Plan Review Details - Permit 05030144
Plan Review Stops For Permit 05030144
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By jwitmer Date 2005-03-21 Time 08:37 Rev Time 0.77
Received By jwitmer Date 2005-03-21 Time 08:37 Sent To  
Notes
2005-03-21 00:00:00BUILDING PLAN REVIEW
 PERMIT:05030144
 ADD:950 EVERNIA STREET
 CONT:COMPLETE PROPERTY MANAGEMENT
 TEL:(561)252-8372
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-07 Cont ID  
Sent By dpalmer Date 2005-03-07 Time 14:44 Rev Time 0.30
Received By dpalmer Date 2005-03-07 Time 14:44 Sent To  
Notes
2005-03-07 00:00:00***UNSAT ***
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
 215.5
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF ANY EM/EXT LTS.
  
 2)NOTE: PLEASE SHOW NEW OR EXSITNG SIGN
 CIRCUIT REQUIRED UNDER 600.5
  
 3)NOTE: PLEASE PROVIDE OCCUPANCY/LOAD
 FOR NEW ELECTRICAL ON EXISTING PANEL
 SHOWN.
 215.5,220
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY OR MAY NOT
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-28 Cont ID  
Sent By mwennerg Date 2005-03-28 Time 10:21 Rev Time 0.00
Received By mwennerg Date 2005-03-28 Time 10:21 Sent To  
Notes
2005-03-28 00:00:001) PLEASE BE ADVISED THAT SEPARATE SHOP
 DRAWINGS AND PERMITS WILL BE REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-29 Cont ID  
Sent By pkrauss Date 2005-03-29 Time 08:39 Rev Time 0.00
Received By pkrauss Date 2005-03-04 Time 13:33 Sent To  
Notes
2005-03-04 00:00:00TO "COMM" BD#22

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-03-29 Cont ID  
Sent By pkrauss Date 2005-03-29 Time 08:39 Rev Time 0.40
Received By pkrauss Date 2005-03-29 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By kstevens Date 2005-03-21 Time 06:42 Rev Time 0.50
Received By kstevens Date 2005-03-21 Time 06:42 Sent To  
Notes
2005-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) AS REQUIRED BY 104.3.1.1 OF THE CODE,
 TWO OR MORE SETS OF DRAWINGS SHAL
 ACCOMPANY THE APPLICATION FOR A PERMIT.
 SECTION 104.2.1. - PLANS SHALL BE
 SUBMITTED IN SETS, NOT LOOSE SHEETS.
 2) INDICATE FLUSH CONTROLS FOR W/C PER
 SECTION 11-4.16.5. SHT A-1
 3) SHOW COMPLIANCE WITH 11-4.19.7,
 FAUCETS FOR THE LAV. SHT A-1
 4) SUBMIT SANITARY AND WATER RISER
 DIAGRAMS. SHOW PIPE SIZE, VENTING AND
 POINT OF CONNECTION FOR THE SANT., AND
 SHOW PIPE SIZE, VALVES, LOCATION OF
 WATER HAMMER ARRESTORS, (IF INSTALLED
 PER PDI-WH 201), AND POINT OF
 CONNECTION. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  