Plan Review Stops For Permit 05021036 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2005-07-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-22 |
Time |
11:24 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2005-07-22 |
Time |
11:24 |
Sent To |
Z |
|
Notes |
2005-07-23 00:00:00 | SEPARATE PERMIT FOR SHUTTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2005-07-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-21 |
Time |
12:05 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2005-07-21 |
Time |
12:05 |
Sent To |
Z |
|
Notes |
2005-07-21 00:00:00 | ****CORRECTIONS*** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | AND THE RECEIPT ATTACHED TO THE | | APPLICATION.233-5025 | | | | 2.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | | | ROUTED TO ZONING (NO ZONING STAMP ON | | SURVEY/SITE PLAN). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-06-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-22 |
Time |
10:23 |
Rev Time |
0.50 |
Received By |
shill |
Date |
2005-06-22 |
Time |
10:23 |
Sent To |
PC |
|
Notes |
2005-06-22 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | NOTE - CHANGED PLAN TO BE ISSUED FROM | | MASTER #04031090 | | | | 1.)SHEET 5.1 DOES NOT MATCH THE PLANS | | SUBMITTED. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-04-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-04-05 |
Time |
15:54 |
Rev Time |
4.00 |
Received By |
shill |
Date |
2005-04-05 |
Time |
11:46 |
Sent To |
PC |
|
Notes |
2005-04-05 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED, FS713.13. | | | | 2.) IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | AND THE RECEIPT ATTACHED TO THE | | APPLICATION.561-233-5025 | | | | 3.) NAILING FOR ROOF SHEATHING, 1-A6 AND | | BB-A3 (6 IN OC) IS NOT COMPLIANT FOR | | ZONE 3, FBC*TABLE 2306.1. | | | | 4.) ADDITIONAL FEES DUE TO VALUE | | ADJUSTMENT.1888SF X 76.96, 513 X 41.6, | | TOTAL OF 166640.SEE ATTACHED. | | | | 5.) WINDOW/DOOR BUCK DETAIL, A6, SHOWS | | ATTACHMENT INTO WOOD FRAMING. OTHER | | DETAILS SHOW THE CONSTRUCTION AS CBS. | | | | 6.) SPECIFY WINDOW AND DOOR SIZES. | | BEDROOM WINDOWS ARE TO COMPLY WITH | | EMERGENCY EGRESS REQUIREMENTS, | | FBC1005.4. | | | | 7.) SIGN THE OWNER/AGENT LINE OF THE | | ENERGY CALC. | | | | 8.) PROVIDE REACTION LOADS, ROOF FRAMING | | PLAN. | | | | 9.) DOOR 2 BETWEEN LAUNDRY ROOM AND | | GARAGE IS TO BE SOLID CORE, | | FBC?13-403.1.ABCD. | | | | 10.) BB-A3 REFERS TO TRUSS PLAN FOR | | GIRDER DETAIL.THIS WAS NOT PROVIDED. | | NO CONNECTORS OR REACTION LOADS | | SPECIFIED FOR GIRDER CONNECTIONS. | | | | 11.) AA-A3, PORCH DETAILS, REFERS TO | | MECHANICAL PAGE. | | | | 12.) FLORIDA STATE PRODUCT APPROVAL DOES | | NOT APPEAR TO MATCH THE NOA PROVIDED. | | PROVIDE FLORIDA STATE PRODUCT APPROVAL | | AND CIRCLE WHICH PRODUCT YOU ARE USING | | | | 13.) THE SAME DATA SHEETS WERE PROVIDED | | FOR FL18 AND FL19.I CANNOT DETERMINE | | COMPLIANCE WITH FAC9B72. | | | | 14.) THE TWO SPEC SHEETS SUBMITTED FOR | | DOORS ARE FOR SINGLE DOORS.THE GLAZED | | DOORS ON THE PLAN ARE DOUBLE DOORS. | | | | 15.) THE PLAN SHOWS A PANEL DOOR FOR THE | | FRONT DOOR.THIS SERVES AS THE | | EMERGENCY MEANS OF ESCAPE FBC1005.4.5. | | IF THIS DOOR IS TO BE GLAZED, CHANGE THE | | PANEL DOOR NOTE ON THE PLAN AND INDICATE | | THE EMERGENCY MEANS OF ESCAPE. | | | | 16.) PRODUCT APPROVALS ALSO REQUIRED | | FOR: | | ROOF TILE | | SHUTTERS | | SINGLE HUNG WINDOWS | | OPAQUE DOOR | | | | PRODUCT APPROVALS NOT APPROVED PRIOR TO | | ISSUANCE WILL REQUIRE SEPARATE PERMITS | | FOR THOSE ITEMS. | | | | 17.) COMPLETE A HURRICANE SHUTTER | | INSTALLATION SCHEDULE, SEE ATTACHED. | | | | 18.) THIS PROPERTY IS IN THE FIRE | | DISTRICT.DECLARE A BUILDING TYPE | | FBC600.TYPE VI CONSTRUCTION NOT | | ALLOWED IN THE FIRE DISTRICT, FBC*102.1. | | | | 19.) SHOW COMPLIANCE WITH FBC TABLE 600 | | IN REGARDS TO FIRE RESISTANCE FOR | | EXTERIOR BEARING WALLS. | | | | 20.) PROVIDE DESIGN CRITERIA FOR THE | | TRUSSES, TCLL, TCDL, BCLL, BCDL.BCLL | | TO COMPLY WITH FBC TABLE 1604.1. | | | | 21.)SHOW ATTIC ACCESS LOCATION AND | | SIZE, FBC2309.6, 2309.7. | | | | 22.)32" CLEAR OPENING REQUIRED FOR THE | | FRONT DOOR, FBC TABLE 1004. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2005-07-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-21 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-07-21 |
Time |
13:35 |
Sent To |
|
|
Notes |
2005-07-21 00:00:00 | SEE MASTER |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2005-06-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-02 |
Time |
13:46 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-06-02 |
Time |
12:56 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-03-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-03-18 |
Time |
12:09 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-03-18 |
Time |
11:03 |
Sent To |
M |
|
Notes |
2005-03-18 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} COMPLETE THE RISER DIAGRAM. SHOW | | CONDUIT SIZES AND THE GROUNDING | | ELECTRODE SYSTEM CONNECTIONS PER 250.50. | | | | 2} PROVIDE LOAD CALCS AND PANEL | | SCHEDULES PER 215.5. | | | | 3} SHOW FAULT CURRENT CALC AND INDICATE | | THE AIC RATING OF THE EQUIPMENT, 110.9. | | | | 4} LOCATE OUTDOOR RECEPTACLE'S PER | | 210.52(E). | | | | 5} KITCHEN COUNTERTOP RECEPTACLE SPACING | | MUST COMPLY WITH 210.52(C). | | | | 6} SHOW SMOKE DETECTOR LOCATIONS PER | | 905.2.2 FBC & 8-1.4.1.6.2. NFPA-72. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2005-07-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-13 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-13 |
Time |
10:26 |
Sent To |
M |
|
Notes |
2005-07-13 00:00:00 | TO "M" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2005-07-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-07 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-07 |
Time |
09:47 |
Sent To |
M |
|
Notes |
2005-07-07 00:00:00 | TO "PKRAUSS" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2005-06-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-17 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-17 |
Time |
08:10 |
Sent To |
B |
|
Notes |
2005-06-17 00:00:00 | TO SH DESK | | | | CHANGED TO BE ISSUED FROM MASTER PLAN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2005-06-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-09 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-09 |
Time |
15:52 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-05-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-26 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-26 |
Time |
09:06 |
Sent To |
E |
|
Notes |
2005-05-26 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-03-16 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-03-16 |
Time |
11:46 |
Sent To |
E |
|
Notes |
2005-03-16 00:00:00 | TO "SFR""E" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-03-14 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-03-15 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-03-14 |
Time |
15:06 |
Sent To |
Z |
|
Notes |
2005-03-14 00:00:00 | TO "Z" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-02-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-04-05 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-02-17 |
Time |
13:50 |
Sent To |
PC |
|
Notes |
2005-02-17 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
N |
Date |
2005-07-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-21 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-07-21 |
Time |
13:36 |
Sent To |
|
|
Notes |
2005-07-21 00:00:00 | SEE MASTER |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2005-07-16 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2005-07-16 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-07-16 |
Time |
11:42 |
Sent To |
P |
|
Notes |
2005-07-16 00:00:00 | PLAN DENIED | | 1) PLEASE PROVIDE TWO SETS OF ENERGY | | CALCULATIONS AND MANUAL J. | | 2) RETURN AIR CANS IN THE BEDROOMS ARE | | TO SMALL FOR THE RETURN AIR DUCT. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2005-03-22 |
Time |
|
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-03-22 |
Time |
17:19 |
Sent To |
B |
|
Notes |
2005-03-22 00:00:00 | PLAN DENIED | | 1) INDICATE SIZE OF RETURN DUCT OFF THE | | RETURN AIRPLENUM. | | 2) REFER TO SECTION 601.4 # 3 2001 | | FLORIDA BUILDING CODE MECHANICAL | | PLAN REVIEW BY HAROLD MOSER | | (561)805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2005-07-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-21 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-07-21 |
Time |
13:36 |
Sent To |
|
|
Notes |
2005-07-21 00:00:00 | SEE MASTER |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-03-22 |
|
|
Cont ID |
|
Sent By |
gsalfeld |
Date |
2005-03-22 |
Time |
14:43 |
Rev Time |
1.00 |
Received By |
gsalfeld |
Date |
2005-03-22 |
Time |
14:43 |
Sent To |
B |
|
Notes |
2005-03-22 00:00:00 | 3/22/05- | | 1-SHEET A-1 SANITARY RISER DIAGRAM | | DOES NOT REFLECT THE FLOOR PLAN,NOR | | DOES IT MEET CODE REQUIREMENTS. | | 2-RISER DIAGRAM MUST BE IN ISOMETRIC | | FORM | | AND MATCH THE INSTALLATION OF | | PLUMBING,SEE FBC 2001 | | 104.2.1-REQUIREMENTS |
|
|
Review Stop |
S |
SIGNS |
Rev No |
1 |
Status |
P |
Date |
2005-03-15 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-03-15 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-03-15 |
Time |
16:13 |
Sent To |
I |
|
Notes |
2005-06-16 00:00:00 | PLEASE NOTE THAT THE STOP FOR THIS | | PERMIT SHOWS (S) INSTEAD OF (Z) ERROR. | 2005-03-15 00:00:00 | APPROVED BY SHIRLEY GRAHAM, ASSOC. | | PLANNER 822-1458 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2005-07-22 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-07-22 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-07-22 |
Time |
16:21 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2005-06-16 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-06-16 |
Time |
18:48 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-06-16 |
Time |
18:48 |
Sent To |
I |
|
Notes |
2005-06-16 00:00:00 | DENIED. | | 1. NEED TO REDUCE DRIVEWAY/WALKWAY TO | | MEET THE ZONING REQUIRMENTS. | | 2. MUST PROVIDE THE WIDTH & LENGTH OF | | DRIVEWAY/WALKWAY. | | **MUST HAVE 1000SQ FT OR 75% OF | | LANDSCAPE WITHIN THE FIRST 25FT FRONT | | SETBACK.** | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-03-02 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-03-02 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-03-02 |
Time |
09:12 |
Sent To |
|
|
Notes |
2005-03-02 00:00:00 | DENIED, | | 1. NEED CORRECT SITE PLAN, SHOWING | | BUILDING ON BOTH SIDES WITH SETBACKS. | | CALLED CONTR FILE S FOR P/U | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | CONSTRUCTION SERVICES | | 805-6720 |
|
|