2005-03-03 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05021224 |
| ADD: 1300 S DIXIE HWY |
| CONT:RAPP CONSTRUCTION |
| TEL: (561)248-6411 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)PROVIDE NOC RECORDED WITH THE CLERK OF |
| COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) SEE ELECTRICAL COMMENTS AS ENGINEERS |
| FULL SIGNATURE, 471.025.PLANS, |
| SPECIFICATIONS,REPORTS OR OTHER |
| DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| |
| 3) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| PLANS INDICATE WORK TO BE ACCOMPLISHED |
| UNDER THIS PERMIT " SECOND FLOOR |
| GRAPHICS HALL" BUT SHEET A-4.1.1 |
| INDICATES WORK ON THE FIRST FLOOR BACK |
| STAGE COORIDOR 126 AND STORAGE AREA, IS |
| THERE WORK TO BE COMPLETED UNDER THIS |
| PERMIT OR ELSEWHERE ON THE FIRST FLOOR? |
| |
| 4) PLANS (A-321) INDICATE WORK IN |
| HALLWAY # 204, SEE SECTION 1021.4 DOORS |
| SWINGING INTO A CORRIDOR SHALL BE |
| RECESSED TO PREVENT INTERFERENCE WITH |
| CORRIDOR TRAFFIC OR SWING OPEN 180 |
| DEGREES. DOORS IN ANY POPSITION SHALL |
| NOT REDUCE THE CORRIDOR WIDTH BY MORE |
| THAN ONE HALF. |
| |
| 5A) A-2.2.3 NOTE# 7 REFERS TO LIFE |
| SAFETY PLAN FOR LOCATION AND DETAILS OF |
| 1-HR RATED CEILING ABOVE 2X2 ACT |
| CEILING, CAN NOT FIND THE LIFE SAFETY |
| PLAN REFRENCED. |
| 5B) DIRECTLY BELOW THIS NOTE IS A |
| DESIGNATION FOR A 1 HR RATED WALL, WALL |
| IS NOT SHOWN ON PLANS. |
| |
| 6) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| PLANS DO NOT INDICATE THE MINIMUM BLDG |
| TYPE OR IF 1HR PROTECTED OR FIRE |
| SPRINKLERED? |
| |
| 7)1005.4 EMERGENCY ESCAPE AND RESCUE |
| OPENINGS, (2) EVERY ROOM OR SPACE |
| GREATER THAN 250 FT USED FOR CLASSROOM |
| OR OTHER ED- UCATIONAL PURPOSES OR |
| NORMALLY SUBJECT TO STUDENT OCCUPANCY, |
| AND EVERY ROOM SUBJECT TO CLIENT |
| OCCUPNCY SHALL NOT HAVE NOT LESS THAN |
| ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE, |
| SEE EXCEPTIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |