Plan Review Details - Permit 05020785
Plan Review Stops For Permit 05020785
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-25 Cont ID  
Sent By btrobaug Date 2005-02-25 Time 16:50 Rev Time 0.33
Received By btrobaug Date 2005-02-25 Time 16:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-23 Cont ID  
Sent By btrobaug Date 2005-02-23 Time 11:00 Rev Time 0.50
Received By btrobaug Date 2005-02-23 Time 10:18 Sent To  
Notes
2005-02-23 00:00:00 
 PLEASE NOTE THAT TWO DEMAND FACTORS WERE
 USED IN THE LOAD CALCULATION. IF 220.32
 IS USED THEN PART III CANNOT BE. USE ONE
 OR THE OTHER AND ADJUST CONDUIT RISER,
 CONDUCTOR AND GEC SIZES, RESUBMIT FOR
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW