Plan Review Details - Permit 05040155
Plan Review Stops For Permit 05040155
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-05-23 Cont ID  
Sent By lsmith Date 2005-05-23 Time 16:36 Rev Time 0.75
Received By lsmith Date 2005-05-23 Time 16:36 Sent To  
Notes
2005-05-23 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 VALUE OF POOL UNDERSTATED. ADJUSTED PER
 MARESHALL SWIFT COST GUIDE.
  
 SHORING REQUIRED BETWEEN HOUSE & POOL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-11 Cont ID  
Sent By btrobaug Date 2005-07-11 Time 14:08 Rev Time 0.33
Received By btrobaug Date 2005-07-11 Time 13:50 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-16 Cont ID  
Sent By btrobaug Date 2005-05-16 Time 16:30 Rev Time 0.33
Received By btrobaug Date 2005-05-16 Time 14:45 Sent To P
Notes
2005-05-16 00:00:00 
 PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 10:48 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 10:48 Sent To E
Notes
2005-07-11 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 16:19 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 16:19 Sent To E
Notes
2005-05-13 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 17:57 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 17:57 Sent To Z
Notes
2005-05-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-04 Cont ID  
Sent By adarroug Date 2005-04-04 Time 12:54 Rev Time 0.00
Received By adarroug Date 2005-04-04 Time 12:54 Sent To Z
Notes
2005-04-04 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-01 Cont ID  
Sent By jleech Date 2005-08-01 Time 08:27 Rev Time 0.50
Received By jleech Date 2005-08-01 Time 08:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-23 Cont ID  
Sent By kstevens Date 2005-05-23 Time 09:24 Rev Time 0.50
Received By kstevens Date 2005-05-23 Time 09:24 Sent To B1
Notes
2005-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) SHEET ATTACHED TO PLANS FOR HEAT PUMP
 TIE DOWN DETAIL NOT APPROVED. CODE CALLS
 FOR A NOMINAL 4" SUBSTANTIAL SLAB FOR
 MECHANICAL EQUIPMENT. DETAIL INDICATES
 THAT THE SLAB IS 3" PLEASE CORRECT THE
 DETAIL OR DELETE FROM PLANS. SECTION
 1820.5.
 2) POOL LAY OUT SHEET SHOWS 3 RETURNS TO
 THE POOL, BUT POOL SPECIFICATIONS
 INDICATE 8 RETURNS AS WELL AS THE RETURN
 DETAIL. PLEASE CORRELATE POOL LAYOUT
 WITH SPECIFICATIONS & RETURN DETAIL.
 3) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 4) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUF. CUT SHEETS - SUBMITTAL)
 5) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE WATER
 HEATER. (ADD TO NOTES).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-08-01 Time 16:40 Rev Time 0.00
Received By mmclean Date 2005-08-01 Time 16:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-05-12 Cont ID  
Sent By mmclean Date 2005-05-12 Time 14:29 Rev Time 0.00
Received By mmclean Date 2005-05-12 Time 14:29 Sent To I
Notes
2005-05-12 00:00:00DENIED,
 1. NEED TO SHOW THE SIDE SETBACK OF THE
 POOL & DECK ON TWO COPY OF SURVEY
 2. POOL MUST BE 5FT ON THE ZERO SIDE AND
 DECK MUST BE 2FT ON THE ZERO SIDE.
 3. MUST PROVIDE TWO NEW COPY OF SURVEY
 SHOWING THE ABOVE SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-06 Cont ID  
Sent By mmclean Date 2005-04-06 Time 16:45 Rev Time 0.00
Received By mmclean Date 2005-04-06 Time 16:45 Sent To  
Notes
2005-04-06 00:00:00DENIED.
 1. MUST PROVIDE THE SETBACK FOR THE POOL
 & DECK.(POOL - WATERS EDGE TO PROPERTY
 LINE) AND DECK TO PROPERTY LINE.) THE
 MUST BE ON 2 COPY OF SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN