Plan Review Details - Permit 05030116
Plan Review Stops For Permit 05030116
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-15 Cont ID  
Sent By btrobaug Date 2005-03-08 Time 13:17 Rev Time 0.50
Received By btrobaug Date 2005-03-08 Time 13:09 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 11:29 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 11:29 Sent To M
Notes
2005-03-10 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 14:38 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 14:38 Sent To E
Notes
2005-03-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-03 Cont ID  
Sent By mjacobs Date 2005-03-03 Time 10:23 Rev Time 0.00
Received By mjacobs Date 2005-03-03 Time 10:23 Sent To Z
Notes
2005-03-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By btrobaug Date 2005-03-15 Time 08:06 Rev Time 0.30
Received By pkrauss Date 2005-03-15 Time 07:41 Sent To E
Notes
2005-03-15 00:00:00GAS PERMIT - 04090812
 PLANS RESUBMITTED INDICATE NO WINDOWS ON
 THE WALL WHERE THE GENERATOR IS TO BE
 INSTALLED & IS 3FT OFF THE EXTERIOR WALL
 PER THE MANUFACTURER'S SPECIFICATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-08 Cont ID  
Sent By pkrauss Date 2005-03-08 Time 13:41 Rev Time 0.35
Received By pkrauss Date 2005-03-08 Time 13:40 Sent To  
Notes
2005-03-08 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.INDICATE NATURAL GAS OR LP GAS.
 2.ADDITIONAL PERMIT REQUIRED FOR GAS
 3.LP GAS - PROVIDE TANK CAPACITY AND
 LOCATION.
 4.SITE PLAN SUBMITTED INDICATES
 GENERATOR AGAINST THE HOUSE.PLEASE
 PROVIDE CLEARANCES.THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS RECOMMEDS 5 FT
 CLEARNANCE.
 5.INDICATE DISTANCE FROM PROPERTY LINE
 AND WINDOWS, DOORS, AND FRESH AIR
 INTAKES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2005-03-08 Cont ID  
Sent By mmclean Date 2005-03-08 Time 12:55 Rev Time 0.00
Received By mmclean Date 2005-03-08 Time 12:55 Sent To E
Notes
2005-03-08 00:00:00PLANS NOW SHOW GENERATOR 5FT FROM
 PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-07 Cont ID  
Sent By mmclean Date 2005-03-07 Time 11:27 Rev Time 0.00
Received By mmclean Date 2005-03-07 Time 11:27 Sent To I
Notes
2005-03-07 00:00:00DENIED,
 1. MUST PROVIDE SIDE SETBACK OF
 GENERATOR FROM PROPERTY LINE. CALLED
 CONTRACTOR
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERIVCES
 805-6720