Plan Review Details - Permit 05030113
Plan Review Stops For Permit 05030113
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-08 Cont ID  
Sent By btrobaug Date 2005-03-08 Time 12:07 Rev Time 0.50
Received By btrobaug Date 2005-03-08 Time 11:39 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 16:22 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 16:22 Sent To M
Notes
2005-03-17 00:00:00TO "PKRAUSS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 13:26 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 13:26 Sent To Z
Notes
2005-03-10 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 14:36 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 14:36 Sent To E
Notes
2005-03-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-03-03 Cont ID  
Sent By mjacobs Date 2005-03-03 Time 10:20 Rev Time 0.00
Received By mjacobs Date 2005-03-03 Time 10:20 Sent To Z
Notes
2005-03-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-05 Cont ID  
Sent By pkrauss Date 2005-04-05 Time 06:47 Rev Time 0.20
Received By pkrauss Date 2005-04-05 Time 06:45 Sent To  
Notes
2005-04-05 00:00:00GAS PERMIT #04110415, REVISION 1 ADDS
 GENERATOR TO GAS PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-08 Cont ID  
Sent By pkrauss Date 2005-03-08 Time 13:01 Rev Time 0.45
Received By pkrauss Date 2005-03-08 Time 13:01 Sent To P
Notes
2005-03-08 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.INDICATE FUEL SYSTEM INTENDED, GAS
 OR LP.
 2.LP GAS - INDICATE TANK CAPACITY AND
 LOCATION.
 3.INDICATE DISTANCE FROM WINDOWS.
 4.PLEASE NOTE INSTALLATION
 INSTRUCTIONS FOR THE RECOMMENDED
 CLEARANCE AROUND THE GENERATOR.THE
 SITE PLAN INDICATES THE GENERATOR
 AGAINST THE HOUSE.
 5. ADDITIONAL PERMIT REQUIRED FOR GAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2005-03-16 Cont ID  
Sent By mmclean Date 2005-03-16 Time 10:20 Rev Time 0.00
Received By mmclean Date 2005-03-16 Time 10:20 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-07 Cont ID  
Sent By mmclean Date 2005-03-07 Time 11:30 Rev Time 0.00
Received By mmclean Date 2005-03-07 Time 11:30 Sent To I
Notes
2005-03-07 00:00:00DENIED,
 1. MUST PROVIDE SIDE SETBACK FOR
 GENERATOR FROM PROPERTY LINE. CALLED
 CONTRACTOR
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICES.
 805-6720