Plan Review Details - Permit 05011403
Plan Review Stops For Permit 05011403
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-28 Cont ID  
Sent By rbrown Date 2005-04-28 Time 12:15 Rev Time 0.00
Received By rbrown Date 2005-04-28 Time 12:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-28 Cont ID  
Sent By rbrown Date 2005-02-28 Time 09:40 Rev Time 0.00
Received By rbrown Date 2005-02-28 Time 09:40 Sent To  
Notes
2005-02-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT FOR
 PUBLIC RECORD SHALL INCLUDE THE PRINTED
 NAME OF THE ARCHITECT SEALING THE PLANS.
 ADD THE PRINTED NAME OF SERGIO BAKAS TO
 EACH COPY OF SHEETS A1.3.09 AND A2.2.06.
 THIS MAY BE ADDED BY HAND.
  
 2) FBC* 104.2.1SUBMIT REVISED PLANS
 UNDER THE BASE BUILDING PERMIT# 03020961
 TO REFLECT THE PROPOSAL TO COMBINE UNITS
 UPH01 AND UPH18.
  
 3) FBC 1707.4SHEET A1.3.09 ANNOTATES
 WINDOW TYPES A AND D RESPECTIVELY, AS
 ALUMINUM FIXED PICTURE WINDOW AND
 ALUMINUM HORIZONTAL SLIDING WINDOW. EACH
 NOTE STATES "...CONTRACTOR TO PROVIDE
 PRODUCT APPROVAL, TYP."ARE THESE
 WINDOWS A REVISION TO THE WINDOWS
 PERMITTED UNDER THE BASE BUILDING
 PERMIT# 03020961 ?IF SO, SUBMIT
 PRODUCT APPROVALS FOR THE REVISED
 WINDOWS.
  
 4) FBC 1603.1WEIGHT OF STONE FLOORING.
 WHAT IS THE THICKNESS AND COMBINED
 WEIGHT OF THE STONE FLOORING AND
 ADHESIVE/MUD AND IS THE WEIGHT LESS THAN
 THE ALLOWANCE MADE FOR FLOOR FINISH
 UNDER THE BASE BUILDING PERMIT# 03020961
 ?
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 18:58 Rev Time 0.25
Received By dpalmer Date 2005-07-26 Time 18:58 Sent To FIRE
Notes
2005-07-26 00:00:00REV FOR ADDED DUCT DETECTORS,
 AUDIO/VISUAL(HORN-LT/STROBE).

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-22 Cont ID  
Sent By dpalmer Date 2005-04-22 Time 16:48 Rev Time 0.33
Received By dpalmer Date 2005-04-22 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-03-03 Cont ID  
Sent By dpalmer Date 2005-03-03 Time 10:07 Rev Time 0.10
Received By dpalmer Date   Time   Sent To  
Notes
2005-03-03 00:00:00REV BROUGHT IN W/ OUT PERMIT BEING
 ISSUED.
 PLANS ARE STILL ON BOARD BEING REVIEWED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-17 Cont ID  
Sent By dpalmer Date 2005-02-17 Time 06:40 Rev Time 0.30
Received By dpalmer Date 2005-02-15 Time 04:45 Sent To  
Notes
2005-02-17 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE SHEETA1.3.09 MENTIONS
  
 COMBINATION UNITS FOR OTHER LOACTIONS,
 HOWEVER THESE PLANS SHOULD ONLY BE FOR
 ONE COMBO UNIT. THESE WILL BE
 INDIVIDUALLY OWNER UNITS AND PERMIT AND
 PLANS SHALL BE SUBMITTED SEPARATELY.
 PLEASE ALSO SEE BLDG REVIEW NOTES IN
 REFERENCE TO POSSIBLE UNITY OF TITLE
 ETC.
  
 2)NOTE: PLEASE SEE PLANS UNDER BASE BLDG
 #03020961 MUST ALSO BE REVISED TO REMOVE
 ALL ELECTRICAL UNDER BASE BLDG FOR EACH
 OF THESE UNITS WHICH ARE BEING CHANGED
 AND SUBMITTED FOR SEPARATE TENANT/BUILD
 OUT PERMITS.
  
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S)WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SEE BLDG REVIEW COMMENTS.
 PLEASE SEE ELECTRICAL SHEET CONTAIN
 STAMPED FROM PALM BEACH COUNTY FOR
 IMPACT FEES.
 THIS SHOULD HAVE BEEN STAMPED ON A COVER
 SHEET(S).
  
 ELECTRICAL PLANS REVIEWED FOR CODE
 COMPLIANCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-02 Cont ID  
Sent By nmccray Date 2005-08-02 Time 10:31 Rev Time 0.00
Received By nmccray Date 2005-08-02 Time 10:31 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-10 Cont ID  
Sent By mcarsill Date 2005-03-10 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2005-03-10 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-19 Cont ID  
Sent By adarroug Date 2005-07-19 Time 08:56 Rev Time 0.00
Received By adarroug Date 2005-07-19 Time 08:56 Sent To M
Notes
2005-07-19 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 09:11 Rev Time 0.00
Received By shill Date 2005-06-08 Time 09:11 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 13:58 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 13:57 Sent To  
Notes
2005-04-12 00:00:00TO "COMM" BD#46

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-03 Cont ID  
Sent By mjacobs Date 2005-03-03 Time 09:56 Rev Time 0.00
Received By mjacobs Date 2005-03-03 Time 09:56 Sent To E
Notes
2005-03-03 00:00:00TO "DP" DESK/REV. THIS PLAN IS PRESENTLY
 BEEN REVIEWED, HOWEVER A REVISION WAS
 ACCEPTED IN.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-03-10 Time 10:05 Rev Time 0.00
Received By rbrown Date 2005-01-28 Time 08:51 Sent To  
Notes
2005-01-28 00:00:00TO "COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-06-16 Cont ID  
Sent By pkrauss Date 2005-06-16 Time 09:02 Rev Time 0.45
Received By pkrauss Date 2005-06-16 Time 08:40 Sent To  
Notes
2005-06-16 00:00:00PROVISO:
 JP UNIT IS A "COMBINED" UNIT WHICH
 CHANGES THE AGGREGATE AIR TO EXCEED
 2,000 CFM.DUCT SMOKE DETECTORS WITH
 NOTIFICATION WILL BE REQUIRED IN
 ACCORDANCE WITH 2001 FBC(M)606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-16 Cont ID  
Sent By pkrauss Date 2005-05-16 Time 20:44 Rev Time 0.35
Received By pkrauss Date 2005-05-16 Time 20:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-04 Cont ID  
Sent By pkrauss Date 2005-03-04 Time 11:42 Rev Time 0.35
Received By pkrauss Date 2005-03-04 Time 11:25 Sent To  
Notes
2005-03-04 00:00:00DENIED:
 1.PLEASE CLARIFY THE LOCATION OF THE
 RETURN AIR FOR BEDROOM #2.THE
 MECHANICAL PLAN REFLECTS ONLY ONE DOOR
 INTO THE BED/BATH/CLOSET AREA, WHEREAS
 PLAN SHEET A1.3.09 & A2.2.06 INDICATE AN
 ADDITIONAL DOOR INTO THE BEDROOM AREA.
 PLEASE CLARIFY.
  
 2.PLEASE INDICATE EQUIPMENT SCHEDULE
 WITH THE PLANS.
  
 3.NO COMBUSTIBLES ALLOWED IN THE
 MECHANICAL CLOSETS AS THE CLOSET APPEARS
 TO BE A RETURN AIR PLENUM.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-05-12 Cont ID  
Sent By kstevens Date 2005-05-12 Time 08:12 Rev Time 1.00
Received By kstevens Date 2005-05-09 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-19 Cont ID  
Sent By kstevens Date 2005-02-19 Time 17:10 Rev Time 1.00
Received By kstevens Date 2005-02-19 Time 17:10 Sent To  
Notes
2005-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) SHTS P-9A-CU & P-13 SUBMITTED FOR
 THIS PERMIT ARE REVISIONS TO THE BASE
 BUILDING PERMIT AND SHALL BE SUBMITTED
 AS REVISIONS UNDER PERMIT #03020961.
 PLEASE DELETE THESE SHEETS AND RESUBMIT
 FOR PERMIT. - WATER RISER DIAGRAM SHALL
 BE SUBMITTED ON A SEPARATE SHEET FOR
 THIS PERMIT ONLY. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]