Plan Review Stops For Permit 05020768 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-02-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-02-16 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2005-02-16 |
Time |
14:36 |
Sent To |
|
|
Notes |
2005-02-16 00:00:00 | *** UNSAT *** | | | | 1)NOTE: PLEASE SUBMIT A PANEL SCHEDULE | | FOR MIN CIRCUITS REQUIRED PER 2002 NEC. | | BATHS, 210.11C3, KITCHEN 210.52/210.11C1 | | WASHER 220.16, 210.52 ETC. | | 215.5 | | | | 2)NOTE: PLEASE SEE SD'S, INSIDE AND | | OUTSIDE BEDRMS WILL BE REQUIRED. | | NFPA-72 8-1.4.1.6.2 | | PLEASE SEE EGRESS LT PER 210.70 WILL BE | | REQUIRED. | | PLEASE SEE ARC FAULT PROTECTION REQUIRED | | PER 210.12. | | | | PLEASE SEE PLANS HAVE BEEN REDLINED FOR | | LOCATIONS OF REQUIRED ITEMS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | | | |
|
|