Plan Review Details - Permit 05030554
Plan Review Stops For Permit 05030554
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-13 Cont ID  
Sent By shill Date 2005-05-13 Time 15:18 Rev Time 1.00
Received By shill Date 2005-05-13 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-22 Cont ID  
Sent By shill Date 2005-03-22 Time 10:31 Rev Time 2.00
Received By shill Date 2005-03-22 Time 10:31 Sent To  
Notes
2005-03-22 00:00:00PERMIT #05030554
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) THE SEAL IS TO BE DATED, FAC61G1-15.
  
 3.) OCCUPANCY CLASSIFICATIONS OF B AND M
 (STATED AS ?RETAIL?) ARE DECLARED, SHEET
 A.PLEASE READ FBC CHAPTER 3.IF THERE
 ARE TWO OCCUPANCIES, PLEASE SHOW
 OCCUPANCY SEPARATION REQUIRED FBC TABLE
 704.1.
  
 4.) SHOW THE MANEUVERING CLEARANCE, PUSH
 SIDE, FOR THE NEW DOCTOR?S OFFICE, NEW
 TREATMENT ROOM #1,EXISTING KITCHEN
 PULL SIDE, ACCESSIBLE BATHROOM PULL
 SIDE, NEW TREATMENT ROOM #3 PUSH AND
 PULL SIDE.
  
 5.) THE ELEVATION FOR THE TOILET/LAV, P2
 DOES NOT MATCH THE FLOOR PLAN.NOTE
 MINIMUM DISTANCE FROM CENTERLINE OF
 TOILET TO LAV, FBC11 FIGURE 28.
  
 6.) ELEVATION, P2 SIDE WALL, SHOW MAX
 DISTANCE FOR GRAB BAR FROM THE BACK
 WALL, FBC11 FIGURE 29.
  
 7.) NOTE HALLWAY WIDTHS.
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 20:39 Rev Time 0.30
Received By dpalmer Date 2005-09-08 Time 20:37 Sent To  
Notes
2005-09-08 00:00:00REDLINED PANEL SCHEDULE AND PLANS FOR
 CIRCUITING.
 PLEASE SEE 26/28 SHOWS A/C UNIT, HOWEVER
 PLANS INDICATES GEN RECEPTS?
 PLEASE SEE CIRCUITING FO REM/EXT LTS PER
 700.12E, SHALL BE WIRED TO LOCAL
 LIGHTING BRANCH CIRCUIT.
 REDLINED BOTH SETS, PANEL SCHEDULE ON
 PANEL AT FIELD TO BE VERIFIED FOR CODE
 COMPLAINCE AND CORRECT CIRCUITS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-09-04 Cont ID  
Sent By dpalmer Date 2005-09-04 Time 11:48 Rev Time 0.33
Received By dpalmer Date 2005-09-04 Time 11:46 Sent To  
Notes
2005-09-04 00:00:00********* UNSAT ********
  
  
 1)NOTE: PLEASE SEE PLANS HAVE COME BACK
 IN CONTAINING A RAISED SEAL OVER A
 "PHOTO-COPIED "SIGNATURE FOR THE
 ARCHITECT OF RECORD. PLEASE SEE FS
 481.221, FAC 61G1-16.003 WHICH STAES THE
 SIGNATURE OF ARCHITECT MUST BE AN
 ORIGINAL SIGNATURE.
 PLEASE SEE ONE COPY OF PLANS SUBMITTED
 IS BEING RETAINEDAND MAY BE SUBMITTED
 FOR POSSIBLE REVIEW BY STATE BOARD OF
 ARCHITECTS.
  
 2)NOTE: PLEASE RE-CAD PLANS WITH ALL
 INFORMATION AS CHANGED FROM ORIGINAL
 PLANS. PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES PLANS TO BE DONE IN A NEAT A
 DETAILED MANNER FOR LEGIBILITY.
 PLEASE BE SURE ALL CIRCUITING FOR NEW
 DEVICES AND EQUIPMENTIS SHOWN ON PLANS
 AND CORRELATES WITH THE SUBMITTED PANEL
 SCHEDULE.
 PLEASE ALSO REVISE LOAD CALCULATIONS PER
 NEC 220
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-08-18 Cont ID  
Sent By dpalmer Date 2005-08-18 Time 20:53 Rev Time 0.30
Received By dpalmer Date 2005-08-18 Time 20:52 Sent To  
Notes
2005-08-18 00:00:00********* UNSAT ***********
  
 *** PLEASE SEE COMMENTS FROM PREVIOUS
 "PROVISO" WHICH WAS GIVEN IN JUNE 05.
  
  
 1)NOTE: PLEASE SEE 240.4,310.16 FOR MIN
 SEC'S/FEEDERS FOR A 200A SERVICE.
 PLEASE SEE 2/0'S ARE NOT RATED FOR
 200A'S.
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 FOR FEEDERS, OCP, CONDUIT ETC FOR X-RAY
 EQUIPMENT.
 310.16, 240.4, 215.5
  
 3)NOTE: PLEASE SEE FS 481.221 AND FAC
 61G1-16.003 REQUIRES THE SEAL OF
 ARCHITECT TO RAISED, CLEAR AND VISABLE
 WITH ALL INFORMATION AS SET-FORTH ON
 SAID SEAL.
 PLEASE SEE RAISED SEAL IS NOT READABLE.
 PLEASE ALSO SEE FS 481.221 ALSO REQUIRES
 ARCHITECT TO "DATE" PLANS WHEN SIGNING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-06-24 Cont ID  
Sent By dpalmer Date 2005-06-24 Time 10:59 Rev Time 0.30
Received By dpalmer Date 2005-06-24 Time 10:54 Sent To I
Notes
2005-06-24 00:00:00********** PROVISO/REVISION *********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULE FOR NEW X-RAY FEED.
 PLEASE SEE RISER SHOWS 2/0'S AND PANEL
 SCHEDULE SHOWS #4??
 215.5
  
 2)NOTE: PLEASE SEE UPGRADE FOR SERVICE
 TO 200A'S PER 310.16, RISER SHOWS 2/0'S
 AND 3/0'S ARE REQUIRED.
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT REVISION FOR REVIEW AND STAMPING
 BEFORE ROUGH ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 07:46 Rev Time 0.50
Received By dpalmer Date 2005-04-26 Time 07:35 Sent To  
Notes
2005-04-26 00:00:00****** UNSAT 2ND REVIEW ********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 NO, PLEASE SEE RISER
 STILL INDICATED AS EXISTING YET, ALSO
 SHOWS UPGRADE. PLEASE CLARIFY WHAT WORK
 IS BEING DONE TO SERVICE.
 PLEASE SEE MAIN BRKR DISCONNECT IS SHOWN
 FEEDING MLO PANEL AND ALSO SHOWS A TAP ?
 TO NEW 150A DISC?
 215.5,240.21,240.4,310.16 ETC.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE PREVIOUS
 NOTES.
 PLEASE SEE NEW NOTES AT BOTTOM.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE NO
 CIRCUITING SHOWN FOR NEW?
 PLEASE SEE ONLY NOTE ADDED FOR EM LTS.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE A PANEL SCHEDULE WAS
 NOW SUBMITTED, HOWEVER NO LIGHTING IS
 CIRCUITED ON PLANS? NO LIGHTING IN LOAD
 CALCULATIONS ?
 PLEASE ALSO SEE NO LOAD CALCULATIONS
 WERE DONE FOR SERVICE MAIN, TENANT MAIN
 ETC.
 215.5
  
 2)NOTE: PLEASE SEE NEW 150A MAIN DOES
 NOT MEET 110.26 FOR MIN CLEARENCE AS
 SHOWN ON PLANS.
  
 3)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 4)NOTE: PLEASE SEE ELECTRICAL NOTES
 MENTIONS THE SFBC, WE ARE UNDER THE 2001
 FBC.
 PLEASE ALSO SEE NOTE WHICH MENTIOSN
 BROWARD COUNTY,,,,, ETC.
  
 PLEASE SEE SOME OF THE ABOVE ITEMS ARE
 REDLINED ON PLANS AT LOCATIONS OF NOTES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-14 Cont ID  
Sent By dpalmer Date 2005-03-14 Time 08:48 Rev Time 0.50
Received By dpalmer Date 2005-03-14 Time 08:48 Sent To  
Notes
2005-03-14 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE SERVICE NOTE MENTIONS
  
 UPGRADE EXISTING ELECTRICAL RISER.
 PLEASE VERIFY WHAT APPAEARS TO BE A
 "TAP" FROM 200A MAIN DISC WHICH ALREADY
 FEEDS AND EXISTING 200A MLO PANEL.
 240.21
  
 2)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 FOR EXISTING 200A DISCONNECT AND FOR
 EXSITNG 1200A MAIN SERVICE.
 220.3,220.10,220.11,220.13 ETC.
 PLEASE SEE ALL CONTINOUS LOADS TO BE
 SHOWN AT 125%.215.3,230.42 ETC
 215.5
  
 3)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN
 FROM 150A DISCONNETC. #1?
 PLEASE SEE 310.16 75DEGREE COLUMN FOR
 MIN AWG FOR 150A'S.
  
 4)NOTE: PLEASE INCLUDE ALL CIRCUITNG ON
 PLANS FOR NEW AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF ANY EM/EXT LTS WHICH MAY OR MAY NOT
 BE REQUIRED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-07-01 Cont ID  
Sent By mwennerg Date 2005-07-01 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2005-07-01 Time 14:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-05-04 Cont ID  
Sent By mwennerg Date 2005-05-04 Time 15:15 Rev Time 0.00
Received By mwennerg Date 2005-05-04 Time 15:15 Sent To  
Notes
2005-05-04 00:00:001) EXITS SHOWN ON DRAWINGS. IT DOESN'T
 SHOW AN ILLUMINATION SOURCE.
  
 2) EMERGENCY LIGHTING WITH BACK UP
 BATTERY IS REQUIRED WHERE ARTIFICIAL
 LIGHT IS INADEQUATE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-28 Cont ID  
Sent By mwennerg Date 2005-03-28 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2005-03-28 Time 14:26 Sent To  
Notes
2005-03-28 00:00:00DENIED
  
 1) PLEASE BE ADVISED THAT ALL
 CONSTRUCTION, RENOVATION AND DEMOLITION
 SHALL COMPLY WITH NFPA 241.
  
 2) NO EXIT SIGNS OR EMERGENCY LIGHTING
 CAN BE FOUND ON THE PLANS. PLEASE
 INDICATE HOW THE MEANS OF EGRESS WILL BE
 ACCOMPLISHED.
  
 3) PLEASE BE ADVISED THAT 2A-10B-C FIRE
 EXTINGUISHERS MUST BE MOUNTED NOT TO
 EXCEED A TRAVEL DISTANCE OF 75 FEET.
  
 4) PLEASE PROVIDE INFORMATION REGARDING
 THE INTERIOR FINISH CLASSIFICATION OF
 WALLS AND CEILINGS.
  
 5) SEPARATE SHOP DRAWINGS AND PERMIT
 WILL BE REQUIRED FOR THE FIRE ALARM
 REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 11:25 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 11:25 Sent To E
Notes
2005-09-02 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-17 Cont ID  
Sent By adarroug Date 2005-08-17 Time 14:57 Rev Time 0.00
Received By adarroug Date 2005-08-17 Time 14:57 Sent To E
Notes
2005-08-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-21 Time 08:58 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 08:58 Sent To  
Notes
2005-06-24 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 08:32 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 08:32 Sent To  
Notes
2005-04-25 00:00:00TO "COMM" BD#32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-04-04 Cont ID  
Sent By pkrauss Date 2005-04-04 Time 16:15 Rev Time 0.00
Received By pkrauss Date 2005-03-11 Time 15:45 Sent To  
Notes
2005-03-11 00:00:00TO "COMM" BD#41

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-31 Cont ID  
Sent By pkrauss Date 2005-05-31 Time 15:15 Rev Time 0.20
Received By pkrauss Date 2005-05-31 Time 15:15 Sent To  
Notes
2005-05-31 00:00:00PLANS APPROVED 4-4-05 NO CHANGE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-04-04 Cont ID  
Sent By pkrauss Date 2005-04-04 Time 16:12 Rev Time 0.40
Received By pkrauss Date 2005-04-04 Time 16:04 Sent To  
Notes
2005-04-04 00:00:00DENIED:
 PLANS ARE TO DATED BY THE ARCHITECT AS
 PER FS 481.221 & FAC 61G1-16.004.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-05 Cont ID  
Sent By kstevens Date 2005-07-05 Time 07:14 Rev Time 2.00
Received By kstevens Date 2005-07-01 Time 18:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-06-03 Cont ID  
Sent By kstevens Date 2005-06-03 Time 16:22 Rev Time 1.33
Received By kstevens Date 2005-06-03 Time 16:22 Sent To  
Notes
2005-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 2. SHT A2 PROCESSING UNIT MAY REQUIRED A
 NEUTRALIZING TANK. CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE (561) 837-4074,
 OR E-MAIL [email protected]. SUBMIT HIS
 DETERMINATION WORKSHEET WITH PLANS WHEN
 RESUBMITTING PLANS FOR REVIEW.
 5. SHT P1 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 THE CODE REQUIREMENTS. SECTION 104.2.1.
 B. SHOW REQUIRED WATER HAMMER ARRESTORS
 INSTALLED PER PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
 F. AIR CHAMBERS ARE NOT APPROVED.
 SECTION 604.9. - DELETE FROM RISER.
 6. SHT P2 THE FOLLOWING INFORMATION FOR
 THE ACCESSIBLE TOILET ROOM SHALL BE
 SHOWN ON THE DETAIL SHT P2 AND THE FLOOR
 PLAN:
 A. CLEAR FLOOR SPACE 11-4.16.2 - W/C
 B. CLEAR FLOOR SPACE 11-4.19.3 - LAV
 7. ALL DEVICES INTENDED TO SERVE SOME
 SPECIAL FUNCTION SUCH AS PROCESSING, AND
 THAT CONNECT TO THE WATER SUPPLY SYSTEM,
 SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW. SECTION 608.3 - PLEASE
 PROVIDE METHOD OF PROTECTION. SECTION
 104.2.1. - RESPONSE NOTED, BUT PER
 SECTION 608.15.1 OPENINGS AND OUTLETS
 EQUIPPED FOR HOSE CONNECTION SHALL BE
 PROTECTED BY MEANS OTHER THAN AN AIR
 GAP.
 ****************NEW COMMENTS************
 1B. SHT P1 SANT. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENT.
 A. ONLY SHOW FIXTURES THAT WILL BE ON
 THE RISER DIAGRAM.
 B. THE SINK AND PROCESSOR SHALL NOT
 DRAIN THROUGH THE HORIZONTAL WET VENT
 FOR THE BATHROOM FIXTURES. SECTION 909.1
 SEE RED LINE CORRECTIONS FOR THIS ON THE
 RISER DIAGRAM AND THE FLOOR PLAN.
 C. FIXTURE IS MISLABELED. NEW SINK IN
 DARK ROOM LABELED AS EXISTING LAV.
 D. WASH MACHINE IS NOT VENTED AND A
 CLEANOUT 4' ABOVE THE FLOOR IS REQUIRED
 AT WASH MACHINE.
 2B. SHT P1 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
 A. INDICATE WHERE THE HOT AND COLD
 WATER LINES PAST THE LAST FIXTURES TO
 THE LEFT AND RIGHT ARE CONNECTING TO?
 SECTION 104.2.1.
 B. THE WATER CLOSET IS NOT SHOWN ON THE
 RISER DIAGRAM.
 C. NEW SINK IN DARK ROOM LABELED AS
 EXISTING LAV.
 D. DELETE ALL AIR CHAMBERS, AND SHOW
 WATER HAMMER ARRESTORS AT WASH MACHINE
 AS REQUIRED IN SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-23 Cont ID  
Sent By kstevens Date 2005-03-23 Time 07:31 Rev Time 2.00
Received By kstevens Date 2005-03-22 Time 18:55 Sent To  
Notes
2005-03-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1) SHT A2 ALTERED PORTIONS OF EXISTING
 BUILDINGS AND FACILITIES REQUIRED TO BE
 ACCESSIBLE BY 11-4.1.6 SHALL COMPLY WITH
 11-4.1 THROUGH 11-4.35. SECTION
 11-4.1.1(1)(A).- IF EXISTING ELEMENTS
 , SPACES, OR COMMON AREAS ARE ALTERED,
 THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF 11-4.1.1 TO
 11-4.1.3 MINIMUM REQUIREMENTS FOR NEW
 CONSTRUCTION. - THE "NEW DARKROOM" HAS A
 WATER CLOSET AND "LAV" IN IT AND IS
 STILL CONSIDERED A TOILET ROOM AND SHALL
 BE ACCESSIBLE.
 2) SHT A2 PROCESSING UNIT MAY REQUIRE A
 NEUTRALIZING TANK. CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE (561) 837-4074
 OR E-MAIL [email protected]. SUBMIT HIS
 DETERMINATION WORKSHEET WITH PLANS WHEN
 RESUBMITTING PLANS FOR REVIEW.
 3) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1.
 4) SHT P1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS: SEC 104.2.1.
 A) THE WASH MACHINE IS NOT SHOWN ON THE
 SANT. RISER.
 B) SHOW ALL PIPE SIZES
 C) FLOOR PLANS INDICATES A P-TRAP AND
 STANDPIPE FOR THE PROCESSOR THATS NOT
 SHOWN ON THE RISER DIAGRAM.
 5) SHT P1 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 THE CODE REQUIREMENTS: SECTION 104.2.1.
 A) SHOW ALL PIPE SIZES
 B) SHOW REQUIRED WATER HAMMER ARRESTORS
 INSTALLED PER PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING.
 C) FULL OPEN VALVES ARE REQUIRED ON ALL
 WATER DOWN-FEED PIPES. 606.1(4)
 D) IDENTIFY ALL FIXTURES ON THE RISER,
 AND SHOW THE WASH MACHINE AND ALL
 EXISTING FIXTURES.
 E) SHOW ALL REQUIRED VALVES
 F) AIR CHAMBERS ARE NOT APPROVED.
 SECTION 604.9
 6) SHT P2 THE FOLLOWING INFORMATION FOR
 THE ACCESSIBLE TOILET ROOM SHALL BE
 SHOWN ON THE DETAIL SHT P2 AND THE FLOOR
 PLAN:
 A) CLEAR FLOOR SPACE 11-4.16.2 - W/C
 B) CLEAR FLOOR SPACE 11-4.19.3 - LAV
 C) EXPOSED PIPES & SURFACES 11-4.19.6
 D) A 5' TURNING AREA REQUIRED IN EACH
 TOILET ROOM. 11-4.22.3
 7) ALL DEVICES INTENDED TO SERVE SOME
 SPECIAL FUNCTION SUCH AS PROCESSING, AND
 THAT CONNECT TO THE WATER SUPPLY SYSTEM,
 SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW. SECTION 608.3. -
 PLEASE PROVIDE METHOD OF PROTECTION.
 SECTION 104.2.1.
 8) PROVIDE DETAIL FOR KITCHEN SINK
 ACCESSIBLITY. SHOW THE FOLLOWING
 INFORMATION:
 A) HEIGHT 11-4.24.2
 B) KNEE CLEARANCE 11-4.24.3
 C) SINK DEPTH 11-4.24.4
 D) CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 PROVIDED TO ALLOW FORWARD APPROACH, AND
 SHALL EXTEND A MAXIMUM 19" UNDERNEATH
 THE SINK.
 E) EXPOSED PIPES & SURFACES 11-4.24.6
 F) FAUCETS 11-4.24.7
 G) SHOW TURNING AREA IN KITCHEN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]