Plan Review Details - Permit 05020982
Plan Review Stops For Permit 05020982
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-23 Cont ID  
Sent By btrobaug Date 2005-02-23 Time 13:22 Rev Time 0.33
Received By btrobaug Date 2005-02-23 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-22 Cont ID  
Sent By btrobaug Date 2005-02-22 Time 11:02 Rev Time 0.33
Received By btrobaug Date 2005-02-22 Time 10:54 Sent To  
Notes
2005-02-22 00:00:00 
 PLEASE PROVIDE AIC CALCULATIONS AND
 INDICATE THE AIC RATING OF THE EQUIPMENT
 PER 110.9 & 10.NEC.
  
 PLANS MUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE PLANS PER 104.2.1 FBC.
  
 PLEASE ADD THESE ITEMS TO PLANS AND
 RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 13:17 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 13:17 Sent To E
Notes
2005-02-18 00:00:00TO "E" BOX