Plan Review Details - Permit 05030969
Plan Review Stops For Permit 05030969
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-29 Cont ID  
Sent By jwitmer Date 2005-06-29 Time 14:42 Rev Time 0.55
Received By jwitmer Date 2005-06-29 Time 14:42 Sent To PC
Notes
2005-06-29 00:00:00REVISION- OK JJJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-20 Cont ID  
Sent By jwitmer Date 2005-05-20 Time 08:35 Rev Time 1.66
Received By jwitmer Date 2005-05-20 Time 07:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-13 Cont ID  
Sent By jwitmer Date 2005-04-13 Time 13:19 Rev Time 2.22
Received By jwitmer Date 2005-04-13 Time 13:19 Sent To  
Notes
2005-04-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030969
 ADD:1720 CENTREPARK DR E.
 CONT:THE WEITZ CO
 TEL: (561)951-2677
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) 1016.1.1 PLANS DO NOT INDICATE THE
 ILLUMINATION OF THE EXIT CORRIDOR.
  
 4)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-03-31 Cont ID  
Sent By dpalmer Date 2005-03-31 Time 11:36 Rev Time 0.05
Received By dpalmer Date 2005-03-31 Time 11:36 Sent To  
Notes
2005-03-31 00:00:00NO ELECTRICAL SHOWN.
 ONLY A REFLECTED CEILING PLAN.
 ELECTRICAL PLANS/ PERMIT AT LATER DATE.
  
 SEE ANY POSSIBLE FIRE REVIEW COMMENTS
 WHICH MAY REQUIRE EM/EXT LTS ON AN
 ELECTRICAL PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-11 Cont ID  
Sent By mwennerg Date 2005-05-11 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2005-05-11 Time 11:06 Sent To  
Notes
2005-05-11 00:00:001) PLEASE NOTE THAT THE FIRE SPRINKLER
 DRAWINGS ARE REDLINED IN REGARDS TO THE
 SEPARATE PERMIT REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By mwennerg Date 2005-04-05 Time 14:45 Rev Time 0.00
Received By mwennerg Date 2005-04-05 Time 14:45 Sent To  
Notes
2005-04-05 00:00:001) PLANS DON'T SHOW EXIT SIGNS AND
 EMERGENCY LIGHTING. PLEASE SHOW THE
 LOCATIONS OF EXISTING AND NEW
 APPLIANCES.
  
 2) PLEASE SHOW THE LOCATIONS OF FIRE
 EXTINGUISHERS TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE ALARM AND FIRE
 SPRINKLER REMODELS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-04-21 Time 10:27 Rev Time 0.00
Received By adarroug Date 2005-04-21 Time 10:27 Sent To  
Notes
2005-05-10 00:00:00TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-13 Cont ID  
Sent By jwitmer Date 2005-04-13 Time 13:42 Rev Time 0.00
Received By jwitmer Date 2005-03-16 Time 16:20 Sent To  
Notes
2005-03-29 00:00:00TO "COMM" BD#47

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-05-16 Cont ID  
Sent By pkrauss Date 2005-05-16 Time 21:40 Rev Time 0.45
Received By pkrauss Date 2005-05-16 Time 21:38 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved