Plan Review Details - Permit 05011337
Plan Review Stops For Permit 05011337
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-17 Cont ID  
Sent By nmccray Date 2005-02-17 Time 15:02 Rev Time 0.00
Received By nmccray Date 2005-02-17 Time 15:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By nmccray Date 2005-01-31 Time 14:53 Rev Time 0.00
Received By nmccray Date 2005-01-31 Time 14:33 Sent To  
Notes
2005-01-31 00:00:00DENIED:
  
 1) FIRE ALARM SYSTEMS THAT SUPERVISE
 FIRE SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 2) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSSABLE.
  
 3) THE WEST PALM BEACH FIRE MARSHAL
 OFFICE REQUIRES DUCT SMOKE DETECTORS TO
 SEND A GENERAL FIRE ALARM NOT A
 SUPERVISORY.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-17 Cont ID  
Sent By adarroug Date 2005-02-17 Time 11:28 Rev Time 0.00
Received By adarroug Date 2005-02-17 Time 11:28 Sent To FIRE
Notes
2005-02-17 00:00:00TO "F"BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 13:46 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 13:45 Sent To FIRE
Notes
2005-01-28 00:00:00TO "FIRE" BOX.