Plan Review Details - Permit 05031037
Plan Review Stops For Permit 05031037
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-04-19 Cont ID  
Sent By kstevens Date 2005-04-19 Time 18:13 Rev Time 0.50
Received By kstevens Date 2005-04-19 Time 18:12 Sent To  
Notes
2005-04-19 00:00:00 
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-04-02 Cont ID  
Sent By kstevens Date 2005-04-02 Time 05:47 Rev Time 0.60
Received By kstevens Date 2005-04-02 Time 05:47 Sent To  
Notes
2005-04-02 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
 2) APPLICATION INDICATES INSTALLATION OF
 GAS LINES TO BBQ AND POOL HEATER, BUT
 PLANS INDICATE THESE LINES ARE EXISTING.
 PLEASE CLARIFY.
 3) VALUATION OF THE PERMIT APPLICATION
 SHALL REFLECT THE COST OF ALL GAS
 APPLIANCES, INCLUDING THE POOL HEATER,
 THE GAS LIGHTS, THE TANKLESS W/HEATER,
 AND THE BBQ, NO MATTER WHO PROVIDES
 THESE APPLIANCES. SECTION 104.6.5.
 4) BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-05 Cont ID  
Sent By adarroug Date 2005-04-05 Time 11:31 Rev Time 0.00
Received By adarroug Date 2005-04-05 Time 11:31 Sent To G
Notes
2005-04-05 00:00:00TO "KSTEVENS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 17:17 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 17:17 Sent To G
Notes
2005-03-17 00:00:00TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved