Plan Review Stops For Permit 05040385 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2005-07-15 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-07-15 |
Time |
09:00 |
Rev Time |
0.75 |
Received By |
alange |
Date |
2005-07-15 |
Time |
09:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2005-07-12 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-07-12 |
Time |
09:40 |
Rev Time |
0.50 |
Received By |
alange |
Date |
2005-07-12 |
Time |
09:39 |
Sent To |
|
|
Notes |
2005-07-12 00:00:00 | DENIED | | | | THIRD REVIEW: | | | | OVERHEAD DOOR PRODUCT APPROVAL IS FOR A | | 16FT WIDE DOOR.DOORS ON PLANS ARE | | BETWEEN 9 - 10 FT WIDE. | | SUBMIT THE CORRECT PRODUCT APPROVAL FOR | | THE OVERHEAD DOORS. | | | | FLEMING DOOR STATE APPROVAL PAGE | | SUBMITTED IS NOT THE CORRECT PAGE. | | CLICK ON THE APPROPRIATE SERIES DOOR. | | SEE NOTE ON PAGE SUBMITTED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-06-20 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-06-20 |
Time |
15:40 |
Rev Time |
0.50 |
Received By |
alange |
Date |
2005-06-20 |
Time |
15:39 |
Sent To |
|
|
Notes |
2005-06-20 00:00:00 | DENIED | | | | SECOND REVIEW: | | | | 2.SUBMIT 2 COPIES OF PRODUCT APPROVALS | | FOR OVERHEAD DOOR, EXTERIOR | | DOOR,WINDOWS,IMPACT PROTECTION, ROOFING | | AND STRAPS AND TIE-DOWNS. | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | ANY QUESTIONS CALL ME. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-05-03 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-20 |
Time |
10:57 |
Rev Time |
1.25 |
Received By |
alange |
Date |
2005-05-03 |
Time |
11:41 |
Sent To |
P |
|
Notes |
2005-05-03 00:00:00 | DENIED | | | | 1.PLANS MUST BE SIGNED AND SEALED PER | | FS 481. | | | | 2.SUBMIT 2 COPIES OF PRODUCT APPROVALS | | FOR OVERHEAD DOOR, EXTERIOR | | DOOR,WINDOWS,IMPACT PTOTECTION, ROOFING | | AND STRAPS AND TIE-DOWNS. | | PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | ANY QUESTIONS CALL ME. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-07-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-07-05 |
Time |
17:01 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-07-05 |
Time |
15:29 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-06-20 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-20 |
Time |
10:49 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-06-20 |
Time |
08:32 |
Sent To |
B |
|
Notes |
2005-06-20 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT SPECIFICATIONS FOR THE | | TRANSFER SWITCH. SEE PREVIOUS REVIEW. | | | | 2} THE SERVICE INDICATES IT IS EXISTING. | | ON THE PREVIOUS PLAN IT WAS NEW. PLEASE | | CLARIFY | | | | 3} GIVE THE RATING OF THE SERVICE | | EQUIPMENT. AMPERAGE AND VOLTAGE. IF THIS | | IS A 300 AMP SERVICE, THE GEC MUST BE #2 | | PER 250.66. | | | | 4} SHOW THE LOCATION OF THE SERVICE | | EQUIPMENT ON THE PLAN. THE GENERATOR | | DISCONNECT IS NOT SHOWN. | | | | 5} THERE ARE TWO METERS SHOWN ON THE | | PLAN, ONLY ONE ON THE RISER. PLEASE | | CLARIFY.IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-05-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-05-02 |
Time |
10:38 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-05-02 |
Time |
09:21 |
Sent To |
B |
|
Notes |
2005-05-02 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PROVIDE SPECS FOR THE GENERATOR, ATS | | AND ALL RELATED EQUIPMENT. | | | | 2} PROVIDE A SCHEMATIC INDICATING | | COMPLIANCE WITH ARTICLES 445,700.6 AND | | 702 NEC. | | | | 3} PLEASE INDICATE THE LOAD CALCULATION | | FOR THE CIRCUITS BEING FED FROM THE | | EMERGENCY PANEL. NOTE: CANNOT FEED 300 | | AMP SERVICE FROM A 10K GENERATOR. SEE | | 700.5. | | | | 4} INDICATE THE PRIME MOVER FOR THE | | GENERATOR. | | | | 5} PLEASE PROVIDE A CALCULATION | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | EXISTING LOADS AND THE EXISTING OR | | PROPOSED SERVICE SPECIFICATIONS PER | | 215.15. | | | | 6} THE PLANS MUST BE SIGNED AND SEALED | | PER 481 FS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-06-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-06-28 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-06-28 |
Time |
16:59 |
Sent To |
E |
|
Notes |
2005-06-28 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-06-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-07 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-07 |
Time |
15:49 |
Sent To |
E |
|
Notes |
2005-06-07 00:00:00 | TO BT DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-04-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-04-18 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-04-18 |
Time |
16:41 |
Sent To |
B |
|
Notes |
2005-04-18 00:00:00 | TO "MISC" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-06-20 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-04-18 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2005-04-06 |
Time |
16:01 |
Sent To |
|
|
Notes |
2005-04-06 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2005-05-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-05-04 |
Time |
11:33 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2005-05-04 |
Time |
11:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2005-04-18 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-04-18 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-04-11 |
Time |
16:41 |
Sent To |
I |
|
Notes |
2005-04-18 00:00:00 | OK, PROVIDING THAT THEY MEET THE SETBACK | | FOR REAR. | 2005-04-11 00:00:00 | VERIFY THE ATTACHED PORCH TO THE FREE | | STANDING GARAGE.WILL REVIEW WITH A | | PLANNER |
|
|