Plan Review Details - Permit 05031898
Plan Review Stops For Permit 05031898
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-04-27 Cont ID  
Sent By mwennerg Date 2005-04-27 Time 13:23 Rev Time 0.00
Received By mwennerg Date 2005-04-27 Time 13:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 08:26 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 08:26 Sent To M
Notes
2005-04-01 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-27 Cont ID  
Sent By pkrauss Date 2005-04-27 Time 13:07 Rev Time 0.40
Received By pkrauss Date 2005-04-27 Time 13:07 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-06 Cont ID  
Sent By pkrauss Date 2005-04-06 Time 06:40 Rev Time 0.20
Received By pkrauss Date 2005-04-06 Time 06:40 Sent To FIRE
Notes
2005-04-06 00:00:00PERMIT APPLICATIONWAS SUBMITTED
 WITHOUT PLANS.PLANS SUBMITTED WITH
 BUILDING PERMIT ARE NOT COMPLETE.
 PROVIDE THE FOLLOWING INFORMATION FOR
 REVIEW:
 - DISTANCE TO COMBUSTIBLES OR FIRE WRAP
 INFORMATION.
 - FPM WITHIN THE GREASE DUCT SYSTEM
 AS PER 2001 FBC/M 506.3.6
 - PROVIDE MATERIAL OF GREASE DUCT IN
 ACCORDANCE WITH 2001 FBC/M 506.3.3.
 - GREASE DUCT TO HAVE A MINIMUM SLOPE
 OF 1/4" PER FT.
 - PROVIDE DETAIL FOR HANGING THE HOOD.
  
 SEE THE ATTACHED PROVISO, THIS WAS ON
 THE APPROVED MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.