Plan Review Details - Permit 05030175
Plan Review Stops For Permit 05030175
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-08 Cont ID  
Sent By jwitmer Date 2005-04-08 Time 15:33 Rev Time 2.20
Received By jwitmer Date 2005-04-08 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By jwitmer Date 2005-03-21 Time 09:30 Rev Time 1.10
Received By jwitmer Date 2005-03-21 Time 09:30 Sent To  
Notes
2005-03-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030175
 ADD: 222 LAKEVIEW AVE #1160
 CONT:HEDRICK BROTHERS
 TEL: (561)689-8880
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 4) PLANS DO NOT INDICATE THE CORRIDOR
 RATING NOR THE RATING OF THE ENTRY
 DOORS. TABLE 705.1.2.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 12:43 Rev Time 30.00
Received By dpalmer Date 2005-06-15 Time 12:41 Sent To FIRE
Notes
2005-06-15 00:00:00REDLINED MISSING EQUIPMENT GROUNDING
 CONDUCTORS REQUIRED.
 250.110,250.24,250.122 ETC.
  
 THIS WAS REDLINED ON PREVIOUS PLANS
 ALSO.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 19:37 Rev Time 0.30
Received By dpalmer Date 2005-04-11 Time 19:31 Sent To  
Notes
2005-04-11 00:00:00*** REDLINE DMISSING EQUIPMENT GROUNDING
 CONDUCTORS.
 RESPONSELTR MENTIONS "SHOWN" , HOWEVER
 THESE COULD NOT BE LOCATED.
 250.30,250.86,250,110,250.122 ETC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-07 Cont ID  
Sent By dpalmer Date 2005-03-07 Time 16:37 Rev Time 0.75
Received By dpalmer Date 2005-03-07 Time 16:37 Sent To  
Notes
2005-03-07 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE SEE EACH SET SUBMITTED.
 ONE SET CONTAINS E1 OF 2 AND 2 OF 2, THE
 OTHER SET CONTAINS TWOE1 OF 2 SHEETS.
  
 2)NOTE: PLEASE CORRELATE LABELING OF
 PANELS ON PANEL SCHEDULES AND RISER.
 HP, LP, H OR L?
 215.5
  
 3)NOTE: PLEASE SEE THERE ARE NO
 CONDUCTORS SHOWN FROM PANEL H TO
 TRANSFORMER TO PANEL L.
 310.16, 215.5
  
 4)NOTEP: PLEASE INCLUDE EQUIPMENT
 GROUNDING METHODS FOR ALL EQUIPMENT/
 CONDUITS.
 250.110/ 250.122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-06-28 Cont ID  
Sent By mwennerg Date 2005-06-28 Time 09:41 Rev Time 0.00
Received By mwennerg Date 2005-06-28 Time 09:41 Sent To  
Notes
2005-06-28 00:00:00REVISION DATED 6/9/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-06-16 Cont ID  
Sent By mwennerg Date 2005-06-16 Time 11:22 Rev Time 0.00
Received By mwennerg Date 2005-06-16 Time 11:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-28 Cont ID  
Sent By mwennerg Date 2005-03-28 Time 12:58 Rev Time 0.00
Received By mwennerg Date 2005-03-28 Time 12:58 Sent To  
Notes
2005-03-28 00:00:00PASSED-
  
 1) PLEASE BE ADVISED THAT NEW DUCT SMOKE
 DETECTOR INSTALLATIONS SHALL BE WIRED
 INTO THE FIRE ALARM SYSTEM SO THAT IN
 ADDITION TO FAN SHUT DOWN, ACTIVATION
 WILL CAUSE A GENERAL FIRE ALARM.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 14:32 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 14:32 Sent To P
Notes
2005-06-23 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 11:06 Rev Time 0.00
Received By shill Date 2005-06-10 Time 11:06 Sent To E
Notes
2005-06-10 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-09 Cont ID  
Sent By mjacobs Date 2005-06-09 Time 16:30 Rev Time 0.00
Received By mjacobs Date 2005-06-09 Time 16:30 Sent To M
Notes
2005-06-09 00:00:00TO 'M/AC' BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 09:49 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 09:49 Sent To  
Notes
2005-04-06 00:00:00TO "COMM" BD#31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-29 Cont ID  
Sent By pkrauss Date 2005-03-29 Time 13:06 Rev Time 0.00
Received By pkrauss Date 2005-03-03 Time 14:23 Sent To  
Notes
2005-03-03 00:00:00TO "COMM" BD#23

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-03-29 Cont ID  
Sent By pkrauss Date 2005-03-29 Time 13:02 Rev Time 0.45
Received By pkrauss Date 2005-03-29 Time 13:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-06 Cont ID  
Sent By kstevens Date 2005-07-06 Time 10:32 Rev Time 0.55
Received By kstevens Date 2005-07-06 Time 10:32 Sent To  
Notes
2005-07-06 00:00:00REVISION OK - CHANGED PUMP MANUF., AND
 INSTA-HOT MODEL - SHT P-1

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-04-18 Cont ID  
Sent By kstevens Date 2005-04-18 Time 18:43 Rev Time 0.75
Received By kstevens Date 2005-04-18 Time 18:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By kstevens Date 2005-03-21 Time 07:30 Rev Time 1.00
Received By kstevens Date 2005-03-21 Time 07:30 Sent To  
Notes
2005-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A1 DETAIL #6 FOLLOWING
 INFORMATION IS REQUIRED ON DETAIL:
 A) KNEE CLEARANCE 11-4.24.3 (HEIGHT)
 B) CLEAR FLOOR SPACE 11-4.24.5FORWARD
 APPROACH REQUIRED, MAX. 19" UNDERNEATH
 THE SINK. - PER BUILDING OFFICIAL, NO
 DOORS IN CLEAR FLOOR SPACE UNDER SINK.
 C) EXPOSED PIPES AND SURFACES 11-4.24.6
  
 2) PLEASE INDICATE IF DRINKING FOUNTAINS
 ARE AVAILABLE IN THE COMMON AREAS OF THE
 BUILDING.
  
 3) A FULL OPEN VALVE IS REQUIRED ON ALL
 WATER DOWN-FEED LINES. SECTION 606.1(4)
  
 4) SHOW WATER HAMMER ARRESTOR REQUIRED
 BY SECTION 604.9 ON WATER RISER DIAGRAM.
 SECTION 104.2.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  