Plan Review Details - Permit 05011522
Plan Review Stops For Permit 05011522
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 11:36 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 11:36 Sent To P
Notes
2005-03-17 00:00:00TO "KSTEVENS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-24 Cont ID  
Sent By adarroug Date 2005-02-24 Time 13:47 Rev Time 0.00
Received By adarroug Date 2005-02-24 Time 13:46 Sent To P
Notes
2005-02-24 00:00:00TO "KSTEVENS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 14:44 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 14:44 Sent To P
Notes
2005-01-31 00:00:00TO "P" BOX.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-05-05 Cont ID  
Sent By kstevens Date 2005-05-05 Time 14:33 Rev Time 1.75
Received By kstevens Date 2005-03-26 Time 16:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-08 Cont ID  
Sent By gsalfeld Date 2005-03-08 Time 09:00 Rev Time 0.00
Received By gsalfeld Date 2005-03-08 Time 09:02 Sent To  
Notes
2005-03-08 00:00:003/8/2005 DENIED
 FAC- 61G1-16.004 TITLE BLOCK
  
 1-TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTUAL DESIGN DWG AND SPEC.
 IDENTIFICATION SHEETS.
 TITLE BLOCK MUST CONTAIN
 1-FIRM NAME,ADDRESS,TELEPHONE NUMBER
 2-FIRM LICENCE NUMBER
 3-NAME OF IDENTIFICATION OF PROJECT
 4-DATE PREPARED
 5-A SPACE FOR THE SIGNATURE/DATED
 SEAL.
 6-A SPACE FOR THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT.
 2-PLAN SHOWS 2-3" BACKFLOWS AT
 DIFFERENT LOCATIONS WITH ONE CONTROLLER
 AND ONE SENSOR PLEASE CLARIFY.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-12 Cont ID  
Sent By pschmitz Date 2005-02-12 Time 08:44 Rev Time 0.00
Received By pschmitz Date 2005-02-12 Time 08:44 Sent To PC
Notes
2005-02-12 00:00:00PLUBING PLAN REVIEW FBC 2001 DENIED
 (1)
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1
 (2))NOTE: PLANS REQUIRED TO BE SIGNED,
 DATED AND SEALED BY THE ARCHITECT,
 PLEASE SEE FS 481.221 AND FAC 61G1-16
 (3)BACK FLOW PREVENTER REQUIRED, SHOW
 LOCATION OF BACK FLOW PREVENTER.
 (4) PROVIDE ALL INFORMATION ON THE
 OPERATION AND CONTROL OF THE IRRIGATION
 SYSTEM.
 END OF COMMENTS, QUESTIONS 561-805-6692