Plan Review Stops For Permit 05031134 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
N |
Date |
2005-04-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-04-12 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2005-04-12 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05031134 | | ADD: 400 N CONGRESS# 110 | | CONT: CRL CONSTRUCTION | | TEL: (561)248-7177 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1)PROVIDE NOC RECORDED WITH THE CLERK OF | | COURT BEFORE A PERMIT CAN BE ISSUED. | | | | 2)PLANS, SPECIFICATIONS,REPORTS OR | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE (NOT | | INITIALS) AND SEAL OF THE DESIGN | | PROFESSIONAL AFFIXED TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | 3) SEE DOOR WITH THE WINDOWS IN THE | | WALL.11-4.13.6 MANEUVERING CLEARENCES | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | AT DOORS THAT ARE NOT AUTOMATIC OR | | POWER-ASSISTED SHALL BE AS SHOWN IN FIG. | | 25. THE FLOOR OR GROUND AREA WITH IN THE | | REQUIRED CLEARENCES SHALL BE CLEAR & | | LEVEL. | | | | 4) FL BLD CODE 104.2.1.2 ADDITIONAL | | INFORMATION REQUIRED, THIS SAME WALL, | | ARE THE WINDOWS RATED? IS THIS BUILDING | | FIRE SPRINKLERED? | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2005-08-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-08-28 |
Time |
13:09 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2005-08-28 |
Time |
13:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2005-06-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-06-06 |
Time |
16:49 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2005-06-06 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-04-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-04-12 |
Time |
08:49 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2005-04-12 |
Time |
08:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-09-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-09-01 |
Time |
17:41 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-09-01 |
Time |
17:27 |
Sent To |
|
|
Notes |
2005-09-01 00:00:00 | REDLINED PLANS ONCE AGAIN. | | | | *************************************** | | | | A MAIN CIRCUIT BRKR WILL BE REQUIRED IN | | PANEL 1L5. | | PLEASE SEE 240.21, 408.16. | | | | | | FUTURE REVISIONS WILL NOT BE REDLINED IF | | NOT CORRECTED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2005-05-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-05-17 |
Time |
06:50 |
Rev Time |
0.30 |
Received By |
dpalmer |
Date |
2005-05-17 |
Time |
06:41 |
Sent To |
|
|
Notes |
2005-05-17 00:00:00 | ******* PLANS REDLINED *********** | | | | PLEASE SEE NOTE #2 FROM PREVIOUS REVIEW | | INDICATED MISSING MCB REQUIRED ON | | SECONDARY SIDE OF TRANSFORMER. PLEASE | | SEE RESPONSE LETTER FROM ARCH INDICATES | | TO SEE REVISED ELECTRICAL RISER DIAGRAM, | | HOWEVER RISER WAS NOT REVISED TO INCLUDE | | THE REQUIRED MCB IN PANEL IL5. | | THIS HAS BEEN REDLINED ON PLANS FOR A | | MCB TO BE INSTALLED AS REQUIRED 408.16 | | ETC. | | | | PLANS NOW SIGNED WITH SIGNATURE FROM | | ARCHITECT. | | | | ELECTRICAL PLANS STAMPED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-03-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-03-25 |
Time |
09:14 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2005-03-25 |
Time |
09:14 |
Sent To |
|
|
Notes |
2005-03-25 00:00:00 | *** UNSAT *** | | | | 1)NOTE: PLEASE SEE PLANS APPEAR TO BE | | SIGNED WITH INITIALS. PLEASE SEE PLANS | | MUSTBE SIGNED WITH LEGAL "SIGNATURE". | | IF INDEED THIS IS LEGAL SIGNATURE, | | PLEASE PROVIDE A SIGNED, DATED AND | | SEALEDNOTORIZED LETTER PERTAINING TO | | SIGNATURE. | | | | 2)NOTE: PLEASE SEE PANEL IL5 IS SHOWN AS | | MLO WITHOUT A MAIN AND IS SHOWN COMING | | DIRECTLY FROM TRANSFORMER. | | PLEASE SEE A MAIN CIRCUIT BRKR IS | | REQUIRED. 225.31,240.4,230.71,408.16 | | | | 3)NOTE: PLEASE SEE MISSING PANEL | | SCHEDULE FOR CP. | | PLEASE SHOW NEW CIRCUITING #'S AND | | CORRELATE WITH PANEL SCHEDULES. | | | | | | PLEASE SEE OTHER POSSIBLE COMMENTS WHICH | | MAY AFFECT ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2005-09-14 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-09-14 |
Time |
14:06 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-09-14 |
Time |
14:06 |
Sent To |
|
|
Notes |
2005-09-14 00:00:00 | ******OK****** | | | | THREE SETS OF PLANS STAMPED 9/14/05 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2005-05-31 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-05-31 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-05-31 |
Time |
14:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2005-04-04 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-04-04 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-04-04 |
Time |
15:25 |
Sent To |
|
|
Notes |
2005-04-04 00:00:00 | 1) SEPARATE SHOP DRAWINGS AND PERMITS | | FOR THE FIRE ALARM AND OR FIRE SPRINKLER | | REMODELS ARE REQUIRED IF APPLICABLE. | | | | | | MIKE WENNERGREN, A/CAPTAIN | | WPBFR(561) 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-08-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-24 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-24 |
Time |
09:27 |
Sent To |
|
|
Notes |
2005-08-24 00:00:00 | TO "COMM" BD#2 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-07-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-05 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-05 |
Time |
16:38 |
Sent To |
M |
|
Notes |
2005-07-05 00:00:00 | TO "PKRAUSS" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-05-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-04 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-04 |
Time |
16:27 |
Sent To |
|
|
Notes |
2005-05-13 00:00:00 | TO "COMM" BD#29 | 2005-05-04 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-03-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-03-23 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-03-23 |
Time |
14:00 |
Sent To |
|
|
Notes |
2005-03-23 00:00:00 | TO "COMM" BD#4 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2005-09-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-09-14 |
Time |
13:03 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2005-09-14 |
Time |
13:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2005-07-25 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-07-25 |
Time |
08:55 |
Rev Time |
0.75 |
Received By |
prafter |
Date |
2005-07-25 |
Time |
08:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2005-06-30 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-06-30 |
Time |
09:06 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2005-06-30 |
Time |
09:05 |
Sent To |
|
|
Notes |
2005-06-30 00:00:00 | DENIED: | | REFERENCE 2001 FBC(M)601.4, BALANCED | | RETURN AIR REQUIRED.PLAN INDICATES | | RETURN AIR THROUGH UNDERCUT DOOR, PLEASE | | NOTE IN THE EXCEPTION #1 & 2 A 1" DOOR | | UNDERCUT IS REQUIRED ALONG WITH A RETURN | | AIR JUMPER OR TRANSFER GRILLE. | | | | PLEASE SHOW COMPLIANCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2005-04-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-04-12 |
Time |
06:48 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2005-04-12 |
Time |
06:44 |
Sent To |
|
|
Notes |
2005-04-12 00:00:00 | DENIED: | | RETURN AIR IS NOT INDICATED ON THE PLAN | | AS EXISTING, RELOCATED OR NEW.PLEASE | | VERFIY AND IDENTIFY RETURNS.PLEASE | | NOTE, NO COMBUSTIBLES ALLOWED IN RETURN | | AIR PLENUMS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2005-09-18 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2005-09-18 |
Time |
00:57 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2005-09-18 |
Time |
00:57 |
Sent To |
|
|
Notes |
2005-09-18 00:00:00 | PROVISO: | | PROVISO: | | 1) IN THE REMOVAL OF ANY PART OF A | | DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | PROHIBITED. SECTION 704.5. | | 2) NO DEMO'D PIPING SHALL BE COVERED | | PRIOR TO INSPECTION BY FIELD INSPECTOR. | | SECTION 312.1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2005-06-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-06-04 |
Time |
18:55 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2005-06-04 |
Time |
18:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-03-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-03-26 |
Time |
08:32 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2005-03-26 |
Time |
08:32 |
Sent To |
|
|
Notes |
2005-03-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) FULL OPEN VALVES ARE REQUIRED ON ALL | | WATER DOWN-FEED LINES. SECTION 606.1(4). | | 2) IN THE REMOVAL OF ANY PART OF A | | DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | PROHIBITED. SECTION 704.5. | | 3) NO DEMO'D PIPING SHALL BE COVERED | | PRIOR TO INSPECTION BY FIELD INSPECTOR. | | SECTION 312.1 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|