Plan Review Details - Permit 05040385
Plan Review Stops For Permit 05040385
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-15 Cont ID  
Sent By alange Date 2005-07-15 Time 09:00 Rev Time 0.75
Received By alange Date 2005-07-15 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-12 Cont ID  
Sent By alange Date 2005-07-12 Time 09:40 Rev Time 0.50
Received By alange Date 2005-07-12 Time 09:39 Sent To  
Notes
2005-07-12 00:00:00DENIED
  
 THIRD REVIEW:
  
 OVERHEAD DOOR PRODUCT APPROVAL IS FOR A
 16FT WIDE DOOR.DOORS ON PLANS ARE
 BETWEEN 9 - 10 FT WIDE.
 SUBMIT THE CORRECT PRODUCT APPROVAL FOR
 THE OVERHEAD DOORS.
  
 FLEMING DOOR STATE APPROVAL PAGE
 SUBMITTED IS NOT THE CORRECT PAGE.
 CLICK ON THE APPROPRIATE SERIES DOOR.
 SEE NOTE ON PAGE SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By alange Date 2005-06-20 Time 15:40 Rev Time 0.50
Received By alange Date 2005-06-20 Time 15:39 Sent To  
Notes
2005-06-20 00:00:00DENIED
  
 SECOND REVIEW:
  
 2.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR OVERHEAD DOOR, EXTERIOR
 DOOR,WINDOWS,IMPACT PROTECTION, ROOFING
 AND STRAPS AND TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-03 Cont ID  
Sent By btrobaug Date 2005-06-20 Time 10:57 Rev Time 1.25
Received By alange Date 2005-05-03 Time 11:41 Sent To P
Notes
2005-05-03 00:00:00DENIED
  
 1.PLANS MUST BE SIGNED AND SEALED PER
 FS 481.
  
 2.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR OVERHEAD DOOR, EXTERIOR
 DOOR,WINDOWS,IMPACT PTOTECTION, ROOFING
 AND STRAPS AND TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-05 Cont ID  
Sent By btrobaug Date 2005-07-05 Time 17:01 Rev Time 0.50
Received By btrobaug Date 2005-07-05 Time 15:29 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By btrobaug Date 2005-06-20 Time 10:49 Rev Time 0.50
Received By btrobaug Date 2005-06-20 Time 08:32 Sent To B
Notes
2005-06-20 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT SPECIFICATIONS FOR THE
 TRANSFER SWITCH. SEE PREVIOUS REVIEW.
  
 2} THE SERVICE INDICATES IT IS EXISTING.
 ON THE PREVIOUS PLAN IT WAS NEW. PLEASE
 CLARIFY
  
 3} GIVE THE RATING OF THE SERVICE
 EQUIPMENT. AMPERAGE AND VOLTAGE. IF THIS
 IS A 300 AMP SERVICE, THE GEC MUST BE #2
 PER 250.66.
  
 4} SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON THE PLAN. THE GENERATOR
 DISCONNECT IS NOT SHOWN.
  
 5} THERE ARE TWO METERS SHOWN ON THE
 PLAN, ONLY ONE ON THE RISER. PLEASE
 CLARIFY.IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-02 Cont ID  
Sent By btrobaug Date 2005-05-02 Time 10:38 Rev Time 0.50
Received By btrobaug Date 2005-05-02 Time 09:21 Sent To B
Notes
2005-05-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE SPECS FOR THE GENERATOR, ATS
 AND ALL RELATED EQUIPMENT.
  
 2} PROVIDE A SCHEMATIC INDICATING
 COMPLIANCE WITH ARTICLES 445,700.6 AND
 702 NEC.
  
 3} PLEASE INDICATE THE LOAD CALCULATION
 FOR THE CIRCUITS BEING FED FROM THE
 EMERGENCY PANEL. NOTE: CANNOT FEED 300
 AMP SERVICE FROM A 10K GENERATOR. SEE
 700.5.
  
 4} INDICATE THE PRIME MOVER FOR THE
 GENERATOR.
  
 5} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 6} THE PLANS MUST BE SIGNED AND SEALED
 PER 481 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 16:59 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 16:59 Sent To E
Notes
2005-06-28 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-07 Cont ID  
Sent By shill Date 2005-06-07 Time 15:49 Rev Time 0.00
Received By shill Date 2005-06-07 Time 15:49 Sent To E
Notes
2005-06-07 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 16:41 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 16:41 Sent To B
Notes
2005-04-18 00:00:00TO "MISC" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-20 Cont ID  
Sent By alange Date 2005-04-18 Time 15:40 Rev Time 0.00
Received By alange Date 2005-04-06 Time 16:01 Sent To  
Notes
2005-04-06 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-04 Cont ID  
Sent By jleech Date 2005-05-04 Time 11:33 Rev Time 0.25
Received By jleech Date 2005-05-04 Time 11:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-04-18 Cont ID  
Sent By mmclean Date 2005-04-18 Time 11:27 Rev Time 0.00
Received By mmclean Date 2005-04-11 Time 16:41 Sent To I
Notes
2005-04-18 00:00:00OK, PROVIDING THAT THEY MEET THE SETBACK
 FOR REAR.
2005-04-11 00:00:00VERIFY THE ATTACHED PORCH TO THE FREE
 STANDING GARAGE.WILL REVIEW WITH A
 PLANNER