Plan Review Details - Permit 05021036
Plan Review Stops For Permit 05021036
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-22 Cont ID  
Sent By shill Date 2005-07-22 Time 11:24 Rev Time 1.00
Received By shill Date 2005-07-22 Time 11:24 Sent To Z
Notes
2005-07-23 00:00:00SEPARATE PERMIT FOR SHUTTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 12:05 Rev Time 1.00
Received By shill Date 2005-07-21 Time 12:05 Sent To Z
Notes
2005-07-21 00:00:00****CORRECTIONS***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
  
 ROUTED TO ZONING (NO ZONING STAMP ON
 SURVEY/SITE PLAN).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-22 Cont ID  
Sent By shill Date 2005-06-22 Time 10:23 Rev Time 0.50
Received By shill Date 2005-06-22 Time 10:23 Sent To PC
Notes
2005-06-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 NOTE - CHANGED PLAN TO BE ISSUED FROM
 MASTER #04031090
  
 1.)SHEET 5.1 DOES NOT MATCH THE PLANS
 SUBMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-04-05 Cont ID  
Sent By shill Date 2005-04-05 Time 15:54 Rev Time 4.00
Received By shill Date 2005-04-05 Time 11:46 Sent To PC
Notes
2005-04-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.) NAILING FOR ROOF SHEATHING, 1-A6 AND
 BB-A3 (6 IN OC) IS NOT COMPLIANT FOR
 ZONE 3, FBC*TABLE 2306.1.
  
 4.) ADDITIONAL FEES DUE TO VALUE
 ADJUSTMENT.1888SF X 76.96, 513 X 41.6,
 TOTAL OF 166640.SEE ATTACHED.
  
 5.) WINDOW/DOOR BUCK DETAIL, A6, SHOWS
 ATTACHMENT INTO WOOD FRAMING. OTHER
 DETAILS SHOW THE CONSTRUCTION AS CBS.
  
 6.) SPECIFY WINDOW AND DOOR SIZES.
 BEDROOM WINDOWS ARE TO COMPLY WITH
 EMERGENCY EGRESS REQUIREMENTS,
 FBC1005.4.
  
 7.) SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 8.) PROVIDE REACTION LOADS, ROOF FRAMING
 PLAN.
  
 9.) DOOR 2 BETWEEN LAUNDRY ROOM AND
 GARAGE IS TO BE SOLID CORE,
 FBC?13-403.1.ABCD.
  
 10.) BB-A3 REFERS TO TRUSS PLAN FOR
 GIRDER DETAIL.THIS WAS NOT PROVIDED.
 NO CONNECTORS OR REACTION LOADS
 SPECIFIED FOR GIRDER CONNECTIONS.
  
 11.) AA-A3, PORCH DETAILS, REFERS TO
 MECHANICAL PAGE.
  
 12.) FLORIDA STATE PRODUCT APPROVAL DOES
 NOT APPEAR TO MATCH THE NOA PROVIDED.
 PROVIDE FLORIDA STATE PRODUCT APPROVAL
 AND CIRCLE WHICH PRODUCT YOU ARE USING
  
 13.) THE SAME DATA SHEETS WERE PROVIDED
 FOR FL18 AND FL19.I CANNOT DETERMINE
 COMPLIANCE WITH FAC9B72.
  
 14.) THE TWO SPEC SHEETS SUBMITTED FOR
 DOORS ARE FOR SINGLE DOORS.THE GLAZED
 DOORS ON THE PLAN ARE DOUBLE DOORS.
  
 15.) THE PLAN SHOWS A PANEL DOOR FOR THE
 FRONT DOOR.THIS SERVES AS THE
 EMERGENCY MEANS OF ESCAPE FBC1005.4.5.
 IF THIS DOOR IS TO BE GLAZED, CHANGE THE
 PANEL DOOR NOTE ON THE PLAN AND INDICATE
 THE EMERGENCY MEANS OF ESCAPE.
  
 16.) PRODUCT APPROVALS ALSO REQUIRED
 FOR:
 ROOF TILE
 SHUTTERS
 SINGLE HUNG WINDOWS
 OPAQUE DOOR
  
 PRODUCT APPROVALS NOT APPROVED PRIOR TO
 ISSUANCE WILL REQUIRE SEPARATE PERMITS
 FOR THOSE ITEMS.
  
 17.) COMPLETE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.
  
 18.) THIS PROPERTY IS IN THE FIRE
 DISTRICT.DECLARE A BUILDING TYPE
 FBC600.TYPE VI CONSTRUCTION NOT
 ALLOWED IN THE FIRE DISTRICT, FBC*102.1.
  
 19.) SHOW COMPLIANCE WITH FBC TABLE 600
 IN REGARDS TO FIRE RESISTANCE FOR
 EXTERIOR BEARING WALLS.
  
 20.) PROVIDE DESIGN CRITERIA FOR THE
 TRUSSES, TCLL, TCDL, BCLL, BCDL.BCLL
 TO COMPLY WITH FBC TABLE 1604.1.
  
 21.)SHOW ATTIC ACCESS LOCATION AND
 SIZE, FBC2309.6, 2309.7.
  
 22.)32" CLEAR OPENING REQUIRED FOR THE
 FRONT DOOR, FBC TABLE 1004.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 13:35 Rev Time 0.00
Received By shill Date 2005-07-21 Time 13:35 Sent To  
Notes
2005-07-21 00:00:00SEE MASTER

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-02 Cont ID  
Sent By btrobaug Date 2005-06-02 Time 13:46 Rev Time 0.50
Received By btrobaug Date 2005-06-02 Time 12:56 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-03-18 Cont ID  
Sent By btrobaug Date 2005-03-18 Time 12:09 Rev Time 0.50
Received By btrobaug Date 2005-03-18 Time 11:03 Sent To M
Notes
2005-03-18 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} COMPLETE THE RISER DIAGRAM. SHOW
 CONDUIT SIZES AND THE GROUNDING
 ELECTRODE SYSTEM CONNECTIONS PER 250.50.
  
 2} PROVIDE LOAD CALCS AND PANEL
 SCHEDULES PER 215.5.
  
 3} SHOW FAULT CURRENT CALC AND INDICATE
 THE AIC RATING OF THE EQUIPMENT, 110.9.
  
 4} LOCATE OUTDOOR RECEPTACLE'S PER
 210.52(E).
  
 5} KITCHEN COUNTERTOP RECEPTACLE SPACING
 MUST COMPLY WITH 210.52(C).
  
 6} SHOW SMOKE DETECTOR LOCATIONS PER
 905.2.2 FBC & 8-1.4.1.6.2. NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-07-13 Cont ID  
Sent By adarroug Date 2005-07-13 Time 10:26 Rev Time 0.00
Received By adarroug Date 2005-07-13 Time 10:26 Sent To M
Notes
2005-07-13 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 09:47 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 09:47 Sent To M
Notes
2005-07-07 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 08:10 Rev Time 0.00
Received By shill Date 2005-06-17 Time 08:10 Sent To B
Notes
2005-06-17 00:00:00TO SH DESK
  
 CHANGED TO BE ISSUED FROM MASTER PLAN

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 15:52 Rev Time 0.00
Received By shill Date 2005-06-09 Time 15:52 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 09:06 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 09:06 Sent To E
Notes
2005-05-26 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-16 Cont ID  
Sent By adarroug Date 2005-03-16 Time 11:46 Rev Time 0.00
Received By adarroug Date 2005-03-16 Time 11:46 Sent To E
Notes
2005-03-16 00:00:00TO "SFR""E"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-14 Cont ID  
Sent By mmclean Date 2005-03-15 Time 16:13 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 15:06 Sent To Z
Notes
2005-03-14 00:00:00TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-17 Cont ID  
Sent By adarroug Date 2005-04-05 Time 13:50 Rev Time 0.00
Received By shill Date 2005-02-17 Time 13:50 Sent To PC
Notes
2005-02-17 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 13:36 Rev Time 0.00
Received By shill Date 2005-07-21 Time 13:36 Sent To  
Notes
2005-07-21 00:00:00SEE MASTER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-07-16 Cont ID  
Sent By hmoser Date 2005-07-16 Time 11:47 Rev Time 0.00
Received By hmoser Date 2005-07-16 Time 11:42 Sent To P
Notes
2005-07-16 00:00:00PLAN DENIED
 1) PLEASE PROVIDE TWO SETS OF ENERGY
 CALCULATIONS AND MANUAL J.
 2) RETURN AIR CANS IN THE BEDROOMS ARE
 TO SMALL FOR THE RETURN AIR DUCT.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2005-03-22 Time   Rev Time 0.00
Received By hmoser Date 2005-03-22 Time 17:19 Sent To B
Notes
2005-03-22 00:00:00PLAN DENIED
 1) INDICATE SIZE OF RETURN DUCT OFF THE
 RETURN AIRPLENUM.
 2) REFER TO SECTION 601.4 # 3 2001
 FLORIDA BUILDING CODE MECHANICAL
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 13:36 Rev Time 0.00
Received By shill Date 2005-07-21 Time 13:36 Sent To  
Notes
2005-07-21 00:00:00SEE MASTER

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-22 Cont ID  
Sent By gsalfeld Date 2005-03-22 Time 14:43 Rev Time 1.00
Received By gsalfeld Date 2005-03-22 Time 14:43 Sent To B
Notes
2005-03-22 00:00:003/22/05-
 1-SHEET A-1 SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN,NOR
 DOES IT MEET CODE REQUIREMENTS.
 2-RISER DIAGRAM MUST BE IN ISOMETRIC
 FORM
 AND MATCH THE INSTALLATION OF
 PLUMBING,SEE FBC 2001
 104.2.1-REQUIREMENTS

Review Stop S SIGNS
Rev No 1 Status P Date 2005-03-15 Cont ID  
Sent By mmclean Date 2005-03-15 Time 16:13 Rev Time 0.00
Received By mmclean Date 2005-03-15 Time 16:13 Sent To I
Notes
2005-06-16 00:00:00PLEASE NOTE THAT THE STOP FOR THIS
 PERMIT SHOWS (S) INSTEAD OF (Z) ERROR.
2005-03-15 00:00:00APPROVED BY SHIRLEY GRAHAM, ASSOC.
 PLANNER 822-1458

Review Stop Z ZONING
Rev No 3 Status P Date 2005-07-22 Cont ID  
Sent By mmclean Date 2005-07-22 Time 16:21 Rev Time 0.00
Received By mmclean Date 2005-07-22 Time 16:21 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-16 Cont ID  
Sent By mmclean Date 2005-06-16 Time 18:48 Rev Time 0.00
Received By mmclean Date 2005-06-16 Time 18:48 Sent To I
Notes
2005-06-16 00:00:00DENIED.
 1. NEED TO REDUCE DRIVEWAY/WALKWAY TO
 MEET THE ZONING REQUIRMENTS.
 2. MUST PROVIDE THE WIDTH & LENGTH OF
 DRIVEWAY/WALKWAY.
 **MUST HAVE 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK.**
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-02 Cont ID  
Sent By mmclean Date 2005-03-02 Time 09:12 Rev Time 0.00
Received By mmclean Date 2005-03-02 Time 09:12 Sent To  
Notes
2005-03-02 00:00:00DENIED,
 1. NEED CORRECT SITE PLAN, SHOWING
 BUILDING ON BOTH SIDES WITH SETBACKS.
 CALLED CONTR FILE S FOR P/U
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICES
 805-6720