Plan Review Details - Permit 05031177
Plan Review Stops For Permit 05031177
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-07 Cont ID  
Sent By jwitmer Date 2005-06-07 Time 10:52 Rev Time 0.75
Received By jwitmer Date 2005-06-07 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-19 Cont ID  
Sent By jwitmer Date 2005-04-19 Time 07:49 Rev Time 1.11
Received By jwitmer Date 2005-04-19 Time 07:48 Sent To  
Notes
2005-04-19 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 05031177
 ADD: 1335 OKEECHOBEE RD
 CONT:BUTLER
 TEL:(561)832-9700
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) PROVIDE THE MINIMUM BUILDING
 CLASSIFICATION, 601.2.1
  
 4) 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-12 Cont ID  
Sent By dpalmer Date 2005-10-12 Time 12:26 Rev Time 0.50
Received By dpalmer Date 2005-10-12 Time 12:18 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-06 Cont ID  
Sent By dpalmer Date 2005-06-06 Time 06:45 Rev Time 0.50
Received By dpalmer Date 2005-06-06 Time 06:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-25 Cont ID  
Sent By dpalmer Date 2005-03-25 Time 16:34 Rev Time 1.00
Received By dpalmer Date 2005-03-25 Time 16:33 Sent To  
Notes
2005-03-25 00:00:00******* UNSAT ******
  
 1)NOTE: PLEASE CORRELATE RISER/ PANEL
 SCHEDULE/ PLANS.
 RISER DOES NOT INDICATE APANEL "A",
 HOWEVER SHOWS A PANEL "B"??
 215.5
  
 2)NOTE: PLEASE SEE PLANS INDICATE AN
 EXSITING COND UNIT, HOWEVER PANEL
 SCHEDULE INDICATES A NEW COND UNIT?
  
 3)NOTE: PLEASE CLARIFY NEW OR EXISTING
 GFI REQUIRED FOR COND UNITS. 210.63
 PANEL SCHEDULE INDICATES AND EXSITNG
 ROOFTOP RECEPT.
  
 4)NOTE: PLEASE SHOW ALL DISC'S REQUIRED
 FOR AHU'S , CU'S. 440.11
  
 5)NOTE: PLEASE SEE MISSING "SHOW WINDOW"
 RECEPTS ON PLANS. PANEL SCHEDULE
 INDICATES "SHOW WINDOW" RECEPTS, HOWEVER
 THESE CIRCUITS ARE SHOWN GOING TO A
 POWER POLE LOCATED IN THE CENTER OF THE
 SHOWROOM.
 PLEASE SEE 210.62, 220.12, NO OTHER
 LOADS ARE PERMITTED ON SHOW WINDOW
 CIRCUIT, PLEASE ALSO SEE 200 VA PER FT.
  
 6)NOTE: PLEASE VERIFY #3 EQUIPMENT
 GROUNDING CONDUCTOR SHOWN FROM 175A MAIN
 BRKR TO PANEL. THIS IS PERMITTED AND
 ONLY A NOTE:
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 THIS WILL HELP IN PROCESS TO EXPEDITE
 PLANS FOR PERMITTING.
 PLEASE SUBMIT ONE COPY OF ANY OLD SHEETS
 FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESTITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-10-13 Cont ID  
Sent By mwennerg Date 2005-10-13 Time 10:20 Rev Time 0.00
Received By mwennerg Date 2005-10-13 Time 10:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-06-02 Cont ID  
Sent By mwennerg Date 2005-06-02 Time 15:02 Rev Time 0.00
Received By mwennerg Date 2005-06-02 Time 15:02 Sent To  
Notes
2005-06-02 00:00:00****APPROVED****
  
 AS INDICATED ON THE DRAWINGS, SEPARATE
 SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR THE FIRE SPRINKLER AND FIRE ALARM
 REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-06 Cont ID  
Sent By mwennerg Date 2005-04-06 Time 12:54 Rev Time 0.00
Received By mwennerg Date 2005-04-06 Time 12:54 Sent To  
Notes
2005-04-06 00:00:001) ALL LIFE SAFETY SHALL COMPLY WITH
 NFPA 101, 2003 EDITION AFTER JAN.1,
 2005.
  
 2) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO BE IN ACCORDANCE WITH NFPA
 241.
  
 3) ADDITIONAL EMERGENCY LIGHTING IS
 REQUIRED IN THE MIDDLE OPEN OFFICE AREA.
 ADDITIONAL EXIT SIGNS MAY BE REQUIRED AT
 THE REQUEST OF THE FIELD INSPECTOR.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 14:40 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 14:40 Sent To E
Notes
2005-10-11 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 13:56 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 13:56 Sent To M
Notes
2005-09-01 00:00:00TO "PKRAUSS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-11 Cont ID  
Sent By adarroug Date 2005-08-11 Time 18:46 Rev Time 0.00
Received By adarroug Date 2005-08-11 Time 18:46 Sent To M
Notes
2005-08-11 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 15:10 Rev Time 0.00
Received By shill Date 2005-06-10 Time 15:10 Sent To P
Notes
2005-06-10 00:00:00TO PAUL SCHMITZ DESK (PLUMBING LAST
 REVIEW; TOOK OFF OF BOARD)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 14:22 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 14:22 Sent To  
Notes
2005-05-27 00:00:00TO "COMM" BD#25
2005-05-16 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-02 Cont ID  
Sent By adarroug Date 2005-04-29 Time 10:30 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 14:09 Sent To  
Notes
2005-03-23 00:00:00TO "COMM" BD#15

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-01 Cont ID  
Sent By pkrauss Date 2005-09-01 Time 14:25 Rev Time 0.35
Received By pkrauss Date 2005-09-01 Time 14:04 Sent To  
Notes
2005-09-01 00:00:00REVISED HANGING OF THE AHU.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-16 Cont ID  
Sent By pkrauss Date 2005-08-16 Time 14:59 Rev Time 0.45
Received By pkrauss Date 2005-08-16 Time 14:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-18 Cont ID  
Sent By pkrauss Date 2005-04-18 Time 14:20 Rev Time 0.45
Received By pkrauss Date 2005-04-18 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-11 Cont ID  
Sent By pschmitz Date 2005-06-11 Time 08:59 Rev Time 0.00
Received By pschmitz Date 2005-06-11 Time 08:58 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-26 Cont ID  
Sent By kstevens Date 2005-03-26 Time 14:00 Rev Time 0.55
Received By kstevens Date 2005-03-26 Time 14:00 Sent To  
Notes
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT 3.1 LUNCH ROOM SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. SHOW:
 A) HEIGHT 11-4.24.2
 B) KNEE CLEARANCE 11-4.24.3
 C) SINK DEPTH 11-4.24.4
 D) CLEAR FLOOR SPACE 11-4.24.5 FORWARD
 APPROACH REQUIRED. MAXIMUM 19"
 UNDERNEATH THE SINK. NO CABINET DOORS
 ALLOWED.
 E) EXPOSED PIPES & SURFACES 11-4.24.6
 F) FAUCETS 11-4.24.7
 2) A DRINKING FAUCET IS REQUIRED PER
 TABLE 403.1.
 3) SHT M1 WATER ISOMETRIC. FULL OPEN
 VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED LINES. SECTION 606.1(4).
 4) SHT M1 PLUMBING NOTES #10, AIR
 CHAMBERS ARE NOT APPROVED. SECTION 604.9
 IF WATER HAMMER ARRESTORS ARE PROVIDED,
 THEY SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]