Plan Review Details - Permit 05031175
Plan Review Stops For Permit 05031175
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-04 Cont ID  
Sent By mjacobs Date 2005-04-04 Time 15:08 Rev Time 0.75
Received By mjacobs Date 2005-04-04 Time 15:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-23 Cont ID  
Sent By jgomez Date 2005-03-23 Time 10:42 Rev Time 0.33
Received By jgomez Date 2005-03-23 Time 10:42 Sent To PC
Notes
2005-03-23 00:00:00CHECKLIST:
 1- FLAT ROOF SYSTEM FROM FIRESTONE
 BUILDING PRODUCTS CO. IS LIMITED BY
 GENERAL LIMITATION #9 FOR -45PSF AS THE
 MAX. DESIGN PRESSURE. SYSTEM CAN'T BE
 ENHANCED TO ALLOW FOR GREATER DESIGN
 PRESSURES AS REQUIRED AT PERIMETER AND
 CORNERS OF ROOF. SEE TABLE 1606.2B
 FLORIDA BUILDING CODE 2001.
 NEED ANOTHER FLAT ROOF SYSTEM THAT CAN
 BE ENHANCED TO RESIST HIGHER UPLIFT
 REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By alange Date 2005-03-21 Time 14:52 Rev Time 0.33
Received By alange Date 2005-03-21 Time 14:49 Sent To  
Notes
2005-03-21 00:00:00DENIED
 SUBMIT 2 COMPLETE SETS OF PRODUCT
 APPROVALS FOR MONIER LIFETILE.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop HIST HISTORICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2005-03-21 00:00:00OK PER E BOWERS 3-21-05