Plan Review Details - Permit 05020946
Plan Review Stops For Permit 05020946
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-02-18 Cont ID  
Sent By shill Date 2005-02-18 Time 14:58 Rev Time 1.00
Received By shill Date 2005-02-18 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 06:49 Rev Time 0.25
Received By dpalmer Date 2005-02-23 Time 06:49 Sent To  
Notes
2005-02-23 00:00:00NOTES REDLINED:
 EM/EXT LTS PER 700.12E
 TRANSFOMER GROUNDING PER 250.30
 NO STORAGE IN ELEC RM,PANELS ETC.
 110.26, 408.7.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-17 Cont ID  
Sent By mwennerg Date 2005-03-17 Time 14:40 Rev Time 0.00
Received By mwennerg Date 2005-03-17 Time 14:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-30 Cont ID  
Sent By adarroug Date 2005-03-30 Time 16:38 Rev Time 0.00
Received By adarroug Date 2005-03-30 Time 16:38 Sent To P
Notes
2005-03-30 00:00:00TO "KSTEVENS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-16 Cont ID  
Sent By adarroug Date 2005-02-16 Time 14:15 Rev Time 0.00
Received By adarroug Date 2005-02-16 Time 14:15 Sent To  
Notes
2005-02-16 00:00:00TO "COMM"BD#55

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-03-12 Time   Rev Time 0.00
Received By hmoser Date 2005-03-12 Time 13:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-04-14 Cont ID  
Sent By kstevens Date 2005-04-14 Time 17:58 Rev Time 0.60
Received By kstevens Date 2005-04-14 Time 17:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-11 Cont ID  
Sent By kstevens Date 2005-03-11 Time 14:58 Rev Time 0.50
Received By kstevens Date 2005-03-11 Time 14:58 Sent To  
Notes
2005-03-11 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) SHT 1 BREAK ROOM SINK SHALL BE
 ACCESSIBLE. THE FOLLOWING INFORMATION
 SHALL BE SHOWN ON PLANS.
 11-4.24.4 SINK DEPTH (6-1/2" MAX)
 11-4.24.5 CLEAR FLOOR SPACE, SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH, AND SHALL EXTENDA
 MAXIMUM OF 19" UNDERNEATH THE SINK. BLDG
 OFFICIAL DETERMINED THAT NO DOORS OR
 PANELS SHALL BE COVERING THE CLEAR FLOOR
 SPACE REQUIRED.
 11-4.24.6 EXPOSED PIPES AND SURFACES.
  
 2) A DRINKING FOUNTAIN IS REQUIRED. IF A
 DRINKING FOUNTAIN IS LOCATED IN THE
 COMMON AREA, PLEASE INDICATE ON PLANS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  