Plan Review Details - Permit 05021008
Plan Review Stops For Permit 05021008
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2005-12-10 Cont ID  
Sent By kstevens Date 2005-12-10 Time 10:22 Rev Time 1.00
Received By kstevens Date 2005-12-10 Time 10:22 Sent To  
Notes
2005-12-10 00:00:00REVISION OK - ADDED ADDITIONAL GAS LINE
 TO POOL HEATER
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.
  
  
  
 .
  
  
  
  
  
  
  
  
  
  
  
 .
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-04-02 Cont ID  
Sent By kstevens Date 2005-04-02 Time 06:12 Rev Time 0.33
Received By kstevens Date 2005-04-02 Time 06:12 Sent To  
Notes
2005-04-02 00:00:00PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  
  
  
 .
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-03-01 Cont ID  
Sent By pschmitz Date 2005-03-01 Time 13:45 Rev Time 0.00
Received By pschmitz Date 2005-03-01 Time 13:50 Sent To PC
Notes
2005-03-01 00:00:00GAS PLAN REVIEW, FBC 2001 DENIED
 (1) PROVIDE GAS REGULATOR MANFACTURE CUT
 SHEET.
 (2)PROVIDE CSST TYPE OF MATERIAL AND
 GAS TABLE SIZING INFORMATION.
 QUESTIONS561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 14:57 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 14:57 Sent To P
Notes
2005-11-14 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 17:15 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 17:15 Sent To G
Notes
2005-03-17 00:00:00TO "G" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 11:06 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 11:06 Sent To G
Notes
2005-02-18 00:00:00TO "G" BOX