Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-16 Cont ID  
Sent By dpalmer Date 2005-02-16 Time 14:36 Rev Time 0.00
Received By dpalmer Date 2005-02-16 Time 14:36 Sent To  
Notes
2005-02-16 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 FOR MIN CIRCUITS REQUIRED PER 2002 NEC.
 BATHS, 210.11C3, KITCHEN 210.52/210.11C1
 WASHER 220.16, 210.52 ETC.
 215.5
  
 2)NOTE: PLEASE SEE SD'S, INSIDE AND
 OUTSIDE BEDRMS WILL BE REQUIRED.
 NFPA-72 8-1.4.1.6.2
 PLEASE SEE EGRESS LT PER 210.70 WILL BE
 REQUIRED.
 PLEASE SEE ARC FAULT PROTECTION REQUIRED
 PER 210.12.
  
 PLEASE SEE PLANS HAVE BEEN REDLINED FOR
 LOCATIONS OF REQUIRED ITEMS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 16:57 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 16:57 Sent To E
Notes
2005-02-11 00:00:00TO "E" BOX