Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-15 Cont ID  
Sent By hmoser Date 2005-06-15 Time 09:34 Rev Time 0.50
Received By prafter Date 2005-07-07 Time 07:53 Sent To  
Notes
2005-07-07 00:00:00MECH.PLAN REV.
  
 PROVISO: PROVIDE FOR BALANCED AIR IF
 POSABLE FBC/M 601.4 .
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-05 Cont ID  
Sent By pkrauss Date 2005-04-05 Time 13:28 Rev Time 0.35
Received By pkrauss Date 2005-04-05 Time 13:28 Sent To  
Notes
2005-04-05 00:00:00BALANCED AIR REQUIRED PER 2001 FBC/M
 601.4 - RETURN AIR REQUIRED FROM
 HABITABLE ROOMS THAT ARE ISOLATED FROM
 THE RETURN.PLEASE CONTANCT HAROLD
 MOSER, CHIEF MECHANICAL INSPECTOR SHOULD
 RETURN AIR NOT BE ATTAINABLE.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC/M
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.