Plan Review Details - Permit 05020807
Plan Review Stops For Permit 05020807
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-18 Cont ID  
Sent By shill Date 2005-05-18 Time 15:55 Rev Time 0.50
Received By shill Date 2005-05-18 Time 13:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-02-18 Cont ID  
Sent By shill Date 2005-02-18 Time 15:33 Rev Time 1.00
Received By shill Date 2005-02-18 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 17:09 Rev Time 0.25
Received By dpalmer Date   Time   Sent To  
Notes
2005-09-02 00:00:00NO ELEC SUBMITTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-17 Cont ID  
Sent By dpalmer Date 2005-05-17 Time 08:14 Rev Time 0.25
Received By dpalmer Date 2005-05-17 Time 08:14 Sent To FIRE
Notes
2005-05-17 00:00:00REDLINED 517.13 FOR ALL BRANCH
 CIRCUITING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 05:13 Rev Time 0.00
Received By shill Date 2005-05-18 Time 13:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-18 Cont ID  
Sent By nmccray Date 2005-05-18 Time 12:22 Rev Time 0.00
Received By nmccray Date 2005-05-18 Time 12:22 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-11 Cont ID  
Sent By mcarsill Date 2005-03-11 Time 12:13 Rev Time 0.00
Received By mcarsill Date 2005-03-11 Time 12:13 Sent To  
Notes
2005-03-11 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. NEW CEILING TILES SHALL MEET
 APPROPRIATE FLAME SPREAD REQUIREMENTS.
  
 3. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 14:48 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 14:48 Sent To P
Notes
2005-08-19 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 12:33 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 12:33 Sent To B
Notes
2005-05-18 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 08:13 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 08:13 Sent To E
Notes
2005-05-10 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 14:06 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 14:06 Sent To  
Notes
2005-02-14 00:00:00TO "COMM" BD #51

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-31 Cont ID  
Sent By jleech Date 2005-08-31 Time 10:37 Rev Time 3.00
Received By jleech Date 2005-08-31 Time 10:37 Sent To E
Notes
2005-08-31 00:00:00DENIED;
 ADDITONAL WORK BEING DONE WAS NOT PART
 OF ORIGINAL SCOPE OF WORK. ADDITIONAL
 FEE'S DUE.
 MED-GAS APPLICATION # 05060902 WAS
 REVIEW ON 6/28/05 AND DENIED. (COPY OF
 REVIEW ATTACHED)
 ADDITIONAL NOTES;
 1.PAGE A-3 NOTE 5 VACUUM LINES SHALL BE
 SUPPORTED EVERY 4' PER FBC PLUMBING
 TABLE 308.5
 2.CUT SHEET FOR STERI-CENTER IS NOT
 LEGIBLE, PLEASE RESUBMIT.
 3.MANUFACTORS INSTALLATION INSTRUCTIONS
 ARE NOT TO CODE NFPA SEC 5.3.3.6.3.1.
 (MUST BE DIRECTLY PIPED TO SANITARY
 SYSTEM.
 4.PIPING RISER DIAGRAM DOES NOT SHOW A
 TRAP FOR OVER HEAD VACUUM LINE AS SHOWN
 IN THE INSTALLATION INSTRUCTIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695