ON PLANS AS
 BATHRM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 15:31 Rev Time 0.33
Received By dpalmer Date 2005-06-13 Time 15:31 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By dpalmer Date 2005-04-13 Time 17:23 Rev Time 0.50
Received By dpalmer Date 2005-04-13 Time 17:23 Sent To M
Notes
2005-04-13 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PANEL "A" SHOWS FEED
 TO PANEL "B" AS 100A OCP ON #6 AWG.
 PLEASE SEE 240.4,310.16 AND PLEASE
 CORRELATE WITH RISER DIAGRAM.
 PLEASE ALSO SEE THIS IS SHOWN AS 100A SP
 BRKR ON ONE PHASE? (MISPRINT)
  
 2)NOTE: PLEASE SEE PANEL "B" SHOWS SUB
 PANEL "C" IN TWO DIFFERENT LOCATIONS?
 PLEASE SEE THIS IS SHOWN ON SAME PHASE.
 PLEASE ALSO CORRELATE AWG FOR 60A OCP.
 SHOWS #6 AND #8?
 PLEASE ALSO SEE SINGLE POLE 60A FOR
 ADDITIONAL SUB PANEL.
 PLEASE SEE 240.4,310.16, 310.15B6
  
 3)NOTE: PLEASE SEE NOTE ADDED TO CENTER
 OF PLANS WHICH IS A PROVISO SET UP BY A
 PLAN REVIEWER FOR A PREVIOUS PROJECT.
 THIS COMMENT FROM OTHER ELECTRICAL PLAN
 REVIEW SHOULD NOT BE LOCATED ON THESE
 PLANS.
 PLEASE REMOVE.
  
 4)NOTE: PLEASE SEE SD'S ARE REQUIRED TO
 BE WIRED "INLINE" ON THE SAME CIRCUIT,
 HOWEVER PLANS INDICATE TWO SEPARATE
 CIRCUITS FOR THE SD'S.THESE MAY NOT BE
 ON THE SAME CIRCUIT.
 NFPA-72 8-1.4.1.6.2
  
 5)NOTE: PLEASE SEE ONE OF THE ABOVE
 CIRCUITS FOR SD'S (#38) IS THE SAME
 CIRCUIT ON PANEL SCHEDULE FOR SUB PANEL
 "B".
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
 215.5
  
 7)NOTE: PLEASE SHOW LOADS ON EACH
 ELECTRICAL PANEL. PANEL "B AND "C
 MENTIONS TO SEE LOAD CALCS, HOWEVER
 THESE PANELS NEED TO SHOW ACTUAL LOAD
 FOR THOSE PANELS.
 220,215.5
  
 8 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 9)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS SHOWN ON ON PANEL SCHEDULE,
 HOWEVER THIS IS NOT SHOWN ON PLANS AT
 WHAT APPEARS TO BE THE WP/JACUZZI TUB.
  
 PLEASE BE SURE TO REMOVE ALL OLD VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 PLEASE SEE ONE COPY/SET OF OLD SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 15:45 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 15:45 Sent To B
Notes
2006-02-03 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-01-06 Cont ID  
Sent By adarroug Date 2006-01-06 Time 09:49 Rev Time 0.00
Received By adarroug Date 2006-01-06 Time 09:49 Sent To E
Notes
2006-01-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 08:59 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 08:59 Sent To B
Notes
2005-10-19 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 16:23 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 16:23 Sent To B
Notes
2005-07-29 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-07 Cont ID  
Sent By mjacobs Date 2005-06-07 Time 09:38 Rev Time 0.00
Received By mjacobs Date 2005-06-07 Time 09:38 Sent To B
Notes
2005-06-07 00:00:00TO 'JGOMEZ' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-02 Cont ID  
Sent By adarroug Date 2005-06-02 Time 18:06 Rev Time 0.00
Received By adarroug Date 2005-06-02 Time 18:06 Sent To E
Notes
2005-06-02 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 15:58 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 15:58 Sent To E
Notes
2005-04-12 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-06 Cont ID  
Sent By jgomez Date 2005-05-06 Time 18:58 Rev Time 0.00
Received By jgomez Date 2005-04-07 Time 10:55 Sent To  
Notes
2005-04-07 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-04-18 Time   Rev Time 0.00
Received By hmoser Date 2005-04-18 Time 08:44 Sent To P
Notes
2005-04-18 00:00:00PASS PRIVISO
 #1 REFER TO SECTION 610.1 ABC.3.5.2
 FIORIDA ENERGY CODE #1 ACCESS TO
 EQUIPMENT.AND NOTICE TO HOMEOWNER.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-20 Cont ID  
Sent By kstevens Date 2005-06-20 Time 16:27 Rev Time 0.75
Received By kstevens Date 2005-06-20 Time 16:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-04-21 Cont ID  
Sent By kstevens Date 2005-04-21 Time 18:49 Rev Time 0.33
Received By kstevens Date 2005-04-21 Time 18:45 Sent To B
Notes
2005-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A1.0 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. SECTIONS
 905.3 & 905.4 DRY HORIZONTAL VENTS ARE
 NOT APPROVED. THE VENT DOWNSTREAM OF THE
 MASTER BATH SHOWER IS NOT REQUIRED AND
 SHOULD BE DELETED AS IT DOES NOT MEET
 CODE.
 2) CLEANOUT AT WASH MACHINE SHALL BE 4'
 ABOVE THE FLOOR FOR ACCESS. SECTION
 708.10.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-11 Cont ID  
Sent By mmclean Date 2005-04-11 Time 16:15 Rev Time 0.00
Received By mmclean Date 2005-04-11 Time 16:15 Sent To I
Notes
2005-04-11 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 GATE/WALL/FENCE