Plan Review Details - Permit 05020215
Plan Review Stops For Permit 05020215
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-10 Cont ID  
Sent By alange Date 2005-06-10 Time 10:52 Rev Time 1.00
Received By alange Date 2005-06-10 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-04-28 Cont ID  
Sent By alange Date 2005-04-28 Time 14:31 Rev Time 0.66
Received By alange Date 2005-04-28 Time 14:11 Sent To  
Notes
2005-04-28 00:00:00DENIED
  
  
 6.SUBMIT PRODUCT APPROVALS FOR NUVEN
 NUATA 12 STRAP.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-16 Cont ID  
Sent By alange Date 2005-02-16 Time 10:48 Rev Time 2.75
Received By alange Date 2005-02-15 Time 10:15 Sent To P
Notes
2005-02-16 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SURVEY AND FLOOR PLAN MEASUREMENTS
 DON'T MATCH.
  
 3.SEE ELECTRICAL REVIEW COMMENT #11
 THAT COULD CAUSE A DELAY IN ISSUING A
 PERMIT.
  
 4.A / A-6 FOOTING DEPTH.THE BOTTOM
 OF FOUNDATION SHALL BE NO LESS THAN
 12" BELOW FINISHED GRADE.FBC 1804.1.3
  
 5.STAIR KEY #1.SHALL COMPLY WITH FBC
 2001 NOT SBCCI.
  
 6.SUBMIT PRODUCT APPROVALS FOR LINTELS
 AND NUVEN NUATA 12 STRAP.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-30 Cont ID  
Sent By dpalmer Date 2006-03-30 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2006-03-30 Time 12:26 Sent To PC
Notes
2006-03-30 00:00:00REDLINED EGREE LT FIXTURE REQUIRED,
 210.70,LS101 7.8

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-02 Cont ID  
Sent By dpalmer Date 2006-03-02 Time 20:20 Rev Time 0.00
Received By dpalmer Date 2006-03-02 Time 19:57 Sent To PC
Notes
2006-03-02 00:00:00REDLINED, LT FIXTURE NOT ADDED AS NOTED
 ON PREVIOUS REVIEW FOR BACK PORCH.
 210.70, LS 101 7.8.1.3
  
 REDLINED WRONG CHAPTER'S/CODE FOR
 NFPA-72, SHOULD BE 2002 ,
 11.5.1.1,11.8.3.5
  
 REV OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-06-02 Cont ID  
Sent By btrobaug Date 2005-06-02 Time 17:49 Rev Time 0.50
Received By btrobaug Date 2005-06-02 Time 17:19 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-01 Cont ID  
Sent By dpalmer Date 2005-04-01 Time 15:33 Rev Time 1.25
Received By dpalmer Date 2005-04-01 Time 14:23 Sent To P
Notes
2005-04-01 00:00:00********* UNSAT 2ND REVIEW ***********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES DUE TO CHANGES
 ON PLANS.
  
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE: NOTE #3 NO, PLEASE SEE
 COUNTERSPACE REDLINED.
 PLEASE ALSO SEE 210.52C1 FOR SPACING.
 PLEASE ALSO SEE NEW NOTES BELOW.
  
 4)NOTE: NO, PREVIOUS NOTES AND NOTE #3
 ABOVE.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK
  
 9)NOTE: NOTE #9 NO, PLEASE SEE REDLINED
 2' OF WALL IN BEDRM #5.
  
 10)NOTE: NOTE #10 NO, PLEASE SEE RISER
 SHOWS REQUIRED GROUNDING ELECTRODE
 ATTACHMENTS AS "OPTIONS". PLEASE SEE
 250.50, THESE ARE REQUIRED.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE #12 OK.
  
 NEW NOTES:
  
 1)NOTE: PLEASE CORRRELATE WIRE SIZES FOR
 SUB PANEL "B". PLEASE SEE PANEL "A",
 SHOWS 80A BRKR ON #12 AWG WHICH IS RATED
 AT 20A'S PER 310.16
  
 2)NOTE: PLEASE SEE CIRCUITING FOR
 CIRCUIT #23, THIS IS SHOWN ON MANY GEN
 RECEPT/LIGHTING, SMALL APPLIANCE
 COUNTERSPACE AND IS ALSO SHOWN FOR ONE
 PHASE OF OVEN.
 PLEASE REVISE AND ADJUST CIRCUITING.
  
 3)NOTE: PLEASE SEE CIRCUITING FOR CU,
 SHOWN AS "B 1,2, PLEASE SEE THIS SHOWS
 BOTH LEGS FROM THE SAME PHASE. (A).
 PLEASE SEE PANEL SCHEDULE. #1&3??
 (MISPRINT)
  
 4)NOTE: PLEASE SEE PANEL "B" IS NOW
 SHOWN BEHIND A/C CU.
 PLEASE SEE 110.26 FOR MIN CLEARENCE FOR
 PANEL AND A/C DISCONNECT.
  
 5)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 6)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONAL AND
 COMMENTS WHICH ARE REPEATED AFTER THREE
 REVIEWS. THIS IS ONLY GIVEN AS A NOTICE
 AT THIS TIME.
  
 PLEASE SEE PLANS, ALL OF THE ABOVE ITEMS
 HAVE BEEN REDLINED FOR AREAS OF NOTES.
  
 PLEASE REMOVE ALL OL/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-11 Cont ID  
Sent By dpalmer Date 2005-02-11 Time 13:28 Rev Time 0.75
Received By dpalmer Date 2005-02-11 Time 13:28 Sent To M
Notes
2005-02-11 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRM
 AND PANEL "M".
 PLEASE SEE RISER INDICATES AS METER/MAIN
 COMBO WITH 200A MAIN BREAKER AND FEED
 THRU LUGS, HOWEVER PANEL "M" IS SHOWN AS
 225A MLO W/ A 200A BRKR FEEDING
 PANEL"A".?
 PLEASE SEE RISER SHOWS 1/0'S (RATED AT
 150A'S) AS THE "FEED-THRU" CONDUCTORS
 WHICH ARE PROTECTED BY A 200A BRKR.
 310.16/310.15B6
 PLEASE SEE PANEL SCHEDULE "M" SHOWS
 3/0'S FEEDING PANEL "A"??
 PLEASE ALSO SEE PANEL "M" CONTAINS MORE
 THAN 6 POSSIBLE MAINS, WHICH IS NOT
 PERMITTED UNDER 230.71A
 PLEASE PROVIDE A MCB AS SHOWN ON RISER.
  
 2)NOTE: PLEASE SEE CIRCUITING FOR SD'S
 WHICH IS #21. PLEASE SEE 210.12 UNDER
 2002 NEC. SD'S ARE ALSO REQUIRED TO BE
 ON AN ARC FAULT PROTECTED CIRCUIT.
 PLEASE SEE CIRCUIT #21 IS ALSO SHOWN AS
 "WATER HEATER" CIRCUIT.
  
  
 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 4)NOTE: PLEASE SEE MISSINGREQUIRED
 GFI'S AT ISLNAD PER 210.8A6(PREVIOUS
 NOTE) AND ALSO SPACING PER 210.52C1-5
  
 5)NOTE: PLEASESEE RECEPT SHOWN ON
 SMALL APPL CIRCUIT WHICH IS NOT PART OF
 DINING RM.(MORNING RM)? A-13.
 THIS MAY NOT BE ON SAME CIRCUIT.
 210.52B
  
 6)NOTE: PLEASE SEE 210.52D.
 IN DWELLING UNITS, AT LEAST ONE WALL
 RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN 900 MM (3 FT) OF THE
 OUTSIDE EDGE OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A
 WALL OR PARTITION THAT IS ADJACENT TO
 THE BASIN OR BASIN COUNTERTOP.
  
 7)NOTE: PLEASE SEE PLANS INDICATE A "GAS
 WATER HEATER", YET PANEL SCHEDULE
 INDICATES ELECTRIC?
 PLEASE CORRELATE.
  
 8)NOTE: PLEASE SEE "NOTES" #15, MENTIONS
 250.60 FOR NEUTRAL/GROUNDING FOR RANGES
 AND DRYERS. PLEASE SEE THIS ART IS FROM
 A PREVIOUS CODE. WE ARE NOW UNDER 2002
 NEC. THIS IS NOW 250.140
  
 9)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING IN BDRM #5 AND DINING RM.
  
 10)NOTE: PLEASE SEE RISER MENTIONS
 GROUNDING ELECTRODE "OPTIONS". PLEASE
 SEE 250.50 FOR MIN REQUIRED. FOOTER
 STEEL AND CWP (IF METAL) IS NOT AN
 OPTIONAL CONNECTION POINT.PLEASE
 ADJUST NOTE.
  
 11)NOTE: PLEASE SEE FS 481.025 WHICH
 REQUIRES PLANS TO BE SIGNED WITH LEGAL
 SIGNATURE. PLANS APPEAR TO BE "SIGNED"
 WITH AN INITIAL? IF THIS IS THE LEGAL
 SIGNATURE, PLEASE PROVIDE A SIGNED,
 DATED AND SEALED NOTORIZED LETTER TO
 ATTEST THIS AS YOUR LEGAL SIGNATURE.
 THIS WILL BE PLACED IN SIGNATURE FILE
 FOR ANY NEED OF FUTURE REFERENCE.
 WE HAVE HAD A PROBLEM, WITH PLANS
 FORGED, SEALS STOLEN ETC.
  
 12)NOTE: PLEASE SEE CODE REFERENCES FOR
 SD'S ARE FROM THE 1996 NFPA-72. PLEASE
 SEE WE ARE CURRNETLY UNDER THE 1999
 NFPA-72. THESE REFERENCES SHOULD READ
 8-1.4.1.6.2, 8-1.4.2 FOR SD
 REQUIREMENTS
  
 PLEASE SEE MOST OF THE ABOVE HAS BEEN
 REDLINED ON ONE SET OF PLANS FOR AREAS
 OF NOTES ABOVE.
  
 ***PLEASE REMOVE ANY/ ALL OLD VOIDED
 SHEETS AND INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 * ADDED NOTE ****
  
 PLEASE SEE CIRCUIT FOR WHIRLPOOL TUB
 SHOWS GFI PROTECTION OPTIONAL?
 PLEASE SEE 680.71

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-29 Cont ID  
Sent By adarroug Date 2006-03-29 Time 14:23 Rev Time 0.00
Received By adarroug Date 2006-03-29 Time 14:23 Sent To E
Notes
2006-03-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 16:25 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 16:24 Sent To E
Notes
2006-03-02 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-01 Cont ID  
Sent By adarroug Date 2005-06-01 Time 14:46 Rev Time 0.00
Received By adarroug Date 2005-06-01 Time 14:46 Sent To E
Notes
2005-06-01 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 14:42 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 14:42 Sent To E
Notes
2005-03-29 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-11 Cont ID  
Sent By mjacobs Date 2005-02-11 Time 10:10 Rev Time 0.00
Received By mjacobs Date 2005-02-11 Time 10:10 Sent To E
Notes
2005-02-11 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-07 Cont ID  
Sent By mjacobs Date 2005-02-07 Time 08:23 Rev Time 0.00
Received By mjacobs Date 2005-02-07 Time 08:23 Sent To Z
Notes
2005-02-07 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-27 Cont ID  
Sent By pkrauss Date 2005-04-27 Time 14:34 Rev Time 0.30
Received By pkrauss Date 2005-04-27 Time 14:34 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-02-14 Cont ID  
Sent By pkrauss Date 2005-02-14 Time 10:52 Rev Time 0.35
Received By pkrauss Date 2005-02-14 Time 10:43 Sent To P
Notes
2005-02-14 00:00:00PROVISO:
 PLEASE NOTE, PLAN DOES NOT INDICATE IF
 THE DRYER IS GAS OR ELECTRIC.SHOULD
 THE DRYER BE GAS PROVIDE THE
 MANUFACTURER'S SUBMITTAL/INSTALLATION
 INSTRUCTIONS AND COMBUSTION AIR
 CALCULATIONS.PLEASE PROVIDE VENTING
 LAYOUT, MATERIAL AND TERMINATION.
  
 PLEASE NOTE GAS WATER HEATER LOCATED IN
 THE GARAGE SHALL HAVE PROTECTION FROM
 DAMAGE IN ACCORDANCE WITH 2001
 FBC(M)303.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-04-14 Cont ID  
Sent By kstevens Date 2005-04-14 Time 14:04 Rev Time 0.50
Received By kstevens Date 2005-04-14 Time 14:04 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-02-17 Cont ID  
Sent By jleech Date 2005-02-17 Time 16:26 Rev Time 0.00
Received By JLEECH Date 2005-04-28 Time 14:11 Sent To B
Notes
2005-02-17 00:00:00DENIED;
 1.PLANS MUST BE SIGNED SEE ELECTRICAL
 PLAN REVIEW NOTE11.
 2.IS WATER HEATER GAS OR ELECTRIC?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-10 Cont ID  
Sent By mmclean Date 2005-02-10 Time 16:09 Rev Time 0.00
Received By mmclean Date 2005-02-10 Time 16:09 Sent To I
Notes
***NONE***