Plan Review Details - Permit 05031157
Plan Review Stops For Permit 05031157
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 08:06 Rev Time 0.44
Received By jwitmer Date 2005-08-28 Time 07:42 Sent To E
Notes
2005-08-28 00:00:00BUILDING PROVISO:
 MANSARD ROOF NOT PART OF THIS PERMIT,
 NO PRODUCT APPROVALS SUBMITTED, NOR
 UNDER THE ROOFING PERMIT . JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-13 Cont ID  
Sent By jwitmer Date 2005-08-13 Time 16:57 Rev Time 0.55
Received By jwitmer Date 2005-08-13 Time 16:57 Sent To  
Notes
2005-08-13 00:00:00MET WITH ROMAN BUCKNER 8/01/05 HE WAS
 NOT SURE IF THIS JOB WAS USING METAL
 MANSARD WAS GOING TO GET BACK WITH ME?
 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-19 Cont ID  
Sent By jwitmer Date 2005-07-19 Time 17:38 Rev Time 0.77
Received By jwitmer Date 2005-07-19 Time 17:38 Sent To  
Notes
2005-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031157
 ADD: 500 PALM STREET STE"C"
 CONT:MIKE MOORE CONST
 TEL: (561)262-0314
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 ""NO ROOFING PRODUCT APPR.SUBMITTED"""
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS INDICATE ROOF DAMAGE TO THE
 MANSARD ROOFING, NO PRODUCT INFORMATION
 WAS PROVIDED FOR THE METAL ROOF.NOTE
 THIS IS IN THE FIRE DISTRICT A CLASS A
 OR B ROOF COVERING IS REQUIRED F102.2.4.
  
 2) THE BUILT UP ROOFING PRODUCT APPROVAL
 SUBMITTED DOESN'T INDICATE WHICH SYSTEM
 IS TO BE USED( FROM FIRST REVIEW). THE
 SECOND ISSUE IS LOW PRESSURES FOR ZONE
 THREE.PLANS INDICATE -68.2 IN ZONE
 THREE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-18 Cont ID  
Sent By jwitmer Date 2005-04-18 Time 11:07 Rev Time 2.22
Received By jwitmer Date 2005-04-18 Time 10:47 Sent To PC
Notes
2005-04-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031157
 ADD: 500 PALM STREET STE"C"
 CONT:MIKE MOORE CONST
 TEL: (561)262-0314
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS INDICATE ROOF DAMAGE TO THE
 MANSARD ROOFING, NO PRODUCT INFORMATION
 WAS PROVIDED FOR THE METAL ROOF.NOTE
 THIS IS IN THE FIRE DISTRICT A CLASS A
 OR B ROOF COVERING IS REQUIRED F102.2.4.
  
 2) THE BUILT UP ROOFING PRODUCT APPROVAL
 SUBMITTED DOESN'T INDICATE WHICH SYSTEM
 IS TO BE USED. THE SECOND ISSUE IS LOW
 PRESSURES FOR ZONE THREE.PLANS INDICATE
 -68.2 IN ZONE THREE.
  
 3) THE PLANS INDICATE WOOD ROOF FRAMING
 BUT NO INDICATION IF THIS IS NEW WORK OR
 EXISTING? WHAT TYPE OF SPECIES OF WOOD
 IS USED AND THE GRADE TO DETERMINE THE
 SPANS? PROVIDE LIVE LOAD/ DEAD LOADS AND
  
 DEFLECTION LIMITATION. FL BLD CODE
 104.2.1.2 ADDITIONAL INFORMATION
 REQUIRED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-29 Cont ID  
Sent By dpalmer Date 2005-08-29 Time 07:31 Rev Time 0.30
Received By dpalmer Date 2005-08-29 Time 07:27 Sent To I
Notes
2005-08-29 00:00:00NEW SHEET, NEEDS REVIEW AND STAMPING BY
 OTHER TRADES.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-25 Cont ID  
Sent By dpalmer Date 2005-03-25 Time 10:41 Rev Time 0.30
Received By dpalmer Date 2005-03-25 Time 10:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-08 Cont ID  
Sent By mwennerg Date 2005-09-08 Time 10:38 Rev Time 0.00
Received By mwennerg Date 2005-09-08 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-04-07 Cont ID  
Sent By mwennerg Date 2005-04-07 Time 15:26 Rev Time 0.00
Received By mwennerg Date 2005-04-07 Time 15:26 Sent To  
Notes
2005-04-07 00:00:001) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL BE IN ACCORDANCE WITH
 NFPA 241.
  
 2) PLEASE BE ADVISED THAT ALL WORK IS TO
 COMPLY WITH NFPA 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 14:49 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 14:49 Sent To B
Notes
2005-08-19 00:00:00TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 11:00 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#27
2005-06-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 10:47 Rev Time  
Received By jwitmer Date 2005-03-24 Time 10:02 Sent To  
Notes
2005-03-24 00:00:00TO "COMM" BD#61

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-15 Cont ID  
Sent By pkrauss Date 2005-09-15 Time 07:14 Rev Time 0.40
Received By pkrauss Date 2005-09-15 Time 06:31 Sent To  
Notes
2005-09-15 00:00:00PLEASE NOTE - A/C CONTRACTOR INDICATED
 ON THE APPLICATION IS NOT CURRENTLY
 REGISTERED WITH THE STATE.A/C PERMIT
 WILL HAVE TO BE APPLIED FOR SEPARATELY
 BY A STATE REGISTERED OR LICENSED
 CONTRACTOR.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY OTHER QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-04-13 Cont ID  
Sent By pkrauss Date 2005-04-13 Time 07:34 Rev Time 0.30
Received By pkrauss Date 2005-04-13 Time 07:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-18 Cont ID  
Sent By pschmitz Date 2005-09-18 Time 01:26 Rev Time 0.00
Received By pschmitz Date 2005-09-18 Time 01:26 Sent To  
Notes
2005-09-18 00:00:00STAMPED NEW SHEET

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-30 Cont ID  
Sent By pschmitz Date 2005-07-30 Time 09:53 Rev Time 0.00
Received By pschmitz Date 2005-07-30 Time 09:53 Sent To  
Notes
2005-07-30 00:00:00ROOF:
 EXISTING GUTTER ANSD DOWN SPOUTS, NO
 PARAPET.PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-26 Cont ID  
Sent By kstevens Date 2005-03-26 Time 14:19 Rev Time 0.33
Received By kstevens Date 2005-03-26 Time 14:19 Sent To  
Notes
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) MORE INFORMATION FOR ROOF DRAINAGE IS
 REQUIRED. SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SQUARE FOOTAGE OF THE ROOF AND SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS. INDICAT SQUARE FOOTAGE TO BE
 DRAINING INTO THE PRIMARY ROOF DRAIN.
 ONLY ONE ROOF DRAIN SHOWN. SHOW THE SIZE
 OF THE NEW OVERFLOW SCUPPER AND
 DOWNSPOUT. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS AND TABLES.
  
  