Plan Review Stops For Permit 05020163 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-02-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-03 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-03 |
Time |
08:14 |
Sent To |
P |
|
Notes |
2005-02-03 00:00:00 | TO "P"BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-02-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-02-16 |
Time |
06:43 |
Rev Time |
1.02 |
Received By |
kstevens |
Date |
2005-02-16 |
Time |
06:43 |
Sent To |
|
|
Notes |
2005-02-16 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) TWO OR MORE COPIES OF DRAWINGS DRAWN | | TO SCALE WITH SUFFICIENT CLARITY AND | | DETAIL TO INDICATE THE NATURE AND | | CHARACTER OF THE WORK SHALL ACCOMPANY | | THE APPLICATION FOR A PERMIT. (SEE | | ATTACHED SHEET. NO PERMIT HAS BEEN | | APPLIED FOR ON THIS PROPERTY FOR REMODEL | | AND IS REQUIRED) | | 2) INDICATE THE OCCUPANCY OF THE | | BUILDING. | | 3) KITCHEN SINK SHALL NOT DRAIN THROUGH | | THE HORIZONTAL WET VENT OF THE BATHROOM | | FIXTURES. SECTION 909.1. KITCHEN SINK | | SHALL DISCHARGE DOWNSTREAM OF THE | | BATHROOM FIXTURES. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|
|
|