Plan Review Details - Permit 05011284
Plan Review Stops For Permit 05011284
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-31 Cont ID  
Sent By jwitmer Date 2005-03-31 Time 12:56 Rev Time 1.35
Received By jwitmer Date 2005-03-31 Time 12:56 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-08 Cont ID  
Sent By jwitmer Date 2005-02-08 Time 10:23 Rev Time 4.40
Received By jwitmer Date 2005-02-08 Time 10:23 Sent To PC
Notes
2005-02-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05011284
 ADD: 6430 SPARROW HAWK DRIVE
 CONT: RIF GROUP
 TEL: (561)239-5790
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY, BETWEEN, SHEETS A-4 & A-5,
 THE AREA OR ROOM LEADING FROM THE DEN/
 BEDROOM# 2 TO THE EXTERIOR, THE
 ELEVATIONS SHOW A ROOFED OVER AREA,
 WHEREAAS A-5 INDICATES NO ROOF IN THIS
 AREA, CORRECT.
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-4 VERSES A-5 AREA OR ROOM BY THE
 DEN/ BEDROOM# 2, A-4 ELEVATION SHOWS THE
 ROOF COVERING THIS AREA, A-5 ROOF
 FRAMING PLAN INDICATES THIS AREA BEING
 OPEN TO THE SKY.
  
 3) FRONT DOOR INDICATES THIS DOOR TO
 HAVE GLAZING, DISCUSSED WITH CONTRACTOR
 OVER THE PHONE THIS DOOR SHALL BE SOLID
 CORE, WILL SUBMIT NEW PRODUCT APPROVALS
 INDICATING SUCH, ARCHITECT WILL ALSO
 REVISE FRONT DOOR TO INDICATE SOLID
 CORE/ NO GLAZING.THIS WILL ACCOMPLISH
 COMPLIANCE WITH:FBC 1005.4.5
 (GLITCH AMENDMENTS JULY 1, 2003)
 REQUIRES AT LEAST ONE MEANS OF ESCAPE
 FROM A DWELLING WHEN SHUTTERED FOR
 IMPACT PROTECTION. THE MEANS OF ESCAPE
 SHALL BE WITHIN THE FIRST FLOOR OF THE
 DWELLING AND CAN NOT BE LOCATED IN A
 GARAGE. OCCUPANTS IN ANY PART OF THE
 DWELLING SHALL HAVE ACCESS TO IT WITHOUT
 HAVING TO PASS THROUGH A LOCKABLE DOOR
 NOT UNDER THEIR CONTROL. INDICATE HOW
 COMPLIANCE WILL BE ACHIEVED.
  
 4) SPOKE TO CONTRACTOR, WILL COME IN
 UNDER A SEPERATE PERMIT FOR STORM
 SHUTTERS. STORM SHUTTERS TO COMPLY
 WITH:
 4A) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 4B)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-11 Cont ID  
Sent By jleahy Date 2005-10-11 Time 14:35 Rev Time 0.30
Received By jleahy Date 2005-10-11 Time 14:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-21 Cont ID  
Sent By dpalmer Date 2005-07-21 Time 12:31 Rev Time 0.33
Received By dpalmer Date 2005-07-21 Time 12:31 Sent To  
Notes
2005-07-21 00:00:00REDLINED:
  
 SD'S SHOWN ON CIRCUIT 24 ON PLANS,
 HOWEVER PANEL SCHEDULE SHOWS GARAGE LTS
 FOR THIS CIRCUIT??REDLINED

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 10:24 Rev Time 0.50
Received By btrobaug Date 2005-01-28 Time 07:43 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 12:12 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 12:12 Sent To E
Notes
2005-10-06 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 14:05 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 14:05 Sent To E
Notes
2005-07-20 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-11 Cont ID  
Sent By adarroug Date 2005-03-11 Time 09:17 Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 09:17 Sent To B
Notes
2005-03-11 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-26 Cont ID  
Sent By mjacobs Date 2005-01-26 Time 17:47 Rev Time 0.00
Received By mjacobs Date 2005-01-26 Time 17:45 Sent To E
Notes
2005-01-26 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-26 Cont ID  
Sent By mjacobs Date 2005-01-26 Time 17:44 Rev Time 0.00
Received By mjacobs Date 2005-01-26 Time 17:44 Sent To Z
Notes
2005-01-26 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-22 Cont ID  
Sent By hmoser Date 2005-03-22 Time   Rev Time 0.00
Received By hmoser Date 2005-03-22 Time 14:23 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By pkrauss Date 2005-01-31 Time 12:39 Rev Time 0.35
Received By pkrauss Date 2005-01-31 Time 12:39 Sent To P
Notes
2005-01-31 00:00:00DENIED:
 TRANSFER GRILLES ARE NOT SIZED FROM THE
 MASTER SUITE & BEDROOM #3.THE R/A
 GRILLE FROM BEDROOM/DEN #2 IS INDICATED
 AS 8" X 8", WHICH IS NOT SIZED IN
 ACCORDANCE WITH 2001 FBC(M)601.4
 EXCEPTION #2.TRANSFER GRILLES ARE TO
 BE A MINIMUM OF 50 SQ INCHES PER 100 CFM
 OF SUPPLY AIR INTO THAT SPACE.PLEASE
 NOTE ALL AIR INTO THE MASTER SUITE IS TO
 BE INCLUDED FOR PROPER SIZING OF THE
 TRANSFER AIR GRILLE (INCLUDE ALL SUPPLY
 AIR INTO THE MASTER BEDROOM, BATHROOM
 AND CLOSET AREAS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-02-04 Cont ID  
Sent By kstevens Date 2005-02-04 Time 13:34 Rev Time 0.33
Received By kstevens Date 2005-02-04 Time 13:34 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-26 Cont ID  
Sent By mmclean Date 2005-01-26 Time 16:45 Rev Time 0.00
Received By mmclean Date 2005-01-26 Time 16:45 Sent To I
Notes
***NONE***