Plan Review Details - Permit 05030839
Plan Review Stops For Permit 05030839
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By jgomez Date 2005-03-15 Time 13:54 Rev Time 0.50
Received By jgomez Date 2005-03-15 Time 13:54 Sent To PC
Notes
2005-03-15 00:00:00BUILDING REVIEW PROVISO:
 1- NEED TO INSTALL 2 LAYERS OF
 UNDERLAYMENT AS REQUIRED BY SECTION
 1507.3.8 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-15 Cont ID  
Sent By jgomez Date 2005-03-15 Time 12:48 Rev Time 0.50
Received By jgomez Date 2005-03-15 Time 12:48 Sent To PC
Notes
2005-03-15 00:00:00CHECKLIST:
 1- FLORIDA PRODUCT APPROVAL FL1476 AND
 DADE COUNTY NOA NO 03-0306.14 REPORT
 DON'T CORRESPOND TO EACH OTHER. CLARIFY
 IF FLORIDA PRODUCT APPROVAL FL728 IS THE
 ONE INTENDED TO BE USED IN THIS
 APPLICATION.
  
 2- ROOF SLOPE OF 4:12 REQUIRES TWO
 LAYERS OF UNDERLAYMENT AS REQUIRED BY
 SEC. 1507.3.8 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.