Plan Review Details - Permit 05010919
Plan Review Stops For Permit 05010919
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-01-20 Cont ID  
Sent By ptjomsto Date 2005-01-20 Time 14:36 Rev Time 0.00
Received By ptjomsto Date 2005-01-20 Time 14:36 Sent To  
Notes
2005-01-20 00:00:00EXT REQUIRED FOR 150A

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-17 Cont ID  
Sent By jwitmer Date 2005-05-17 Time 08:31 Rev Time 1.25
Received By jwitmer Date 2005-05-17 Time 07:37 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-04-01 Cont ID  
Sent By jwitmer Date 2005-04-01 Time 14:41 Rev Time 1.55
Received By jwitmer Date 2005-04-01 Time 14:41 Sent To  
Notes
2005-04-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010919
 ADD: 1801 PALM BCH LAKES# 150A
 CONT: PLAN REVIEW
 TEL: (281)579-2226
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 M-RETAIL ENGINEERING INC
 61G15-23.002 IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS
 THE NAME, ADDRESS, AND ENGINEERING
 BUSINESS NUMBER ( CERTIFICATE OF
 AUTHORIZATION) SHALL BE LEGIBLY
 INDICATED ON EACH SHEET.
  
 THE ENGINEERING PAGES G1.2, E1.0, E2.0
 & E4.0 ALL REQUIRE THE CORRECTION OF THE
  
 ENGINEERS CERTIFICATE OF AUTHORIZATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By jwitmer Date 2005-01-31 Time 10:11 Rev Time 1.55
Received By jwitmer Date 2005-01-31 Time 07:40 Sent To  
Notes
2005-01-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010919
 ADD: 1801 PALM BCH LAKES# 150A
 CONT: PLAN REVIEW
 TEL: (281)579-2226
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 M-RETAIL ENGINEERING INC
 61G15-23.002 IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS
 THE NAME, ADDRESS, AND ENGINEERING
 BUSINESS NUMBER ( CERTIFICATE OF
 AUTHORIZATION) SHALL BE LEGIBLY
 INDICATED ON EACH SHEET.
  
 3)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4)11-4.35.1 EVERY DRESSING ROOM OR
 FITTING ROOMREQUIRED TO BE ACCESSIBLE
 BY 11-4.1 SHALL COMPLY WITH 11-4.35 AND
 SHALL BE ON AN ACCESSIBLE ROUTE.
  
 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6) FL BLD CODE 104.2.1.2*
 ADDITIONAL INFORMATION REQUIRED, SHEET
 A1.2 DETAIL# 9B INDICATES FIRE RATED
 COLULNS WITH UL LISTING# X790 & D902,
 BUT THE THICKNESS OF INSULATION REQUIRED
 IS NOT PROVIDED, HOW WILL THE INSPECTOR
 DETERMINE IF THE INSULATION IS CODE
 COMPLIANT WITHOUT THIS INFORMATION
 PROVIDED?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-09 Cont ID  
Sent By dpalmer Date 2005-05-09 Time 11:35 Rev Time 0.25
Received By dpalmer Date 2005-05-09 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-28 Cont ID  
Sent By dpalmer Date 2005-03-28 Time 12:09 Rev Time 0.50
Received By dpalmer Date 2005-03-28 Time 12:09 Sent To  
Notes
2005-03-28 00:00:00*********UNSAT 2ND REVIEW ********
  
 1)NOTE; PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS.
 FAC 61G15-23.002, FS 471.023
  
 PLEASE SEE ONLY ONE SHEET WAS CORRECTED
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
  
 PLEASE SEE PLANS ARE ONLY IN FOR "PLAN
 REVIEW" AT THIS TIME.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-27 Cont ID  
Sent By dpalmer Date 2005-01-27 Time 08:53 Rev Time 0.50
Received By dpalmer Date 2005-01-27 Time 08:53 Sent To  
Notes
2005-01-27 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK PER FAC
 61G15-23.002 AND FS 471.023
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE RISER DIAGRAM, THIS
 SHOWS METER INSTALLED ON THE LOAD SIDE
 OF THE DISC?
  
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-05-12 Cont ID  
Sent By mwennerg Date 2005-05-12 Time 11:16 Rev Time 0.00
Received By mwennerg Date 2005-05-12 Time 11:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-02-09 Cont ID  
Sent By mwennerg Date 2005-02-09 Time 11:31 Rev Time 0.00
Received By mwennerg Date 2005-02-09 Time 11:19 Sent To  
Notes
2005-02-09 00:00:001) PLEASE BE ADVISED THAT ALL LIFE
 SAFETY MUST COMPLY WITH THE 2003
 EDITION AFTER JANUARY 1, 2005.
  
 2) PLEASE SUBMIT SHOP DRAWINGS FOR THE
 FIRE ALARM AND FIRE SPRINKLER REMODEL.
  
 3) PLEASE BE ADVISED THAT 2A-10BC FIRE
 EXTINGUISHERS ARE TO BE MOUNTED NOT TO
 EXCEED 5 FEET FROM THE FLOOR SURFACE
 WITH NOT MORE THAN 75 FEET TRAVEL
 DISTANCE.
  
 MIKE WENNERGREN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 13:25 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 13:25 Sent To  
Notes
2005-07-11 00:00:00TO "COMM" BD#18
2005-07-05 00:00:00WAITING FOR SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 09:04 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 09:04 Sent To B
Notes
2005-07-05 00:00:00TO "JWITMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-04-27 Time 11:44 Rev Time 0.00
Received By adarroug Date 2005-04-27 Time 17:07 Sent To  
Notes
2005-05-11 00:00:00TO "COMM" BD#3
2005-05-03 00:00:00IN INCOMING/AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 13:22 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 13:22 Sent To  
Notes
2005-03-23 00:00:00TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 15:23 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 15:23 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#18

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-20 Cont ID  
Sent By hmoser Date 2005-07-20 Time 16:13 Rev Time 0.00
Received By hmoser Date 2005-07-20 Time 16:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-07-19 Cont ID  
Sent By hmoser Date 2005-07-19 Time 08:46 Rev Time 0.00
Received By hmoser Date 2005-07-19 Time 08:26 Sent To  
Notes
2005-07-19 00:00:00PLAN DENIED
 PLEASE PROVIED TWO SETS OF SEALED PLANS
 WITH SIGNATURES PER SECTION 104.2.1 FBC.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-02 Cont ID  
Sent By hmoser Date 2005-04-02 Time   Rev Time 0.00
Received By hmoser Date 2005-04-02 Time 11:47 Sent To  
Notes
2005-04-02 00:00:00PRIVIAO
 PLEASE REFER TO SECTION 606.4.1 FLORIDA
 BUILDING CODE (M).IF THERE IS NO FIRE
 ALARM SYSTEM YOU MUST HAVE HORN AND
 STROBE WITH FAN SHUTDOWN.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By pkrauss Date 2005-01-31 Time 14:45 Rev Time 0.00
Received By hmoser Date 2005-04-02 Time 11:46 Sent To  
Notes
2005-01-31 00:00:00DENIED:
 1.DUCT SMOKE DETECTOR IS INDICATED ON
 THE RETURN AIR.PER 2001 FBC(M)606.2.1
 AND NFPA 90A6.4.2.1 (1), DUCT SMOKE
 DETECTORS SHALL BE INSTALLED IN THE
 SUPPLY AIR DUCT.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M)602.2.1.
  
 3.PLEASE NOTE THE ENERGY CALCULATIONS
 SHOW MAXIMUM TONNAGE AS 0.PLEASE
 CLARIFY.
  
 4.SEE COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLANS EXAMINER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-20 Cont ID  
Sent By kstevens Date 2005-07-20 Time 18:31 Rev Time 0.60
Received By kstevens Date 2005-07-20 Time 18:31 Sent To  
Notes
2005-07-20 00:00:00REVISION OK - CHANGED THE PIPING LAYOUT
 AND SANT. RISER DIAGRAM FOR THE TOILET
 ROOM. SHT M-2

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-25 Cont ID  
Sent By kstevens Date 2005-03-25 Time 18:56 Rev Time 0.95
Received By kstevens Date 2005-03-25 Time 18:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-19 Cont ID  
Sent By kstevens Date 2005-02-19 Time 13:45 Rev Time 0.75
Received By kstevens Date 2005-02-19 Time 13:45 Sent To  
Notes
2005-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET, AND IF PRACTICING THROUGH
 A DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHROIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025. -
 SIGNATURE REQUIRED - NO INITIALS PER
 FDPE,S RULING.
 2) PERSONAL SIGNATURE OF THE ARCHITECT
 REQUIRED. G1G1-16.003 FS 481.2055 - THE
 FOLLOWING INFORMATION MISSING FROM
 REQUIRED TITLE BLOCK: 61G1-16.004
 (2) FIRM LICENSE NUMBER
 (6) PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT. FS 481.219 (CERTIFICATE OF
 AUTHORIZATION).
 3) SHT D1.0 IN THE REMOVAL OF ANY PART
 OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5. ALL DEMO'D
 PIPING SHALL NOT BE COVERED PRIOR TO
 INSPECTION.
 4) THE FOLLOWING INFORMATION IS REQUIRED
 ON THE PLANS TO SHOW COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22:
 A) CLEAR FLOOR SPACE W/C 11-4.16.2
 (TURNING AREA IS NOT CLEAR FLOOR SPACE)
 B) FLUSH CONTROLS W/C (WIDE SIDE)
 11-4.16.5.
 C) HEIGHT OF LAV (34") 11-4.19.2
 5) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A) SPOUT HEIGHT 11-4.15.2
 B) CLEARANCES/CLEAR FLOOR SPACE
 11-4.15.5
 6) SHT M2.0 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTOR SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 7) SHT M2.0 WATER HEATER DETAIL.
 EMERGENCY HEATER PAN DRAIN AND P&T VALVE
 DISCHARGE LINE SHALL DRAIN TO A HUB
 DRAIN OR A FLOOR SINK. FLOOR DRAINS ARE
 NOT AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTIONS 802.3 & 802.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]