Plan Review Details - Permit 05030422
Plan Review Stops For Permit 05030422
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-05-26 Cont ID  
Sent By mwennerg Date 2005-05-26 Time 09:38 Rev Time 0.00
Received By mwennerg Date 2005-05-26 Time 09:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-26 Cont ID  
Sent By mwennerg Date 2005-05-26 Time 09:38 Rev Time 0.00
Received By mwennerg Date 2005-05-26 Time 09:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-16 Cont ID  
Sent By mwennerg Date 2005-03-16 Time 16:04 Rev Time 0.00
Received By mwennerg Date 2005-03-16 Time 16:04 Sent To  
Notes
2005-03-16 00:00:001) THE SAFETY MARGIN IS BELOW 5 PSI. PER
 THE CITY OF WEST PALM BEACH FIRE
 MARSHAL'S OFFICE, THE SAFETY MARGIN MUST
 BE 5 PSI OR GREATER.
  
 2) PLEASE SHOW THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION AND IT'S DISTANCE
 TO THE CLOSEST FIRE HYDRANT. THAT
 DISTANCE CAN BE NO FURTHER THAN 150'.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 10:27 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 10:27 Sent To FIRE
Notes
2005-03-08 00:00:00TO "F" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-05-26 Cont ID  
Sent By mwennerg Date 2005-05-26 Time 09:38 Rev Time 0.00
Received By mwennerg Date 2005-05-26 Time 09:38 Sent To  
Notes
***NONE***