Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2005-04-04 Cont ID  
Sent By lsmith Date 2005-04-04 Time 11:01 Rev Time 0.00
Received By lsmith Date 2005-04-04 Time 11:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-19 Cont ID  
Sent By btrobaug Date 2005-04-19 Time 11:42 Rev Time 0.50
Received By btrobaug Date 2005-04-19 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-21 Cont ID  
Sent By btrobaug Date 2005-03-21 Time 10:19 Rev Time 0.50
Received By btrobaug Date 2005-03-18 Time 16:21 Sent To M
Notes
2005-03-21 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} VERIFY THAT THE TRANSFER SWITCH
 (PANEL), AND DISCONNECT SUPPLIED BY THE
 MANUFACTURER IS SERVICE RATED PER
 230.66. IT HAS BEEN THE EXPERIENCE OF
 THIS DEPARTMENT THAT THEY ARE NOT.
  
 2} THE LOAD SELECTED TO BE SERVED BY THE
 GENERATOR MUST HAVE A DEMAND (AT 100%
 PER 702.5)EQUAL TO OR LESS THAN THE
 STATED GENERATOR OUTPUT.
 GIVE A CALCULATION FOR THE CIRCUITS TO
 BE SERVED AND INDICATE SAME ON A PANEL
 SCHEDULE FOR PANEL BEING INSTALLED.
  
 3} INDICATE THE PRIME MOVER FOR THE
 GENERATOR. IF GAS INDICATE LP. OR
 NATURAL.PLEASE NOTE A SEPERATE PERMIT IS
 REQUIRED FOR GAS.
  
 4} THE VALUE ON THE PERMIT APPLICATION
 MUST REFLECT THE COST OF ALL MATERIAL
 AND LABOR FOR THE WORK DESCRIBED,
 INCLUDING THE GENERATOR AND RELATED
 EQUIPMENT, EVEN IF OWNER SUPPLIED.
 UNLESS THAT COST WAS INCLUDED ON ANOTHER
 PERMIT IN WHICH CASE PLEASE INDICATE
 THAT PERMIT NUMBER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-03-11 Cont ID  
Sent By btrobaug Date 2005-03-11 Time 11:44 Rev Time 0.25
Received By btrobaug Date 2005-03-11 Time 11:44 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-16 Cont ID  
Sent By adarroug Date 2005-03-16 Time 11:42 Rev Time 0.00
Received By adarroug Date 2005-03-16 Time 11:42 Sent To E
Notes
2005-03-16 00:00:00TO "BT" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 09:54 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 09:54 Sent To E
Notes
2005-03-08 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-03-29 Cont ID  
Sent By pkrauss Date 2005-03-29 Time 15:53 Rev Time 0.20
Received By pkrauss Date 2005-03-29 Time 15:53 Sent To P
Notes
2005-03-29 00:00:00PROVISO:
 GENERATOR EXHAUST SHALL BEINSTALLED AS
 NOT TO BE READILY DRAWN INTO THE
 BUILDING.(10 FT FROM WINDOWS, DOORS OR
 FRESH AIR INTAKE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-04-02 Cont ID  
Sent By kstevens Date 2005-04-02 Time 05:03 Rev Time 0.25
Received By kstevens Date 2005-04-02 Time 05:03 Sent To B
Notes
2005-04-02 00:00:00GAS APPLICATION APPLIED FOR 3/17/5 SENT
 TO BUILDING FOR SLAB, RESTRAINT REVIEW

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-15 Cont ID  
Sent By mmclean Date 2005-03-15 Time 16:33 Rev Time 0.00
Received By mmclean Date 2005-03-15 Time 16:33 Sent To I
Notes
***NONE***