Plan Review Details - Permit 05020946
Plan Review Stops For Permit 05020946 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2005-02-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-02-18 |
Time |
14:58 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2005-02-18 |
Time |
14:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2005-02-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-02-23 |
Time |
06:49 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-02-23 |
Time |
06:49 |
Sent To |
|
|
Notes |
2005-02-23 00:00:00 | NOTES REDLINED: | | EM/EXT LTS PER 700.12E | | TRANSFOMER GROUNDING PER 250.30 | | NO STORAGE IN ELEC RM,PANELS ETC. | | 110.26, 408.7. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2005-03-17 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-03-17 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-03-17 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-03-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-03-30 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-03-30 |
Time |
16:38 |
Sent To |
P |
|
Notes |
2005-03-30 00:00:00 | TO "KSTEVENS" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-02-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-16 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-16 |
Time |
14:15 |
Sent To |
|
|
Notes |
2005-02-16 00:00:00 | TO "COMM"BD#55 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2005-03-12 |
Time |
|
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-03-12 |
Time |
13:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2005-04-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-04-14 |
Time |
17:58 |
Rev Time |
0.60 |
Received By |
kstevens |
Date |
2005-04-14 |
Time |
17:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-03-11 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-03-11 |
Time |
14:58 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2005-03-11 |
Time |
14:58 |
Sent To |
|
|
Notes |
2005-03-11 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | | | 1) SHT 1 BREAK ROOM SINK SHALL BE | | ACCESSIBLE. THE FOLLOWING INFORMATION | | SHALL BE SHOWN ON PLANS. | | 11-4.24.4 SINK DEPTH (6-1/2" MAX) | | 11-4.24.5 CLEAR FLOOR SPACE, SHALL BE | | PROVIDED IN FRONT OF A SINK TO ALLOW | | FORWARD APPROACH, AND SHALL EXTENDA | | MAXIMUM OF 19" UNDERNEATH THE SINK. BLDG | | OFFICIAL DETERMINED THAT NO DOORS OR | | PANELS SHALL BE COVERING THE CLEAR FLOOR | | SPACE REQUIRED. | | 11-4.24.6 EXPOSED PIPES AND SURFACES. | | | | 2) A DRINKING FOUNTAIN IS REQUIRED. IF A | | DRINKING FOUNTAIN IS LOCATED IN THE | | COMMON AREA, PLEASE INDICATE ON PLANS. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|
|
|