Plan Review Details - Permit 05031134
Plan Review Stops For Permit 05031134
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-04-12 Cont ID  
Sent By jwitmer Date 2005-04-12 Time 09:04 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2005-04-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031134
 ADD: 400 N CONGRESS# 110
 CONT: CRL CONSTRUCTION
 TEL: (561)248-7177
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE (NOT
 INITIALS) AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) SEE DOOR WITH THE WINDOWS IN THE
 WALL.11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG.
 25. THE FLOOR OR GROUND AREA WITH IN THE
 REQUIRED CLEARENCES SHALL BE CLEAR &
 LEVEL.
  
 4) FL BLD CODE 104.2.1.2 ADDITIONAL
 INFORMATION REQUIRED, THIS SAME WALL,
 ARE THE WINDOWS RATED? IS THIS BUILDING
 FIRE SPRINKLERED?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 13:09 Rev Time 0.33
Received By jwitmer Date 2005-08-28 Time 13:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-06 Cont ID  
Sent By jwitmer Date 2005-06-06 Time 16:49 Rev Time 0.55
Received By jwitmer Date 2005-06-06 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-12 Cont ID  
Sent By jwitmer Date 2005-04-12 Time 08:49 Rev Time 1.11
Received By jwitmer Date 2005-04-12 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 17:41 Rev Time 0.25
Received By dpalmer Date 2005-09-01 Time 17:27 Sent To  
Notes
2005-09-01 00:00:00REDLINED PLANS ONCE AGAIN.
  
 ***************************************
  
 A MAIN CIRCUIT BRKR WILL BE REQUIRED IN
 PANEL 1L5.
 PLEASE SEE 240.21, 408.16.
  
  
 FUTURE REVISIONS WILL NOT BE REDLINED IF
 NOT CORRECTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-17 Cont ID  
Sent By dpalmer Date 2005-05-17 Time 06:50 Rev Time 0.30
Received By dpalmer Date 2005-05-17 Time 06:41 Sent To  
Notes
2005-05-17 00:00:00******* PLANS REDLINED ***********
  
 PLEASE SEE NOTE #2 FROM PREVIOUS REVIEW
 INDICATED MISSING MCB REQUIRED ON
 SECONDARY SIDE OF TRANSFORMER. PLEASE
 SEE RESPONSE LETTER FROM ARCH INDICATES
 TO SEE REVISED ELECTRICAL RISER DIAGRAM,
 HOWEVER RISER WAS NOT REVISED TO INCLUDE
 THE REQUIRED MCB IN PANEL IL5.
 THIS HAS BEEN REDLINED ON PLANS FOR A
 MCB TO BE INSTALLED AS REQUIRED 408.16
 ETC.
  
 PLANS NOW SIGNED WITH SIGNATURE FROM
 ARCHITECT.
  
 ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-25 Cont ID  
Sent By dpalmer Date 2005-03-25 Time 09:14 Rev Time 0.50
Received By dpalmer Date 2005-03-25 Time 09:14 Sent To  
Notes
2005-03-25 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PLANS APPEAR TO BE
 SIGNED WITH INITIALS. PLEASE SEE PLANS
 MUSTBE SIGNED WITH LEGAL "SIGNATURE".
 IF INDEED THIS IS LEGAL SIGNATURE,
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALEDNOTORIZED LETTER PERTAINING TO
 SIGNATURE.
  
 2)NOTE: PLEASE SEE PANEL IL5 IS SHOWN AS
 MLO WITHOUT A MAIN AND IS SHOWN COMING
 DIRECTLY FROM TRANSFORMER.
 PLEASE SEE A MAIN CIRCUIT BRKR IS
 REQUIRED. 225.31,240.4,230.71,408.16
  
 3)NOTE: PLEASE SEE MISSING PANEL
 SCHEDULE FOR CP.
 PLEASE SHOW NEW CIRCUITING #'S AND
 CORRELATE WITH PANEL SCHEDULES.
  
  
 PLEASE SEE OTHER POSSIBLE COMMENTS WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 14:06 Sent To  
Notes
2005-09-14 00:00:00******OK******
  
 THREE SETS OF PLANS STAMPED 9/14/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-31 Cont ID  
Sent By mwennerg Date 2005-05-31 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2005-05-31 Time 14:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-04-04 Cont ID  
Sent By mwennerg Date 2005-04-04 Time 15:25 Rev Time 0.00
Received By mwennerg Date 2005-04-04 Time 15:25 Sent To  
Notes
2005-04-04 00:00:001) SEPARATE SHOP DRAWINGS AND PERMITS
 FOR THE FIRE ALARM AND OR FIRE SPRINKLER
 REMODELS ARE REQUIRED IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 09:27 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 09:27 Sent To  
Notes
2005-08-24 00:00:00TO "COMM" BD#2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 16:38 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 16:38 Sent To M
Notes
2005-07-05 00:00:00TO "PKRAUSS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-04 Time 14:26 Rev Time 0.00
Received By adarroug Date 2005-05-04 Time 16:27 Sent To  
Notes
2005-05-13 00:00:00TO "COMM" BD#29
2005-05-04 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 14:00 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 14:00 Sent To  
Notes
2005-03-23 00:00:00TO "COMM" BD#4

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-09-14 Cont ID  
Sent By pkrauss Date 2005-09-14 Time 13:03 Rev Time 0.40
Received By pkrauss Date 2005-09-14 Time 13:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-07-25 Cont ID  
Sent By prafter Date 2005-07-25 Time 08:55 Rev Time 0.75
Received By prafter Date 2005-07-25 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-06-30 Cont ID  
Sent By pkrauss Date 2005-06-30 Time 09:06 Rev Time 0.30
Received By pkrauss Date 2005-06-30 Time 09:05 Sent To  
Notes
2005-06-30 00:00:00DENIED:
 REFERENCE 2001 FBC(M)601.4, BALANCED
 RETURN AIR REQUIRED.PLAN INDICATES
 RETURN AIR THROUGH UNDERCUT DOOR, PLEASE
 NOTE IN THE EXCEPTION #1 & 2 A 1" DOOR
 UNDERCUT IS REQUIRED ALONG WITH A RETURN
 AIR JUMPER OR TRANSFER GRILLE.
  
 PLEASE SHOW COMPLIANCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-12 Cont ID  
Sent By pkrauss Date 2005-04-12 Time 06:48 Rev Time 0.35
Received By pkrauss Date 2005-04-12 Time 06:44 Sent To  
Notes
2005-04-12 00:00:00DENIED:
 RETURN AIR IS NOT INDICATED ON THE PLAN
 AS EXISTING, RELOCATED OR NEW.PLEASE
 VERFIY AND IDENTIFY RETURNS.PLEASE
 NOTE, NO COMBUSTIBLES ALLOWED IN RETURN
 AIR PLENUMS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-18 Cont ID  
Sent By pschmitz Date 2005-09-18 Time 00:57 Rev Time 0.00
Received By pschmitz Date 2005-09-18 Time 00:57 Sent To  
Notes
2005-09-18 00:00:00PROVISO:
 PROVISO:
 1) IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5.
 2) NO DEMO'D PIPING SHALL BE COVERED
 PRIOR TO INSPECTION BY FIELD INSPECTOR.
 SECTION 312.1

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-04 Cont ID  
Sent By kstevens Date 2005-06-04 Time 18:55 Rev Time 0.33
Received By kstevens Date 2005-06-04 Time 18:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-26 Cont ID  
Sent By kstevens Date 2005-03-26 Time 08:32 Rev Time 0.75
Received By kstevens Date 2005-03-26 Time 08:32 Sent To  
Notes
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FULL OPEN VALVES ARE REQUIRED ON ALL
 WATER DOWN-FEED LINES. SECTION 606.1(4).
 2) IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5.
 3) NO DEMO'D PIPING SHALL BE COVERED
 PRIOR TO INSPECTION BY FIELD INSPECTOR.
 SECTION 312.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]